©Vantage, 1/3/2017 / IS-0584-B DIN WireLink and RadioLink CIS — MODEL: CIS10-DIN & STIDER121 page 1 of 2
INSTALLATION
VANTAGECONTROLS.COM VANTAGE INSTALL GUIDES
2168 West Grove Parkway, Suite 300, Pleasant Grove, UT. 84062 USA
Telephone: 801 229-2800 ●Fax: 801 224-0355 DIN WireLink and RadioLink CIS — MODEL: CIS10-DIN & STIDER121
Overview
The DIN Contact Input Station WireLink™ model, CIS10-DIN and
RadioLink™ model, STIDER121 feature 10 contact input channels for
receiving Dry-Contact Open/Close states from external devices.
Various types of external switches and sensors are available from
Vantage and other third party manufacturers. These include
magnetic door contact switches, momentary switches, motion
detectors, stress sensors, humidity and temperature sensors,
smoke and carbon monoxide detectors, driveway probes, etc.
Station Specifications
Description Specification
Dimensions, HWD 85.7mm x 157.2mm x 61.9mm
3.38” x 6.19” x 2.44”
Weight 201g / 7.09oz
Mounting 35 mm DIN Rail (EN 50 022: 1977)
Number of Contacts 10
Max. Current from +12V 50mA combined
Station Wiring
configuration Daisy-chain/Star/Branch
Station Bus Specification
2C, 16AWG / 1.31mm2, twisted, non-
shielded, <30pF per foot. Separate a
minimum of 12" / 30.5cm from other
parallel communication and/or high
voltage runs.
Station Equivalent
InFusion 0.5W on IC-24 / 0.7W on IC-36
Station Equivalent
RadioLink 1 Station on RadioLink Systems
Station Bus connections* 24V / 36V Station Bus
LED Indicators Contact State, Program State and
Status
Ambient Operating
Temperature 0-35°C / 32-95°F
Ambient Operating
Humidity 5-95% non-condensing
CE, UL and CUL Listed Yes
*CAUTION: 36V stations have a symbol on the Serial Number
sticker. Any station, not displaying this symbol, should not be
connected to a 36Volt Station Bus.
Software/Firmware
The WireLink and RadioLink models are compatible with InFusion
Design Center software. For new projects it is recommended that
firmware and software be kept to the most current release.
Installation/Mounting
Installation of Vantage products should be performed or
supervised by a Certified Vantage Installer. There are two methods
of connecting the Station Bus to the Contact Input Relay Station:
1. Using the Station Bus connection on the removable
screw terminal connectors.
2. The RadioLink model requires a 15-36VDC, 500mA power
supply.
Connecting Device Requirements
All low voltage connections to each Contact Input are wired to
removable screw terminal connectors. All 10 Contact Inputs are
available on the bottom of the Station. Each Contact Input can be
given custom names in software to facilitate their use in the
installation.
Auxiliary 12Vdc connections are also available on the DIN CIS screw
terminal connectors. There are 4 screw terminal connections
available with a maximum, combined current of 50ma or any single
connection with a maximum of 50ma. The ground for the 12Vdc
connections is any one of the Contact Input ground connections.
The DIN CIS has two sets of removable screw terminal connectors
on the bottom for wiring. Any device that connects to the CIS must
only use the CIS ground for the ground reference.
This is often called a "floating" or "isolated" input to the DIN CIS.
This isolation can be provided from several different systems. The
most common are door contacts and motion detectors, providing a
dry contact relay connection to the CIS. Battery powered devices
that are not connected to other equipment can be used with the
DIN CIS. Devices that are powered from the +12Vdc and CIS
ground connections can also be used.
The DIN CIS inputs can accept small voltage levels (0 to 12VDC)
instead of dry contacts as long as the voltage is only referenced to
the CIS's ground. The input will switch the CIS when the voltage
reaches the required level. The logic may be reversed in the
software by changing the polarity from Normally Open to Normally
Closed. A power level of 0.0VDC to 0.5VDC equals a PRESS,
3.0VDC to 12VDC equals a RELEASE. A 2.0VDC power range is
insufficient to toggle an Open/Close state.
Example:
Current CIS State Input Voltage Resulting CIS State
Open < 0.5V Closed (PRESS)
Closed > 3.0V Open (RELEASE)
WIRE RECOMMENDATION: Contact wire runs should be
limited to 250 feet / 76.2 meters for each wire run, using
a minimum of 20AWG gauge wire. All connections use
4.4 inch pound torque. Stranded wire recommended.
Station Set Up in Software
InFusion: First select the room, then click on Vantage Objects in
the Object Explorer and expand Stations, WireLink or Stations,
RadioLink. From the list of stations double click on the DIN Contact
Input Station to place it in the room. In the Object Editor, name the
station and make sure it is on the correct station bus port. Each
contact is also listed in the Object Editor and may be assigned to a
task and given unique names, Polarity and Hold On Time settings.
Programming Contact Inputs
When programming, each Contact Input can trigger any
appropriate tasks or functions available in Design Center, and work
like a button press and release. Select Switch Polarity Normally
Open or Normally Closed and set Switch Hold Time (Default hold
time of 0.00s, is normally used).
Configuration with WireLink Models
When the DIN CIS is first connected to the Station Bus, the Status
LED will blink twice followed by a pause, meaning that the station
is connected correctly but not yet configured. From Design Center,
click in the Serial Number section in the Object Editor and type in
the serial number. Once configured, the Status LED will blink
evenly. The ability to configure a CIS station by pressing any button
on the front of the CIS was removed because it was possible for the
station to send unwanted presses during the configuration stage
causing a station to receive the wrong serial number. An example
of this happening is as follows: A CIS could have motion detectors
connected to it and when walking through a project to configure
stations the person walking could inadvertently cause the motion
detectors to send button presses telling the software to configure
the station that was currently highlighted in the Configure Stations
window. This could happen on DIN CIS and Standard CIS stations.
Now Button presses received from dry-contacts are ignored when
on-line configuration is selected.
Configuration with RadioLink*
RadioLink DIN CIS stations need to be configured to associate
which physical station goes with the station in software.
When the station is initially powered-up, the Status LED will blink
three times followed by a pause - this means the station is
powered correctly but not yet on the network. Before uploading
the file to the Vantage system, do the following: From Design
Center, click in the Serial Number section in the Object Editor and
type in the serial number.
The serial number of each station is located on the station. Record
the number for easy reference when programming. The Main
Controller will add to its network and configure all the RadioLink
stations that it has serial numbers for. This may take several
minutes depending on the number of RadioLink stations on the
I N S T A L L A T I O N
©Vantage, 1/3/2017 / IS-0584-B DIN WireLink and RadioLink CIS — MODEL: CIS10-DIN & STIDER121 page 2 of 2
Side
Label
Enlarged
NOTE: RadioLink Model – Top Label; Power Input Connection is
15-36VDC or 12-28VAC, 250mA IN
RadioLink Model FCC Information
This device contains transmitter module:
FCC ID: PII-VSUB075-1 or PII-VSUB235
IC ID: 3505A-VSUB0751 or 3505A-VSUB235
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Changes or modifications to this product not expressly approved by
Vantage Controls could void the user’s authority to operate this product.
network. The Status LED will blink steadily when a station has been
added to the network and configured.
*NOTE: A new feature with Design Center 2.3 and up is the ability
to configure RadioLink stations the same way WireLink stations are
configured, e.g., 3-button press. When configuring stations, if the
Exclude RadioLink Bus check box, under Settings | System
Preferences, is not checked, all RadioLink stations go back to non-
programmed mode when the Configure Stations button on the tool
bar is clicked. The station’s LEDs will all blink while in configure
station mode. After configuring stations and clicking the Configure
Stations button again to turn configure stations mode off, all
RadioLink stations need to log back on to the system before
working as programmed. Allow time for this to occur.
Diagnostic and Test Information
Each contact input has an actuator button and 2 status LED's. The
actuator button shorts the input to ground. The Contact State LED
illuminates when the contact input is grounded. The Program State
LED operates the same as switch LEDs on a keypad station. When
grounded, Contact States trigger the Program State ON or OFF
depending on whether the contact’s polarity is set to Normally
Open or Normally Closed.
The Status LED blinks steady on and off for 1, 2, 3 or 4 blinks
followed by a pause.
One Even Blink: CIS is operating correctly and is configured.
Two Blinks: CIS is operating correctly but is not configured
(wired model).
Three Blinks: CIS is not communicating with the Main
Controller, verify station bus wiring or if
RadioLink it is not yet configured.
Four Blinks: Factory problem. Please contact the factory.
Five blinks: Configuration mode.
Line Drawings

This manual suits for next models

1

Other LEGRAND Switch manuals

LEGRAND Whad 5-6 kVA User manual

LEGRAND

LEGRAND Whad 5-6 kVA User manual

LEGRAND Valena Life LE-752107 User manual

LEGRAND

LEGRAND Valena Life LE-752107 User manual

LEGRAND PRO 21 7756 27 User manual

LEGRAND

LEGRAND PRO 21 7756 27 User manual

LEGRAND Wattstopper LMDM-101 User manual

LEGRAND

LEGRAND Wattstopper LMDM-101 User manual

LEGRAND 300 W RF User manual

LEGRAND

LEGRAND 300 W RF User manual

LEGRAND radiant User manual

LEGRAND

LEGRAND radiant User manual

LEGRAND In One 770 24 User manual

LEGRAND

LEGRAND In One 770 24 User manual

LEGRAND Adorne User manual

LEGRAND

LEGRAND Adorne User manual

LEGRAND HS4658 User manual

LEGRAND

LEGRAND HS4658 User manual

LEGRAND DRD3 v2 User manual

LEGRAND

LEGRAND DRD3 v2 User manual

LEGRAND Adorne sofTap WNAL10 User manual

LEGRAND

LEGRAND Adorne sofTap WNAL10 User manual

LEGRAND 916 30 User manual

LEGRAND

LEGRAND 916 30 User manual

LEGRAND The Radiant Collection User manual

LEGRAND

LEGRAND The Radiant Collection User manual

LEGRAND Arteor 5 722 69 User manual

LEGRAND

LEGRAND Arteor 5 722 69 User manual

LEGRAND Arteor 5 742 70 User manual

LEGRAND

LEGRAND Arteor 5 742 70 User manual

LEGRAND In One 882 10 User manual

LEGRAND

LEGRAND In One 882 10 User manual

LEGRAND 0 672 21 User manual

LEGRAND

LEGRAND 0 672 21 User manual

LEGRAND Raritan Dominion KX III User manual

LEGRAND

LEGRAND Raritan Dominion KX III User manual

LEGRAND Valena Life 7 521 84 User manual

LEGRAND

LEGRAND Valena Life 7 521 84 User manual

LEGRAND Pro 21 7756 21 User manual

LEGRAND

LEGRAND Pro 21 7756 21 User manual

LEGRAND radiant LC2201 User manual

LEGRAND

LEGRAND radiant LC2201 User manual

LEGRAND C2G 4K60 User manual

LEGRAND

LEGRAND C2G 4K60 User manual

LEGRAND LEXIC AstroRex DY64 User manual

LEGRAND

LEGRAND LEXIC AstroRex DY64 User manual

LEGRAND 0 226 04 User manual

LEGRAND

LEGRAND 0 226 04 User manual

Popular Switch manuals by other brands

Three NR5103e user guide

Three

Three NR5103e user guide

Minicom Smart CAT5 Switch 16 IP operating guide

Minicom

Minicom Smart CAT5 Switch 16 IP operating guide

Eaton Cutler-Hammer AMPGARD instructions

Eaton

Eaton Cutler-Hammer AMPGARD instructions

Panduit CDE2 instructions

Panduit

Panduit CDE2 instructions

Tunstall Lifeline Vi user guide

Tunstall

Tunstall Lifeline Vi user guide

Wise T953 manual

Wise

Wise T953 manual

SignaMax 065-7528 user guide

SignaMax

SignaMax 065-7528 user guide

Elko inels RFUS-11 quick start guide

Elko

Elko inels RFUS-11 quick start guide

VXI SW1 user manual

VXI

VXI SW1 user manual

ECO Sensors OS-3 Instructions for use

ECO Sensors

ECO Sensors OS-3 Instructions for use

Vega VEGAPOINT 11 operating instructions

Vega

Vega VEGAPOINT 11 operating instructions

ENSIM SENSORS ELM Series operating manual

ENSIM SENSORS

ENSIM SENSORS ELM Series operating manual

IBM xSeries 300 Service guide

IBM

IBM xSeries 300 Service guide

Bay Networks 281xSA Using

Bay Networks

Bay Networks 281xSA Using

EMG PA-2 Installation information

EMG

EMG PA-2 Installation information

Luxul AMS-1208P Quick setup guide

Luxul

Luxul AMS-1208P Quick setup guide

Juniper EX2300-C-12P quick start

Juniper

Juniper EX2300-C-12P quick start

Hirschmann MAR1042 user manual

Hirschmann

Hirschmann MAR1042 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.