INSTRUCTION / TROUBLESHOOTING MANUAL FOR MODEL A70B
PAGE 8 OF 16
In the normal mo e, the charger will charge the battery for 3 hours after the 80% point is reache (unless the
rate program terminates the charge first) or the battery is isconnecte . In the equalize mo e, a 6 hour timer
is initiate after the 80% point is reache .
A momentary equalize switch is provi e so that equalizing may be selecte to give a 6 hour charge after the
80% point is reache . Equalizing shoul be one perio ically as recommen e by battery manufacturer. This
switch, when activate , will start the equalize charge mo e for that cycle only. After completion of the cycle,
the charger will automatically be reset to the "normal" mo e.
When the 80% point is reache , the 80% charge lamp will flash at a one secon rate. At this point, the timer
in the microprocessor is set for 3 or 6 hours epen ing on whether or not the equalize mo e is active. The
charger will continue the trickle rate until the microprocessor control turns unit completely off. When a charging
cycle is complete correctly, the 80%/Complete light will in icate until the battery is unplugge . Unplugging a
charge (charge complete light "On") battery will place the unit back in the autostart mo e.
Disconnecting the output connector while a battery is being charged is not recommended If the
battery is isconnecte uring a charge cycle, the complete light will not light, all timers will reset, an the unit
will go into the autostart mo e.
If the battery never reaches the 80% charge point ( ue to battery failure), the unit will turn off in 12 hours
from the overri e timer. The complete light will not light. The "ON CHARGE" light will turn off, the "FAILURE"
lamp will light an the isplay will in icate "0004." If this occurs, the unit will not autostart. The on/off switch
will have to be turne off to reset the lights an turne back on to initiate the autostart mo e. If the AC input
voltage goes below the AC voltage set point, the unit will stop an the failure lamp will light. When the AC is
restore , the unit will turn on again an resume the charge where is left off. A high voltage con ition will also
cause the failure light to come on. (0001 - Low AC voltage, 0002 - High AC voltage)
After starting, the microprocessor imme iately activates the 12 hour overri e timer. This timer is in epen ent
of battery con itions an overri es all other timing functions. The overri e timer will terminate the charge in
the event that the rate control or the 80% timing control oes not terminate the charge before the maximum
time limit of 12 hours is reache .
If the AC input line fails uring the charge cycle, all internal time registers will hol their count until the power
returns. The cycle will then resume from where it left off. The "FAILURE" lamp will light if this con ition is
reache an , epen ing on a low or high AC line, a "0001" (low) or "0002" (high) will in icate on the isplay.
Optional remote start inputs can be provi e so that the charger start up an timer initiation may be controlle
from elsewhere. The battery an "Autostart" con itions must, however, still be met.
A start up elay (measure from the time of vali battery connection) can be pre-selecte by a printe circuit
boar switch for 0,1,4, or 8 hours. This elay will operate both in the normal or equalize mo es. When the
start up elay is active, the "ON CHARGE" light will flash at a one secon rate until the elay is complete an
the igital isplay will show how much time remains until the charger will turn on. Upon completion of the
elay, the charger will perform the "Autostart" function.
A high DC current, high DC voltage feature is incorporate in the charge control system. If an unusually high
DC current occurs simultaneously with a high voltage con ition as a result of a charger malfunction, the high
current feature will terminate the charge cycle an turn on the "FAILURE" light. A "0005" will in icate on the
igital isplay. In this mo e the charger will not restart again unless the on/off switch is toggle to the "off"
an then to the "on" position. If the high current failure still exists the charger will again turn off.
At this
point, a factory service representative should be contacted