GB-7
Technical data
Gas types: natural gas, LPG (gaseous), biogas (max.
0.1%-by-vol. H2S) or clean air; other types of gas
on request.
The gas must be clean and dry in all temperature
conditions and must not contain condensate.
Max. inlet pressure pu:
max. 500mbar (7.25psig).
Leakage rate: ≤500cm3/h (0.132gal/h).
Closing time: quick closing: <1s.
Medium and ambient temperatures:
-20 to +50°C (-4 to +122°F).
No condensation permitted.
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact
manufacturer).
Storage temperature: -20 to +40°C (-4 to +104°F).
Enclosure: IP65.
Valve housing: aluminium, valve seal: NBR.
Connection flanges with internal thread:
Rp to ISO7-1, NPT to ANSI/ASME.
Class A, Group 2 safety valve pursuant to
EN13611 and EN 161.
Mains voltage:
230 V AC, +10/-15%, 50/60 Hz;
200 V AC, +10/-15%, 50/60 Hz;
120 V AC, +10/-15%, 50/60 Hz;
100 V AC, +10/-15%, 50/60 Hz;
24 V DC, ±20%.
Cable gland: M20 x 1.5.
Electrical connection:
electrical cable with max. 2.5mm2(AWG12) or
plug with socket to EN175301-803.
Power consumption:
Type Voltage Power
VAN 1
24 V DC 25 W –
100 V AC 25 W (26 VA)
120 V AC 25 W (26 VA)
200 V AC 25 W (26 VA)
230 V AC 25 W (26 VA)
VAN 2
24 V DC 36 W –
100 V AC 36 W (40 VA)
120 V AC 40 W (44 VA)
200 V AC 40 W (44 VA)
230 V AC 40 W (44 VA)
Switching frequency: max. 15x per minute,
duty cycle: 100%.
Power factor of the solenoid coil: cos φ = 0.9.
Closed position switch contact rating:
Type Voltage
Min. current
(resistive
load)
Max. cur-
rent (resis-
tive load)
VAN..S 12 – 250VAC,
50/60 Hz 100 mA 3 A
VAN..G 12 – 30VDC 2 mA 0.1 A
Closed position switch switching frequency:
max. 5x per minute.
Switching
current [A]
Switching cycles*
cos φ = 1 cos φ = 0.6
0.1 500,000 500,000
0.5 300,000 250,000
1200,000 100,000
3100,000 –
* Limited to max. 200,000 cycles for heating systems.
Air flow rate Q
Air flow rate Q for a pressure loss of ∆p= 1mbar
(0.4"WC)
1 x VAN
∆p 1 mbar (0.4 "WC)
Type Air flow rate
Q [m3/h] Q [SCFH]
VAN 110 4.4 155.4
VAN 115 5.6 197.7
VAN 120 8.3 293.1
VAN 125 10.0 353.1
VAN 225 15.5 547.3
VAN 232 19.5 688.5
VAN 240 21.0 741.5
VAN 250 22.5 794.5
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN 13611, EN 161 for VAN:
Type Designed lifetime
Switching cycles Time [years]
VAN 110 –
VAN 225 500,000 10
VAN 232 –
VAN 250 200,000 10
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu-
lations.