15
6 Setup with the integrated display and adjustment unit
SU 600 • 4 … 20 mA signal conditioning instrument
30652-EN-150129
measuring transducers without separate operating voltage (sensor
in two-wire version).
• In passive mode, the sensors are not powered, only the measure-
ment value is transmitted. This mode is provided for connection of
transmitters with their own separate operating voltage (sensors in
four-wire version).
→ Set the function switch to position [F] and select the suitable
mode with the [+/-] keys. Save your settings by pushing both keys
simultaneously.
Whenapressuretransmitterisused,anosetcorrectionshouldbe
carriedoutrst.Theseinstrumentsarefactory-setinacertainposi-
tion.Ifthepressuretransmitterisnowmountedinadierentposition,
itsmeasuringrangeisshiftedslightly.Thezeropointisreadjustedby
carryingouttheosetcorrectioninuncovered(unpressurised)condi-
tion.The complete measuring range will be shifted by the deviating
amount.
1. Make sure that the pressure transmitter is completely unpressur-
ised,uncovered(unimmersed)andmountedinitsnalposition.
2. Set the function switch to position [A].The display indicates now
the actual sensor current in mA. Save the current status by push-
ing the [+/- ] keys simultaneously.
For this adjustment procedure, two sensor current values
(4 … 20 mA) must be entered corresponding to the levels 0 % and
100 %.
Whenusingapressuretransmitter,anosetcorrectionshouldbecar-
riedouttoreachmaximumaccuracy.Carryoutthisosetcorrection
before adjustment and with the sensor uncovered (unimmersed).
→ Now select the position [D] or [E] on the function switch, enter the
current values in mA for min. or max. adjustment and save your
settings.
During this adjustment procedure, the current level is assigned to
a certain percentage value. For this reason, percentage values that
correspondtotheactualllinglevelsmustbeenteredforthemin.and
max. adjustment. The ideal calibration is at 0 % and 100 %. Because
itisnotalwayspossibletoemptyorllavesselcompletely,anyvalue
canofcoursebeentered.Thegreaterthedierencebetweenthetwo
adjustment points, the more precise the measurement. It does not
matterwhichvalueisenteredrst.
→ Select position [B] or [C] on the function switch, enter the per-
centage values for the min. and max. adjustment and save your
settings.
Two operating relays are integrated inSU 600 for level detection. First
of all, determine at which switching points the relays should switch on
andoagain.Furthermoreyouhavetodistinguishbetweentherelay
modesoverllanddryrunprotection.Youswitchoverbyexchanging
the ON/OFF values of the relay.
Osetcorrection
Adjustment in mA without
changing the level
Adjustment in % by
changing the level
Relay outputs