VAS1–3 · Edition 01.21
EN-2
CHECKING THE USAGE
Gas solenoid valves VAS for safeguarding gas or air on
various appliances. Double solenoid valves VCS are
combinations of two gas solenoid valves.
This function is only guaranteed when used within the
specified limits – see page 13 (Technical data). Any
other use is considered as non-compliant.
Type code
VAS Solenoid valve for gas
1-3 Sizes
–Without flange
10–65 Inlet and outlet flange nominal size
RRp internal thread
FFlange to ISO 7005
NNPT internal thread
/N Quick opening, quick closing
/L Slow opening, quick closing
WMains voltage 230V AC, 50/60Hz
QMains voltage 120V AC, 50/60Hz
KMains voltage 24V DC
PMains voltage 100V AC, 50/60Hz
YMains voltage 200V AC, 50/60Hz
SWith PS and visual position indicator
GWith PS for 24V and visual position
indicator
RViewing side: right
LViewing side: left
Part designations
VAS..G
5
3
1
6
7
4
2
1 Solenoid actuator
2 Flow body
3 Connection box
4 Connection flange
5 Closed position indicator
6 Connection parts
7 Sealing plug
Type label
Mains voltage, electrical power consumption, ambient
temperature, enclosure, inlet pressure and installation
position: see type label.
Elster GmbH
Osnabrück, Germany
Vxx
.XXXX
INSTALLATION
CAUTION
Incorrect installation
Please observe the following to ensure that the
unit is not damaged during installation and oper-
ation:
–Sealing material and dirt, e.g. thread cuttings,
must not be allowed to get into the valve
housing.
–A filter must be installed upstream of every
system.
–Dropping the device can cause permanent
damage. In this event, replace the entire device
and associated modules before use.
–Do not clamp the unit in a vice. Only secure the
flange by holding the octagon with a suitable
spanner. Risk of external leakage.
–It is not permitted to install gas solenoid
valveVAS downstream of flow rate regula-
torVAH/VRH and upstream of fine-adjusting
valveVMV. The VAS would no longer be able to
perform its function as a second safety valve if
installed in the above-mentioned position.
–If more than three valVario controls are installed
in line, the controls must be supported.
–Solenoid valves with overtravel switch and visual
position indicator VAS..SR/SL: actuator cannot
be rotated.
–In the case of double solenoid valves, the
position of the connection box can only be
changed by removing the actuator and
reinstalling it rotated by 90° or180°.
➔
When joining two valves, determine the position
of the connection boxes, push through the knock-
outs in the connection boxes and install a cable
gland set before installation in the pipework, see
accessories, cable gland set for double solenoid
valves.
➔
Install the unit in the pipe free of mechanical stress.
➔
For retrofitting a second gas solenoid valve, use the
double block seal instead of O-rings. The double
block seal is supplied with the seal set, see acces-
sories, seal set for sizes1–3.
➔Installation position: black solenoid actuator in the
vertical upright position or tilted up to the horizontal,
not upside down. In humid environments: black
solenoid actuator in the vertical upright position only.