  9. LEGRAND 4 142 21 User manual

LEGRAND 4 142 21 User manual

1 / 4
87045 LIMOGES Cedex
Telephone: + 33 5 55 06 87 87 – Fax: + 33 5 55 06 88 88
Isolating switch DX3≤63 A
direct current, 800V
Cat. n°(s) : 4 142 21 / 23 / 24 / 26
CONTENTS PAGES
1. Description - Use ................................ 1
2. Range................................................. 1
3. Overall dimensions ............................. 1
4. Preparation - Connection .................... 1
5. General Characteristics ...................... 2
6. Compliances and approvals................ 4
7. Auxiliaries and accessories................. 4
1. DESCRIPTION - USE
. Modular isolating switch (IS) for the control of electrical circuits
supplied with direct current. This isolating switch can be used for
photovoltaic applications.
Symbol:
2. RANGE
Polarity:
. 2P in 4 modules.
. 2 modules per pole (2 x 17,7 mm = 35,4 mm).
Rated currents In:
. 16 A / 25 A / 32 A / 63 A.
Rated voltage:
. 800 V DC (direct current)
3. OVERALL DIMENSIONS
N° of Poles “X” (mm)
2P 70,8 mm
4. PREPARATION - CONNECTION
Mounting:
.On symmetrical EN 60.715 rail or DIN 35 rail
Operating positions:
.Vertical Horizontal Upside down On the side
Power supply:
. Only from the top like it is shown in the wiring diagram on right side
of the device.
Warning : isolating switches 32 A (Cat. No. 4 142 24) and 63 A (Cat.
No. 4 142 26) do not accept « reverted currents ». In a photovoltaic
installation, they cannot be installed close to the solar panels but
only close to the UPS.
Technical data sheet
: F01282EN/02 Updated : 24/08/2016 created : 7/10/2011
2 / 4
Isolating switch DX3≤63 A
direct current, 800V
Cat. n°(s) : 4 142 21 / 23 / 24 / 26
4. PREPARATION - CONNECTION
(continued)
Supply and localisation in the installation:
Warning: isolating switches 32 A (Cat. No. 4 142 24) and 63 A (Cat.
No. 4 142 26) do not accept « reverted currents ». In a photovoltaic
installation, they cannot be installed close to solar panels to control
groups of panels but only close to the UPS to control the whole
group of panels.
Terminal depth:
. 14 mm.
. It is necessary to use the insulating shields between terminals.
. The shields are delivered with this isolating switch.
Screw head:
. Mixed, slotted and Pozidriv n° 2.
Recommended tightening torque:
. 3 Nm.
Recommended tools:
. For the terminals: screwdriver Pozidriv n°2.
. For attaching or removing the DIN rail: screwdriver slotted 5.5 mm
(6 mm maximum).
Conductor type:
Copper cable
Without ferrule With ferrule
Rigid wire 1 x 1,5 mm² to 35 mm²
2 x 1,5 mm² to 16 mm² -
Flexible
wire
1 x 1,5 mm² to 25 mm²
2 x 1,5 mm² to 10 mm² 1 x 1,5 mm² to 25 mm²
Manual actuation of the IS:
.Ergonomic 2-position handle
- “O-OFF”: Device open
- “I-ON”: Device closed
Display of contacts status :
. By the position of the handle and printings
- “O-OFF”: = contacts open
- “I-ON”: = contacts closed
Sealing:
.Possible in the open or closed positions
Locking:
. With padlock (Cat. No. 0 044 43 or 0 227 97), whit support for
padlock (Cat. No. 4 063 03) in the open position.
4. PREPARATION - CONNECTION
(continued)
Labelling:
. Circuit identification by way of a label inserted in the label holder
situated on the front of the product.
5. GENERAL CHARACTERISTICS
Marking on the front side:
.By permanent ink pad printing - category of use DC21B.
- relevant standard n° IEC 60947-3.
- rated current in amps (A).
- rated voltage in volts (V).
- cat. n° and logo
- grand name Legrand.
- I and O with a double arrow.
- electrical diagram.
Marking on the Left side:
. By laser:
- wiring diagram
Technical data sheet
: F01282EN/02 Updated : 24/08/2016 created : 7/10/2011
3 / 4
Isolating switch DX ≤63 A
direct current, 800V
Cat. n°(s) : 4 142 21 / 23 / 24 / 26
5. GENERAL CHARACTERISTICS
(continued)
Minimum operating voltage:
. 12 V DC per pole.
Shocks withstand rated voltage:
. Uimp = 8 kV.
Isolation voltage:
. Ui = 1000 V.
Isolation distance:
. The distance between contacts is more than 5,8mm when the
handle is in open position « O-Off »
. DX DC circuit breaker are suitable for the isolation in accordance
with EN/IEC 60947-3
Category of use:
. DC21B.
Rated short-time withstand current:
. Icw = 12 x In minimum.
Rated short-circuit making capacity:
. Icm = 1500 A.
Short-circuits withstand:
. Icc = 5000 A.
Effort to operate the handle:
. 0,5 Nm per device when closing the contacts.
. 0,3 Nm par device when opening the contacts.
Endurance:
. 20000 operations without load.
. 2000 operations at In and Un.
Enclosure material:
. Polyester.
. Characteristics of this material: self extinguishing, heat and fire
resistant according to EN 60898-1, glow-wire test at 960°C for
external parts made of insulating material necessary to retain in
position current-carrying parts and parts of protective circuit (650°C
for all other external parts made of insulating material).
Weight of the isolating switch:
. 0,581 kg.
Volume and packaging:
Volume (dm3)
Double pole 1,2 dm3
Ambient temperatures:
. Operation: from - 25℃ to + 70℃
. Storage: from - 40℃ to + 70℃
Degree or class of protection:
. Protection index of terminals against solid and liquid bodies:
IP 20 (in according with standards IEC 529, EN 60529 and NF C
20-010).
. Protection index of the box against solid and liquid bodies:
IP 40 (in according with standards IEC 529, EN 60529 and NF C
20-010).
. Protection index against mechanical shocks: IK 02 (in according
with standards EN 50102 et NF C 20-015).
5. GENERAL CHARACTERISTICS
(continued)
Sinusoidal vibration resistance in accordance with
IEC 60068.2.6:
. Axis : x, y, z.
. Frequency range: 5÷100 Hz ; duration 90 min.
. Displacement (5÷13,2 Hz) : 1mm
. Acceleration (13,2÷100 Hz) : 0,7g (g=9,81 m/s
2).
Pollution degree :
. 3 in accordance with EN/IEC 60898-1.
Dielectric strength:
. 2000 V
Dissipated power (W):
. For the 2P isolating switch
In 16 A 25 A 32 A 63 A
2P 1,5 2,4 3,1 5,5
. Impedance of the isolating switch (Ω) = P dissipée
In2
Derating of the isolating switch in terms of ambient
temperature :
. Reference temperature : 40 °C in accordance with EN/IEC 60947-3
standard.
. Rated characteristics of the isolator switch may be modified
depending on the ambient temperature inside the enclosure where it
is installed.
Ambient temperature in °C
Current in Amps
In (A) - 25°C - 10°C 0°C 10°C 20°C
16 21,9 20,0 18,7 18,0 17,3
25 34,5 31,5 29,5 28,3 27,2
32 45,8 41,0 37,8 36,5 34,9
63 88,1 80,6 75,6 72,5 69,9
Ambient temperature in °C
Current in Amps
In (A) 30°C 40°C 50°C 60°C 70°C
16 16,6 16,0 15,4 14,7 14,1
25 26,0 25,0 24,0 22,7 21,7
32 33,3 32,0 30,7 20,1 27,8
63 66,1 63,0 59,8 56,1 52,9
Technical data sheet
: F01282EN/02 Updated : 24/08/2016 created : 7/10/2011
4 / 4
Isolating switch DX ≤63 A
direct current, 800V
Cat. n°(s) : 4 142 21 / 23 / 24 / 26
6. COMPLIANCE AND APPROVALS
In accordance with standards:
. EN/IEC 60947-2
. EN/IEC 60947-3.
. European directives : 73/23/CEE + 93/68/CEE.
. These isolating switches can be used in the conditions of use
defined by IEC/EN 60947 standard.
. The isolating switch performances may be modified in case of
particular climatic conditions.
Plastic materials :
. Halogens-free plastic materials.
. Marking of parts according to ISO 11469 and ISO 1043.
Packaging:
. Design and manufacture of packaging in accordance with Decree
98-638 of 07.20.98 and Directive 94/62/EC
7. AUXILIARIES AND ACCESSORIES
Wiring accessories:
. Sealable screw cover (Cat. No. 4 063 04).
. Insulation shields (Cat. No. 4 063 05).
Signalling auxiliaries:
. Auxiliary changeover switch (½ module – Cat. No. 4 062 58).
. Fault signalling changeover switch (½ module – Cat. No. 4 062
60).
. Auxiliary changeover switch which can be modified into fault
signalling changeover switch (½ module – Cat. No. 4 062 62).
. Auxiliary changeover switch + fault signalling changeover switch
which can be modified into two auxiliary changeover switches (1
module – Cat. No. 4 062 66).
Control auxiliaries:
. It is imperative not to associate control auxiliaries with the
isolating switch .
Auxiliaries and isolating switches combinations allowed :
. Auxiliaries must be fitted on the left side of the isolating switch.
. Maximum of 2 auxiliaries per isolating switch whose only one half-
module wide auxiliary.
Installation software :
. XL PRO3
Te
chnical data sheet : F01282EN/02 Updated : 24/08/2016 created : 7/10/2011

This manual suits for next models

3

Other LEGRAND Switch manuals

LEGRAND Valena Life 7 521 84 User manual

LEGRAND

LEGRAND Valena Life 7 521 84 User manual

LEGRAND LIMOGES Cedex 87045 User manual

LEGRAND

LEGRAND LIMOGES Cedex 87045 User manual

LEGRAND Excel Life EM883 User manual

LEGRAND

LEGRAND Excel Life EM883 User manual

LEGRAND 0 883 26 User manual

LEGRAND

LEGRAND 0 883 26 User manual

LEGRAND C2G 29974 User manual

LEGRAND

LEGRAND C2G 29974 User manual

LEGRAND 3 109 53 User manual

LEGRAND

LEGRAND 3 109 53 User manual

LEGRAND 841 01 User manual

LEGRAND

LEGRAND 841 01 User manual

LEGRAND 784 47 User manual

LEGRAND

LEGRAND 784 47 User manual

LEGRAND Niloe 6 647 03 User manual

LEGRAND

LEGRAND Niloe 6 647 03 User manual

LEGRAND Wattstopper LMPS-104 User manual

LEGRAND

LEGRAND Wattstopper LMPS-104 User manual

LEGRAND Pro 21 7756 44 User manual

LEGRAND

LEGRAND Pro 21 7756 44 User manual

LEGRAND Arteor 5 722 69 User manual

LEGRAND

LEGRAND Arteor 5 722 69 User manual

LEGRAND Elioflux 766 68 User manual

LEGRAND

LEGRAND Elioflux 766 68 User manual

LEGRAND adorne sofTap Dimmer ADTP600RMH User manual

LEGRAND

LEGRAND adorne sofTap Dimmer ADTP600RMH User manual

LEGRAND Belanko 617 076 User manual

LEGRAND

LEGRAND Belanko 617 076 User manual

LEGRAND Wattstopper LMSW-610-S User manual

LEGRAND

LEGRAND Wattstopper LMSW-610-S User manual

LEGRAND Arteor 5 722 69 User manual

LEGRAND

LEGRAND Arteor 5 722 69 User manual

LEGRAND adorne WNAL23W1 User manual

LEGRAND

LEGRAND adorne WNAL23W1 User manual

LEGRAND Raritan RSS4-102 Service manual

LEGRAND

LEGRAND Raritan RSS4-102 Service manual

LEGRAND 4126 02 User manual

LEGRAND

LEGRAND 4126 02 User manual

LEGRAND Pro 21 7756 21 User manual

LEGRAND

LEGRAND Pro 21 7756 21 User manual

LEGRAND Wattstopper LMSW-632-S User manual

LEGRAND

LEGRAND Wattstopper LMSW-632-S User manual

LEGRAND Adorne User manual

LEGRAND

LEGRAND Adorne User manual

LEGRAND Celiane 048896A User manual

LEGRAND

LEGRAND Celiane 048896A User manual

Popular Switch manuals by other brands

Kramer VS-21HDCP-IR user manual

Kramer

Kramer VS-21HDCP-IR user manual

Indu-Sol PROmesh P20 Quick start user guide

Indu-Sol

Indu-Sol PROmesh P20 Quick start user guide

R&S UPZ operating manual

R&S

R&S UPZ operating manual

ANATEL AS6710-32X quick start guide

ANATEL

ANATEL AS6710-32X quick start guide

Ruijie Reyee RG-NBS6002 Hardware  installation and reference guide

Ruijie

Ruijie Reyee RG-NBS6002 Hardware installation and reference guide

Kramer VP-23DS user manual

Kramer

Kramer VP-23DS user manual

Agilent Technologies Switch/Measure user guide

Agilent Technologies

Agilent Technologies Switch/Measure user guide

CableCreation CD0395 manual

CableCreation

CableCreation CD0395 manual

Flamingo FA106 quick guide

Flamingo

Flamingo FA106 quick guide

ABB NE810 user manual

ABB

ABB NE810 user manual

iHome Hi20 Quick setup guide

iHome

iHome Hi20 Quick setup guide

ABB REL 301 Instruction leaflet

ABB

ABB REL 301 Instruction leaflet

retrotouch RTS2020W instruction manual

retrotouch

retrotouch RTS2020W instruction manual

D-Link DES-1218 user guide

D-Link

D-Link DES-1218 user guide

RFI MA-2080-B user manual

RFI

RFI MA-2080-B user manual

Force 10 S2410 Installing

Force 10

Force 10 S2410 Installing

TP-Link TL-SG108PE installation guide

TP-Link

TP-Link TL-SG108PE installation guide

Vents P2-10 quick start guide

Vents

Vents P2-10 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.