LAMILUX AdComNet RZN4408-K User manual

Anerkennungs-Nr.
approval-no.
G 506001 0786 - CPR - 50382
EN 12101-10 : 2005/AC:2007
conform Zertifikat-Nr.
certificate-no.
B 06 05 22802 024
CNBOP-PIB
2265/2014 AT-0401-0382/2013
CNBOP-PIB
2921/2014
RZN 4408-K
Original instructions
AdComNet ready
®
RZN 4408-K
(ZP RZN 4408-K + GEH-KST)
RZN 4404-M
(ZP RZN 4404-M + GEH-KST)
RZN 4408-M
(ZP RZN 4408-M + GEH-KST)
RZN 4408-KS
(ZP RZN 4408-K + GEH-S-RWA)
RZN 4404-MS
(ZP RZN 4404-M + GEH-S-RWA)
RZN 4408-MS
(ZP RZN 4408-M + GEH-S-RWA)

RZN 4408-K
99.822.96 3.4/08/16
2/36
Table of contents
Introduction / Assembly scheme.................................................................................................................19
Intended use / Safety notes........................................................................................................................20
SHEV opening ............................................................................................................................................20
Servicetimer................................................................................................................................................20
Important regulations / Repair and cleaning...............................................................................................20
Declaration of Conformity / Disposal ..........................................................................................................20
Technical data.............................................................................................................................................21
Emergency supply ......................................................................................................................................21
Pictogram explanation ................................................................................................................................21
Mounting of SHEV control panel with housing GEH-KST...........................................................................22
View motherboard.......................................................................................................................................23
DIP switch settings ................................................................................................................................24-25
Cables for D+H smoke an heat vent systems / Wiring plan (Paragon) ......................................................26
230 V supply...............................................................................................................................................27
Connection overview ..................................................................................................................................27
Connection of smoke vent buttons .............................................................................................................28
Connection of fire detector / Connection of fiire alarm system ..................................................................29
Connection of magnetic clamps..................................................................................................................29
Drives .........................................................................................................................................................29
Informations for starting..............................................................................................................................30
Operation...............................................................................................................................................31-33
Inspection / Maintenance............................................................................................................................34

99.822.96 3.4/08/16
RZN 4408-K
19/36
Assembly scheme
Wind / Rain transmitter
Room temp. control
Window drive
SHEV button
SHEV control panel
Ventilation button
Fire detector External control
SHEV opening
Line
Group
Line
Group
OK
OK
OK
OK
Introduction
D+H service and sales partners
Safety in the building not only comes from the
product. Above all, safety results from competence.
All D+H service and sales partners are certified and
regularly trained specialist SHEV businesses.
Working closely with D+H Mechatronic AG as the
manufacturer, they develop comprehensive system
solutions for SHEVs and natural building ventilation.
With integral customer support and continuous
quality assurance in all phases of the project: from
sales advice, planning and project management
through to installation, commissioning, repair and
service. The highest national and international
quality standards are therefore reliably fulfilled.
Installation and operation
The comprehensive network of D+H service and
sales partners is at your disposal to professionally
install your system and commission it. Our partner
system guarantees that D+H products are installed
exclusively by trained and experienced fitters, in
compliance with the technical guidelines and
specifications. Personal handover and training for
users is included.
Maintenance and repair
Every building operator is responsible for ensuring
that its safety equipment works reliably. Regular and
professional maintenance ensures that your system
is always operational. As specialist SHEV
businesses, the D+H service and sales partners are
best qualified to carry out maintenance. By taking out
a maintenance contract, operators can prove at all
times that they have fulfilled their obligations.
Quality with guarantee
For all D+H SHEV systems, which have been
installed by a D+H service and sales partner and are
regularly serviced, you will receive extended
warranty services. Ask your local D+H service and
sales partner about this.
Always nearby
With the network of our own subsidiaries and
exclusive partners, we are represented nearly all
over the world.
Are you looking for your local D+H partner?
Simply visit our website:
www.dh-partner.com

99.822.96 3.4/08/16
20/36
RZN 4408-K
Intended use
- SHEV control panel for small up to medium sized
building objects
- Applicable in theAdComNet® SHEV bus system
- Microprocessor based control panel
- 1 or 2 lines, 2 or 3 groups
- 4A or 8A actuating current
- Comfort functions for daily ventilation
- Only for inside mounting
O2VC!perating voltage 30 A
Risk of injury from electric shock!
- Connection has to be carried out only by an
authorized electrical specialist
- Only for inside mounting
- Just use unchanged original D+H parts
Safety notes
Smoke gases are to be carried off as unhindered
as possible through smoke and heat vent opening
in case of fire. Size, kind and arrangement of the
opening is of decisive significance for an optimal
effect of the smoke and heat vent system.
These requirements are defined in the relevant
regulations of the respective country.
More informations, are also available under
www.rwa-heute.de.
The SHEV opening should be coordinated with the
responsible fire protection authority.
SHEV opening
An overdue maintenance of the system will be
indicated by the control panel after about ca. 14 to
16 months.
The yellow LED in the smoke vent button and the
green LED (D6) in the control panel will start
flashing.
A malfunction of the smoke vent system will be still
indicated by the extinction of the green LED in the
smoke vent button.
After the maintenance time is expired (approx. 14
to 16 months), the ventilation function OPEN can
be interrupted depending on the presetting of the
service timer.
Attention: Reset of the service timer can be
carried out by a specialist company only, who
has been authorized by the appliance
manufacturer.
Servicetimer
Inspection and maintenance has to be carried out
according to D+H maintenance notes. Only original
D+H spare parts may be used. Repair is to be
carried out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
Repair and cleaning
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling.
Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline
2012/19/EU for waste electrical and
electronic equipment and its implemen-
tation into national right, electrcal devices that are no
longer usable must be collected separately and
disposed of in an environmentally correct manner.
Disposal
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2014/30/EU, 2014/35/EU, EU 305/2011
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder Maik Schmees
Member of the Board Authorized signatory,
Technical Director
15.08.2016
Declaration of Conformity
Observe regulations for danger warning systems
VDE 0833, guidelines for electrical systems VdS
2221, VDE 0100, DIN 18232 for smoke and heat
vent systems, regulations of the local fire-brigade
and of EVU for connection to mains supply.
Important regulations

99.822.96 3.4/08/16
24 V - Emergency supply
Emergency power supply for 72 hours.
Use VdS approved storage batteries only!
RZN 4404-M(-MS): 2x 12V / 2,2 Ah ±0,2Ah (Type 2)
RZN 4408-K(-KS): 2x 12V / 3,4 Ah ±0,3Ah (Type 8)
RZN 4408-M(-MS): 2x 12V / 3,4 Ah ±0,3Ah (Type 8)
With connection of D+H alarm devices:
RZN 4404-M(-MS): 2x 12V / 3,4 Ah ±0,3Ah (Type 8)
RZN 4408-KS*: 2x 12V / 7,0 Ah ±0,3Ah (Type 3)
RZN 4408-MS*: 2x 12V / 7,0 Ah ±0,3Ah (Type 3)
(* Only with -KS or -MS version possible!)
Battery control - TID
TTemperature-guided charging of accumulator
I Impedance measuring. Internal resistance of
accumulator will be measured cyclically. For
example, if a total discharged accumulator is
connected to the control panel = malfunction
(LED on PCB)
D Discharge control = In case of power failure and
total discharge of accumulator, the control panel
will switch off. In this case, smoke vent is no
longer ensured. In this case a malfunction will be
no more indicated either.
+
–
+
-
+
2x 12 V
-
Type ZP RZN 4404-M ZP RZN 4408-K ZP RZN 4408-M
Power supply 230 VAC, 50 Hz 230 VAC, 50 Hz 230 VAC, 50 Hz
Rated power 120 VA 240 VA 240 VA
Stand-by operating 6,8 W 4,5 W 5 W
Output voltage 24 V DC
Ripple < 2 Vss
Output rated current 4A 8 A 8A
Number of lines / groups* 2 / 2 1 / 2 2 / 3
Fire detector per line max. 14 pcs. max. 14 pcs. max. 14 pcs.
SHEV button per line max. 8 pcs. max. 8 pcs. max. 8 pcs.
Current per group ** max. 4A max. 8A max. 8A
Mode of operation
- Monitoring continuous duty
-Alarm / ventilation short-time duty (30 % DC)
Temperature range -5 ... +40°C
* D+H Highspeed (HS) drives will be supported.
** The total current of the control panel must not be exceeded.
Housing GEH-KST GEH-S-RWA
Material plastic with steel sheet door steel sheet
Colour white light grey
Ingress protection IP 30 IP 54
Protection class II, with fuctional ground I
Dimensions WxHxD 310 x 310 x 100 mm 400 x 300 x 120 mm
Technical data
SHEV alarm
Malfunction
Mains existing
Vent button function "OPEN"
Smoke-/ vent button function "CLOSE"
Charging voltage regulator
Ground short
OPEN running time limitation
ventilation time limitation
Pictogram explanation
D+H window drive
OK
Control panel O.K.
min
15
245
30
sec
20
260
40
RZN 4408-K
21/36

99.822.96 3.4/08/16
22/36
RZN 4408-K
01
02
03
04
05
06
07
08
09
10
11
12
13
14
01
02
03
04
05
06
07
08
09
10
11
12
13
14
ABC
ZP RZN 4408-K
ZP RZN 4404-M
ZP RZN 4408-M
ZP GVL 8408-M
ןשע תאצוה
ΕΞΑΕΡΙΣΜΟΣ ΚΑΠΝΟΥ
DUMAN ATIŞ
D MU NOVADIŠANAŪ
RØYKVENTILASJON
SAVUNPOISTO
EVACUAZIONE FUMI
ДИМОВИДАЛЕННЯ
ДЫМОУДАЛЕНИЕ
LT
SUITSUEEMALDUS
DESENFUMAGEM
EVACUARE FUM
ROOKAFVOER
RØGLEM
ODDYMIANIE
EVACUACIÓN DE HUMOS
DESENFUMAGE
ODVOD KOUŘE
ODVOD DYMU
BRANDVENTILATION
2 x 1,2 Ah
2 x 3,4 Ah
Ø max. 5 mm
(not included)
4x
Install batteries: Position of the central pcb:
Mount control panel sheltered and easily accessible for
maintenance in proximity of drive.
Detailed installation instructions are supplied with the housing.
Mounting of SHEV control panel with housing GEH-KST
2x 2,2 Ah
2x 1,2 Ah /
2x 3,4 Ah
GEH-KST

99.822.96 3.4/08/16
12345678
ON
12345678
ON
12345678
ON
1234
ON
1234
ON
12345678
ON
Rauchabzugszentrale
Smoke Vent Controller
D+H Mechatronic - Germany - +49 40 605 65 0
RZN 4408-M
IN : 230VAC / 240VA
OUT : 24VDC / max. 8A
12.345.67-65.43 - 123456
OK
D6 D7 D8 D9 D10 D11 D12 D13
D86
D82
D87
View motherboard
RZN 4404-M
Line 1 Group 1 Line 2 Group 2
RZN 4408-K
Line 2 Group 2
Group 3
RZN 4408-M
Line 1 Group 1 Line 2 Group 2
Group 3
LED control
Fuse ext. signal
Line 1 ON-OFF-RESET
Line 2 ON-OFF-RESET
LED malfunction line 1
LED alarm line 1
DIP switch S1 Line 1
DIP switch S2 group 1
LED malfunction line 1
Fuse group 1
LED malfunction line 2
LED alarm line 2
DIP switch S3 Line 2
DIP switch S4 group 2
LED malfunction line 2
Fuse group 2
DIP switch S5 group 3
LED malfunction line 3
Fuse group 3
Mains supply
Fuse mains
LED mains
Fuse battery
Battery connection
LED-battery fault
Battery charging voltage regulator
Fire recognation element*
LED ground short
OPEN-running time limitation
Ventilation time limitation
DIP switch S6
RZN 4404-M (-MS):
2 lines, 2 groups
RZN 4408-M (-MS):
2 lines, 3 groups
RZN 4408-K (-KS):
1 line, 2 groups
* For monitoring of the internal temperature of the control device. If the
internal temperature is exceeding 72°C (caused by radiant heat of a
fire in immediate vicinity of the mounting place), the entire smoke and
heat vent system will be emergency opened under alarm conditions.
–: Emergency-supplied potential -
+: Emergency-supplied potential +
N– : Not emergency-supplied potential -
N+ : Not emergency-supplied potential +
A: General alarm
K: Control
S: General fault
SB : Battery fault
M1 : Magnetic clamp control by line 1
M2 : Magnetic clamp control by line 2
Z: Input, central function, closing of group
RZN 4408-K
23/36

99.822.96 3.4/08/16
24/36
RZN 4408-K
1 2 3 4 5 6 7 8
ON
S2, S4, S5
Encoding of groups – DIP switches S2, S4, S5
Delivery state:
min
15
245
30
sec
20
260
40
1 = ON * OPEN-running time limitation in ventilation operation
(Only if DIP switch 5= ON).
Using a potentiometer, running time in OPEN
direction can be limited. If the vent button is
actuated in OPEN direction, the drive will run open
as long as the running time is set.
2 = ON * Ventilation time limitation (Only if DIP switch 4 = ON).
Using a potentiometer, ventilation tim can be set.
Drives will automatically close again, after the
adjusted time has expired.
3 = ON * OPEN-retriggering (Only if DIP switch 1 = ON)
The OPEN-running time limitation can be retriggered again.
4 = ON * CLOSE by single pressingDrives up to final position on vent button
4 = OFF * closing only so long asDrives are the vent button or the button "close SHEV" in the
smoke vent button . OPEN-display on vent button is no longer possible then!is pressed
The function power failure-CLOSE will be ineffective (see DIP switch S6.3).
5 = ON * OPEN by single pressingDrives up to final position on vent button.
5 = OFF * OPEN as long as is pressed.Drives will only the vent button
6 = ON * roup CLOSE in case of alarm.G The group will be closing in case of alarm!
7 = ON group faultIn case of a (e.g. in case of an interrupted monitoring line) the control panel
will be switched on alarm, that means the smoke vent opens.
DIP switch must be on ON in conjunction with a ground in thermal maximal detector (e.g.
THE4).
8 = ON SHEV retriggering on. The smoke vent is triggered for a duration of 30 minutes in intervals
of 2 minutes according to VdS 2581.
Encoding of lines – DIP switches S1, S3
1 = ON Two-smoke detectors dependency (Only with SD-O 371/FO 1362)
Alarm will be triggered only, if at least two smoke detectors of
one line respond. False alarm of one smoke detector will be
prevented.
must be always installed.Two smoke detectors in one room
If is connected to one line,only one smoke detector switch
onmust be OFF!
2 = ON Smoke detector alarm be reset by single pressing on the button "close SHEV" incan not
the smoke vent button.
2 = OFF Smoke detector alarm reset by pressing on the button "close SHEV" in the smokewill be
vent button.
3 = ON line faultIn case of a (e.g. at an interrupted detector line or short circuit) the control panel
will be switched on alarm, that means .the smoke vent opens
4 = idle
Delivery state:
1234
ON
S1, S3
12345678
ON

99.822.96 3.4/08/16
12345678
ON
1234
ON
Type S1 S2 S3 S4 S5 S6
RZN 4404-M (-MS) XXXX X
RZN 4408-K (-KS) XXXX
RZN 4408-M (-MS) XXXXXX
DIP switch settings
12345678
ON
S6
S6
12345678
ON
Delivery state:
12345678
ON
12345678
ON
12345678
ON
1234
ON
1234
ON
S5S4S3S2S1
Enter the configuration at start-up:
S5S4S3S2S1
1234
ON
12345678
ON
12345678
ON
12345678
ON
1234
ON
Encoding of control panel – DIP switch S6
1 = ON * ine 2 on group 3.L Line 2 is also effective on group 3.
1 = OFF * Group 3 is independent of line 2. Group 3 is not monitored!
2 = ON * entral alarmC
In case of alarm of one line, the other line will be set on alarm
as well. With the setting Central alarm and only one line
connected and with several groups, the fault, for example,
at the last group will not be shown at the first line.
In this case, fault and control must be set at the E-slot.
(No indication of the servicetimer in the smoke vent button.
See page 20)
3 = ON ower failure "CLOSE" (Only if DIP switch S2.4, S4.4, S5.4 = ON).P
In case of power failure the drives will close.
4 = ON AdComNet Bus Control
When using the control panel (in conjunction with thewithin an AdComNet network
connection module ACN-CM 501) the switch must be on ON.
4 = OFF without an AdComNetWhen using the control panel connection..
5 = idle
6 = ON ED Test / Reset WDT Fehler (W D T )L atch og imer
Actuate DIP switch (ON / OFF). LED’s will light up for 3 seconds in control panel.
7 = idle
8 = idle
*In AdComNet operation (S6.4 = ON) these DIP switches are disabled.
The setting of the functions carried out over the AdComNet software.
1 2 3 4 5 6 7 8
ON
S6
Delivery state:
RZN 4408-K
25/36

99.822.96 3.4/08/16
26/36
RZN 4408-K
Cables for D+H smoke an heat vent systems
When selecting and installing the cables, the
regional electrical installation regulations
concerning wiring systems and the necessary
safety equipment, or guidelines on integrity
maintenance of electric lines are observed (e.g.
MLAR).
Notice:
No type designation is given for these cables,
because of a large variety on the market.
Please consult your D+H partner.
Wiring plan (Paragon)
Group cable (control panel - drive)
At least three wire design:
- 2 wires for the supply of the drive
- 1 wire for line monitoring, on which also the
SHEV high speed (HS) signal is transmitted to the
drive. If group DIP switch 7 is ON, the group will in
case of a fault automatically triggered and opens.
Line cable (control panel - detector)
The cables are monitored for short circuit and for
interruption. If line DIP switch 3 is ON, the group
will in case of a fault automatically triggered and
opens.
Line lenghts and cross sections
Cross section (mm²) =
Cable lenght (m) x Total current
80
RZN 4408-M / RZN 4408-K
RZN 4404-M
1
120
200
2
60
100
3
40
65
4
30
50
5
24
40
6
20
33
7
17
28
8
15
25 m
m
Type
Total current
3 x 1,5 mm²
²3 x 2,5 mm
230 V, 50 Hz
Seperate electric circuit.
Mark fuse.
to further ones
see line lenghts and cross sections
Drive at smoke
vent opening SHEV control panel
Vent button
approx. 1,2 m
above upper edge
firm flooring Smoke vent button
approx. 1,5 m above
upper edge firm flooring
External control
Fire detector
SD-O 371 or FD-T 271
4x 0,8 Ø
6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
2x 0,8 Ø
2x 0,8 Ø
OK
OK
Rain detector
3x 0,8 Ø
System voltage 24 V!
Do not run cables with together power lines!
In case of a cable with ground wire (green /
yellow) this must not be used!
Cable and terminal boxes have to be labeled.
L
N
X15

99.822.96 3.4/08/16
Connection overview
230 V, 50 Hz
Seperate electric circuit..
Mark fuse.
230 V supply
Protective earth (PE)
Only with -KS and -MS Version.
Protection cap:
Place enclosed protection cap
over supply terminal after mains
cable has been connected.
L
N
X15X15
L
N
PE
2
8
316475
RT 45
32
5
SD-O 371
28316475
RT 45
28316475
OK
Line
T
R– A–K EAaZbS
RZN 440x-M / RZN 4408-K
Line
–
N–
Control
Alarm
CLOSE
Mot.b
Mot.a
Monitoring
OPEN
CLOSE
Open signal (only with -SD)
RM LT
10kW
Failure
Alarm
Control
–
Line
CLSOE
Failure
n.c.
RT MOT
32
SD-O 371
10kW
5
OK
LN– Z
LT 84-U (-SD)
LP
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
Drive
Mot.b
Mot.a
HS
RZN 4408-K
27/36

99.822.96 3.4/08/16
28/36
RZN 4408-K
Connection of smoke vent buttons
Max. 8 buttons per line connectable.
Standard connection Parallel connection
Parallel connection of 2x 2 buttons
2
8
316475
RT 45
first to penultimate
button
28316475
RT 45
28316475
OK
last button
Line
345678
RZN 440x-M / RZN 4408-K
Line
–
Control
Alarm
CLOSE
RM
10kW
Failure
Alarm
Control
–
Line
CLOSE
Failure
n.c.
RT
Line
n.c.
Failure
345678
RZN 440x-M / RZN 4408-K
Line
–
Control
Alarm
CLOSE
RM
10kW
Alarm
Control
–
Line
Line
CLOSE
Failure
**
* Shunt connection by customer
Alarm
Control
–
Line
CLOSE
Failure
n.c.
RT
28316475
RT 45
28316475
OK
28316475
RT 45
28316475
OK
2
8
316475
RT 45
2
8
316475
RT 45
first to penultimate
button each
last button each
Line
n.c.
Failure
345678
RZN 440x-M / RZN 4408-K
Line
–
Control
Alarm
CLOSE
RM
Alarm
Control
–
Line
Line
CLOSE
Failure
**
Alarm
Control
–
Line
CLOSE
Failure
n.c.
RT
* Shunt connection by customer
10kW
28316475
RT 45
28316475
OK
28316475
RT 45
28316475
OK

99.822.96 3.4/08/16
-+
-+
N– N+ Z + M1 M2 – SB
Cutout
button
Magnetic
clamps
Connection of magnetic clamps
Magnetic clamps 24V (max. 500 mA overall power)
No output voltage during power failure! Group output:
While an alert, a possible group disturbance will
not notified. Only after reset the alarm, a fault
message will be indicated.
High-speed function (HS):
All D+H drives with SHEV high-speed function are
supported. In daily ventilation operation, a consi-
derable noise reduction is achieved through the
reduced drive speed. In case of SHEV the drives
run with a very high speed to reach the OPEN
position defined within 60 seconds at the most.
SHEV retriggering:
(When DIP switches S2.8 / S4.8 / S5.8 = ON)
The smoke vents will be triggered with an OPEN-
impulse every 2 minutes for a duration of 30
minutes according to VdS 2581. For this, the
drives must be blockage safe. All D+H drives meet
this precondition. Otherwise the DIP switches has
to be switched on OFF.
Mounting of the drives:
Please take mounting informations from the
relevant instruction for use of the respective drive,
because of varied possibilities for choosing drives.
Drives
Connection of fire detector
Max. 14 fire detectors connectable.
Only D+H approved detectors must be used.
* Terminal resistors for line monitoring
It is pinched in control panel for transport.
Take it off there and connect according to plan.
Terminal resistor must remain at terminal RM 1,2,
when no fire detector or external control exists!
Connection of fire alarm system
R
Operating contact
Alarm resistor
1kW
BMZ / BMA
Line
Terminal resistor*
10kW
RM RT
12
–
–
RZN 440x-M / RZN 4408-K
first to penultimate
fire detector
last
fire detector
SD-O 371
or
FD-T 271
RZN 440x-M / RZN 4408-K
RM RT
12
–R
EP 6
EM 2
1
C 3
IN 4
OUT 5
EP 6
EM 2
1
C 3
IN 4
OUT 5
< optional >
10 kW
RZN 4408-K
29/36

99.822.96 3.4/08/16
30/36
RZN 4408-K
Informations for starting
Carry out following sight and performance checks for switching-on the smoke and heat vent
control panel.
All cables
connected?
Factory set?
(DIP switch)
10kΩ resistor in
smoke vent
button?
End module
2x47kΩ
in junction box?
Connect mains.
LED mains lightens?
Connect battery
lines. Control l
ightens?
Smoke vent flap opens
and closes?
All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of
control panel. The smoke vent opens self-acting and can be
reset under special conditions only.
yes
yes
yes
yes
yes
yes
yes
Performance check alarm/reset and ventilation
yes
Partial or incomplete connection of
components can cause malfunction.
Check following connections: mains 230 V,
drives, smoke vent buttons, when necessary
fire detectors and vent buttons.
See wiring an connection plans pages 27-29.
Delivery condition of DIP switch see
pages 24-25.
Resistor must be cramped in electric last
button on terminal 3/8 (RT 45).
See connection plan pages 28.
Resistor must be cramped in last or only fire
detector on terminal 3 and 5 (SD-O/FD-T).
Resistor remains in control panel between
terminal RM "R" and "–", when no fire
detector is connected.
See connection plan page29.
10kΩ resistor in fire
detector?
yes
End module on last or only drive in junction
box on wire 5 orange, 6 black, 7 black.
See connection plan page 27.
Check line safety fuse in distribution box and
fuse mains in control panel.
Mains still not available or line switch on "0"
or one of fuses faulty.
Possibly change poles in drive.
no
no
no
no
no
no
no
no

99.822.96 3.4/08/16
Operation - Release in case of alarm
click
External control
Manual opening by smoke vent button:
Automatic opening by fire detector:
Automatic opening by external control (e.g. fire alarm system):
OK
SMOKE VENT
OK
OK
RT
Reset
OFF
ON
Line
RZN
OK
RT
OK
RT
Reset
OFF
ON
Line
RZN
Reset
OFF
ON
Line
RZN
RZN 4408-K
31/36

99.822.96 3.4/08/16
32/36
RZN 4408-K
OK
~ 1 Sec.
see DIP switch
page 24-25
OK
~ 1 Sec.
OK
Emergency closing in case of non-resettable alarm:
Reset =
OFF / ON
Reset
0
I
Line
click
OFF
Reset
0
I
Line
With manual release:
In case of automatic release by fire detector or external control:
External control
or
Operation - Closing after alarm
Open the housings (control panel and buttons) using the enclosed keys.
Service

99.822.96 3.4/08/16
ST OP ST OP ST OP
Operation - Day-to-day ventilation
Open: Close: Stop:
or
Ventilation button or SHEV button with ventilation function RT 45-LT required.
or
or
STOP
OKOK
Operation -AdComNet
In case of AdComNet operation (S6.4 = ON) the
ventilation control and alarm release can be
carried out by the local connected line and group
inputs, as well as via corresponding links in the
AdComNet Configurator.The alarm and fault
indicators distinguish between a local message
and a message inside a bus link:
Malfunction LED on the line:
1 Line deactivated: LED flashes
2 local fault: LED lights continuous
3 BUS fault: LED flashes
4 Everything OK: LED OFF
Malfunction LED on the group:
1 local fault: LED lights continuous
2 BUS fault: LED flashes
3 Everything OK: LED OFF
Alarm LED on the line:
1 local alarm: LED lights continuous
2 BUS alarm: LED flashes
3 No alarm: LED OFF
Only if wind detector or rain detector available.
Upon triggering of the corresponding sensor, the
group of the control panel is closed.
If alarm is released by a smoke and heat vent
system, the system will open also in case of wind
and rain.
Do not ventilate via smoke vent button,
because otherwise there would be a danger of
damage by wind or water.
The weather automatic can be switched-off via an
optional automatic switch, if gap ventilation is
required in case of bad weather.
Gap ventilation not possible badis in case of
weather, no automatic switch availableif .
If the weather automatic is switched on , the
system will automatically
close in case of wind or rain.
The system will not
automatically open again,
if wind or rain has stopped.
Opening of the system for
ventilation via vent button.
Operation - Weather automatic
Automatic
on/off
LT 84-U-W
OK
SMOKE VENT SMOKE VENTSMOKE VENT
RZN 4408-K
33/36

99.822.96 3.4/08/16
34/36
RZN 4408-K
Once a year by a specialist company, who is
authorized by the appliance manufacturer.
Renew test badge, keep log book.
The respective current D+H maintenance
instruction is decisive.
D+H authorized expert companies have been
specially trained by D+H for carrying out expertly
this maintenance, and they get automatically the
latest maintenance instructions.
Maintenance
Following tests must be carried out in the course of
maintenance:
- Outside examination / inspection of system
components
- Checking of all relevant power supply units
- Functional testing of connected system
components
- Record of competent carrying-out of
maintenance, and designation according to
directions
Inspection
Regular visual inspection between maintenance by the operator or a trained person.
Immediately correct any defects.
Indicators:
- in the buttons must .Green LEDs illuminate
- in the buttons and the control panelYellow LEDs
are (fault).not allowed to illuminate or flash
- If the green LEDs do not illuminate or if the
yellow LEDs illuminate or flash, contact After
Sales service.
Examination:
- Check all appliances and cable connections for
outer damage and dirt accumulation.
- Fire detectors, smoke vent buttons, smoke vents
and so on must not be impaired in their function
by goods in storage or structural changings.