Kobold MWD User manual

DT0621 page 1
Operating Instructions
for
Temperature Sensor
Model MWD

MWD
page 2 DT0621
1 Contents
1 Contents ............................................................................................................................................. 2
2 Note .................................................................................................................................................... 3
3 Instrument Inspection ......................................................................................................................... 3
4 Regulation Use ................................................................................................................................... 3
5 Operating Principle ............................................................................................................................. 4
6 Electrical connection ........................................................................................................................... 4
6.1 Sensor wiring diagram with head ............................................................................................... 4
6.2 Sensor wiring diagram without head .......................................................................................... 5
6.3 Transmitter wiring diagram ......................................................................................................... 6
6.4 Head model E wiring diagram .................................................................................................... 6
6.5 Head model D wiring diagram .................................................................................................... 7
6.6 Head model R wiring diagram .................................................................................................... 7
7 Maintenance and repairs .................................................................................................................... 8
8 Storage ............................................................................................................................................... 8
9 Technical Details ................................................................................................................................. 8
9.1 Sensor wiring .............................................................................................................................. 8
9.2 Sensor according to IEC 60751 .................................................................................................. 8
9.3 Tolerance class ........................................................................................................................... 8
9.4 General details ............................................................................................................................ 8
9.5 Transmitter 5333D ...................................................................................................................... 9
9.6 Transmitter 5337D ...................................................................................................................... 9
9.7 Transmitter 5350A ...................................................................................................................... 9
9.8 Display type E ............................................................................................................................. 9
9.9 Display type D/R ....................................................................................................................... 10
10 Trouble Shooting ........................................................................................................................... 11
11 Dismounting, return and disposal ................................................................................................. 12
11.1 Dismounting .............................................................................................................................. 12
11.2 Disposal .................................................................................................................................... 12
12 Order codes .................................................................................................................................. 12
13 EU-Declaration of conformity ........................................................................................................ 13
14 UK Declaration of Conformity ....................................................................................................... 14
Manufactured by:
Kobold Mesura S.L.U
Avda. Conflent 68 nave 15
08915 Badalona
Tel.: +34 93 460 38 83
Fax: +34 93 460 38 76
E-Mail: info.es@kobold.com
www.kobold.com
Edition: May 2022

MWD
DT0621 page 3
2 Note
Please read these operating instructions before unpacking and putting the unit in
operation. Follow the instructions precisely as described herein.
The instruction manuals on our website WWW.kobold.com are always for currently
manufactured version of our products. Due to technical changes, the instruction
manuals available online may not always correspond to the product version you
have purchased. If you need an instruction manual that correspond to the
purchased product version, you can request it from us free of charge by email
([email protected]) in PDF format, specifying the relevant invoice number and
serial number. If you wish, the operating instructions can also be sent to you by
post in paper form against an applicable postage fee.
The devices are only to be used, maintained and serviced by persons familiar with
these operating instructions and in accordance with local regulations applying to
Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the
machines fulfil the EC-machine guidelines.
3 Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition.
Should damage to a device be visible, we recommend a thorough inspection of the
delivery packaging. In case of damage, please inform your parcel service /
forwarding agent immediately, since they are responsible for damages during
transit.
Scope of delivery:
The standard delivery includes:
Device model: MWD
4 Regulation Use
The temperature sensors of the MWD Series are suitable for all applications where
processes involving fluids, solid bodies or materials, or gases, require temperature
recording and measurement. Our temperature sensors are suitable for use in the
following industrial areas: chemicals, petrochemicals, water, feed, food, sanitary,
etc.
Any use of the Temperature Sensor, model: MWD, which exceeds the
manufacturer’s specification may invalidate its warranty. Therefore, any resulting
damage is not the responsibility of the manufacturer. The user assumes all risk for
such usage.

MWD
page 4 DT0621
5 Operating Principle
Resistance thermometers work by using the continuous change of resistance of
metals subject to temperature rising and decreasing. The most common resistance
material used is platinum, as it is very stable and has very good repeatability. The
temperature coefficient of platinum is positive, so its resistance increases as the
temperature rises. This property is defined in the IEC751 standard, which defines
measurements deviations categories A and B.
6 Electrical connection
6.1 Sensor wiring diagram with head

MWD
DT0621 page 5
6.2 Sensor wiring diagram without head
2 wire
3 wire
4 wire

MWD
page 6 DT0621
6.3 Transmitter wiring diagram
6.4 Head model E wiring diagram

MWD
DT0621 page 7
6.5 Head model D wiring diagram
6.5.1 With transmitter 5333D
6.5.2 With transmitter 5337D
6.6 Head model R wiring diagram
6.6.1 With transmitter 5333D
6.6.2 With transmitter 5337D

MWD
page 8 DT0621
7 Maintenance and repairs
The instrument does not require maintenance or servicing.
Repairs must be only carried out by Kobold (manufacturer)
8 Storage
Measuring instruments should be protected against humidity and dust.
Storage temperature: -40 ºC…+85 ºC for sensors without transmitter.
Storage temperature: See manual of the corresponding transmitter and display
mode
9 Technical Details
9.1 Sensor wiring
- 2 wires Error due to the lead resistance of the sensor
- 3 wires With connecting wires up to 25 m, lead resistance is negligible.
- 4 wires The lead resistance of the connecting wires is negligible
9.2 Sensor according to IEC 60751
-Class B
-Class A
-Class 1/3
-Class 1/10
The nominal value of Pt100 sensors is 100Ω at 0 ºC.
9.3 Tolerance class
-Class B ±0.3 + 0.005 * t
-Class A ±0.15 + 0.002 * t
-Class 1/3 ±0.10 + 0.005 * t
-Class 1/10 ±0.03 + 0.0017 * t
t= measuring temperature in ºC without sign
9.4 General details
Ambient temperature: -40…+150 ºC with ceramic terminal block
-40…+85 ºC with transmitter

MWD
DT0621 page 9
9.5 Transmitter 5333D
Ambient temperature: -40...+85 ºC
Power supply: 8...35 V
Accuracy: Absolute accuracy ≤ ±0.3 ºC
Temp. Coefficient (≤ ±0.01 ºC/ºC)
Current Output: 4...20 mA
Load resistance: ≤ (V supply - 8) / 0.023
Sensor error detection: Programmable 3.5…23 mA
NAMUR NE43 Upscale and
NAMUR NE43 Downscale
9.6 Transmitter 5337D
Ambient temperature: -40...+85 ºC
Power supply: 8...35 V
Accuracy: Absolute accuracy ≤ ±0.1 ºC
Temp. Coefficient (≤ ±0.005 ºC /ºC)
Current Output: 4...20 mA HART®
Load resistance: ≤ (V supply - 8) / 0.023
Sensor error detection: Programmable 3.5…23 mA
NAMUR NE43 Upscale and
NAMUR NE43 Downscale
9.7 Transmitter 5350A
Ambient temperature: -40...+85 ºC
Power supply: 9...32 V
Accuracy: Absolute accuracy ≤ ±0.1 ºC
Temp. Coefficient (≤ ±0.002 ºC / ºC)
Output: PROFIBUS
® PA protocol
FOUNDATIONTM FIELDBUS protocol
9.8 Display type E
Ambient temperature: -40...+85 ºC
Supply Voltage: 7.5...45 V
Accuracy: High accuracy 0.02% of span
for Pt100 sensor
Output signal: 4...20 mA HART®
Load: ≤ (V
supply - 7.5 V)/0.022 A
Sensor error detection: According to the guidelines in
NAMUR NE89

MWD
page 10 DT0621
9.9 Display type D/R
Ambient temperature: -30...+80 ºC
Loop voltage drop: Two levels depending on chosen
backlight brightness at 20 mA:
low bright backlight (<40%):
max. 4 V at 23 ºC
high bright backlight (>40%)
max. 6.5 V at 23 ºC
Accuracy: ≤ ±0.1% of input span within
-10...70 ºC
≤ ±0.2% of input span within
-30...-10 ºC/70...80 ºC
Measuring range: 4...20 mA
Error/warning indication: Individually configurable display
and backlight indication in white,
green or red colour, steady or
between 3.5 and 23 mA
Relay (only type R): Contacts 2 solid state relays
Max. Voltage 60 Vp
Max. Load current 75 mA
Note: For programming of transmitter and/or display please refer to their separates
programming manual.

MWD
DT0621 page 11
10 Trouble Shooting
Faults Possible Causes Corrective actions
No signal/line breakage Mechanical load too high or
over temperature.
Line breakage.
Replace probe or measuring
insert.
Check wiring.
Wrong measured values
Sensor drift caused by over
temperature
Replace probe or measuring
insert.
Sensor drift caused by
chemical attack
Use a sensor with thermowell
Wrong measured values
(too low)
Entry of moisture into cable or
measuring insert
Replace probe or measuring
insert.
Wrong measured values
and response times too long
Wrong mounting geometry, for
example mounting depth too
deep or heat dissipation too
high
The temperature-sensitive
area of the sensor must be
inside the medium, and
surfaces must be isolated.
Deposits on the sensor or
thermowell
Remove deposits
Oscillation of measured
value
Cable break in connecting
cable or loose contact caused
by mechanical overload
Replace probe or measuring
insert with a suitable design,
for example equipped with a
strain relief or a thicker
conductor cross-section.
Check wiring
Corrosion
Composition of the medium
not as expected or modified
or wrong thermowell material
selected
Analyze medium and then
select a more-suitable material
or replace thermowell
regularly
Signal interference
Stray currents caused by
electric fields
or ground loops
Use of screened connecting
cables,
increase the distance to
motors and
power lines
Ground loop
Elimination of potentials, use
of galvanic isolated transmitter
supply isolators or transmitters

MWD
page 12 DT0621
11 Dismounting, return and disposal
11.1 Dismounting
Residual media in dismounted instruments can result in a risk to persons, the
environment and equipment. Take sufficient precautionary measures.
All instruments delivered to KOBOLD must be free from any kind of hazardous
substances (acids, bleaches, solutions, etc.).
11.2 Disposal
Incorrect disposal may endanger the environment.
12 Order codes
For order codes information, please see the technical datasheet.

MWD
DT0621 page 13
13 EU-Declaration of conformity
DT0621
DECLARACIÓN DE CONFORMIDAD EU
EU DECLARATION OF CONFORMITY
EU-KONFORMITÄTSERKLÄRUNG
DÉCLARATION DE CONFORMITÉ EU
DICHIARAZIONE DI CONFORMITÀ EU
KOBOLD MESURA S.L.U.
Avda. Conflent 68 nave 15, 08915 Badalona (España)
Declara, bajo la propia responsabilidad, que el producto
Declares under our sole responsibility, that the product
Erklärt in alleiniger Verantwortung, daß das Produkt
Déclare sous sa seule responsabilité, que le produit
Dichiara sotto la propia responsabilità, che il prodotto
MWD........
A los cuales se refiere esta declaración, son conformes a las siguiente Directivas Europeas
:
To which this declaration relates is in conformity with the following European Directives:
Mit folgenden Richtilinien konform ist:
À auxquels se réfère cette déclaration, ils sont conformes aux Directives Européennes suivant :
A ai quali si riferisce questa dichiarazione, sono conformi alle direttive europee seguente:
EMC2014/30/EU LVD2014/35/EU RoHS2011/65/EU
Normas armonizadas y documentos de la normativa aplicados:
Applied harmonised standards and normative documents:
Angewandte harmonisierte Normen oder normativer Dokumente:
Normes harmonisées et documents normatifs appliqués
Norme armonizzate e documenti normativi applicati:
EN 61010-1:2011, EN 61000-6-2:2019, EN 60529:2018, IEC 61010-1:2016,
IEC 61326-1:2021, IEC 60751:2022
Fabricado en
:
KOBOLD MESURA SLU Avda. Conflent 68, nave 15 08915 BADALONA (Spain
)
Made in:
Hergesteltlt in:
Fabriqué dans:
Fabbricato in:
Badalona 22 june 2016 Gerente
DT0621
Azzam Chamand

MWD
page 14 DT0621
14 UK Declaration of Conformity
DT0672
DECLARACIÓN DE CONFORMIDAD UK
UK DECLARATION OF CONFORMITY
UK-KONFOMITÄTSERKLÄRUNG
DÉCLARATION DE CONFORMITÉ UK
DICHIARAZIONE DI CONFORMITÀ UK
KOBOLD MESURA SLU
Avda. Conflent, 68 nave 15 08915 Badalona (España)
We Kobold Mesura S.L.U. declare under our sole responsibility that the product:
Temperature sensor
MWD…
To which this declaration relates is in conformity with the standards noted below:
BS EN 61010-1:2010
Safety requirements for electrical equipment for measurement,controL, and laboratory use. General
requirements
BS EN 61000-6-2:2019
Electromagnetic compatibility (EMC) -- Part 6-2: Generic standards - Immunity for industrial
environments
BS EN IEC 61326-1:2021
Electrical equipment for measurement, control and laboratory use. EMC requirements. General
requirements
BS EN IEC 60751:2019
Industrial platinum resistance thermometers and platinum temperature sensors
Also, the following UK guidelines are fulfilled:
S.I. 2016/1091 Electromagnetic Compatibility Regulations 2016.
S.I. 2016/1101 Electrical Equipment (Safety) Regulations 2016.
S.I. 2012/3032 The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic
Equipment Regulations 2012.
Badalona May 2022 Gerente

MWD
DT0621 page 15
KOBOLD MESURA S.L.U
Avda. Conflent 68 nave 15
08915 Badalona
Tel.: +34 93 460 38 83
Fax: +34 93 460 38 76
E-Mail: [email protected]
www.kobold.com
Technical data
Subject to change without prior notice
Table of contents
Other Kobold Temperature Controllers manuals