• 13 •
l/h kPa kW kW kW
10 °C
2150 25 --- --- --- 13,59 3,39
3070 40 --- --- --- 13,99 3,43
4390 60 --- --- --- 14,26 3,46
15 °C
2150 25 16,02 6,41 0,67 15,06 3,54
3070 40 16,20 6,67 0,67 15,49 3,58
4390 60 16,31 6,89 0,67 15,80 3,61
20 °C
2150 25 15,49 5,56 0,68 16,54 3,66
3070 40 15,67 5,79 0,67 17,00 3,70
4390 60 15,79 5,98 0,67 17,35 3,72
25 °C
2150 25 14,92 4,79 0,68 18,04 3,76
3070 40 15,10 5,00 0,68 18,52 3,79
4390 60 15,23 5,17 0,68 18,92 3,81
30 °C
2150 25 14,32 4,11 0,70 --- ---
3070 40 14,50 4,30 0,69 --- ---
4390 60 14,63 4,44 0,69 --- ---
35 °C
2150 25 13,68 3,51 0,71 --- ---
3070 40 13,87 3,69 0,70 --- ---
4390 60 14,00 3,80 0,70 --- ---
40 °C
2150 25 13,01 3,01 0,72 --- ---
3070 40 13,20 3,17 0,72 --- ---
4390 60 13,34 3,26 0,71 --- ---
l/h kPa kW kW kW
10 °C
2540 30 --- --- --- 15,55 3,36
3640 45 --- --- --- 16,00 3,42
5200 70 --- --- --- 16,28 3,45
15 °C
2540 30 18,55 5,86 0,66 17,25 3,56
3640 45 18,72 6,07 0,66 17,73 3,62
5200 70 18,81 6,25 0,66 18,07 3,65
20 °C
2540 30 18,03 5,15 0,67 18,98 3,75
3640 45 18,21 5,34 0,66 19,50 3,80
5200 70 18,31 5,50 0,66 19,89 3,84
25 °C
2540 30 17,44 4,51 0,67 20,74 3,91
3640 45 17,63 4,69 0,67 21,30 3,96
5200 70 17,75 4,83 0,67 21,75 4,00
30 °C
2540 30 16,80 3,93 0,68 --- ---
3640 45 17,00 4,10 0,68 --- ---
5200 70 17,14 4,22 0,68 --- ---
35 °C
2540 30 16,09 3,43 0,69 --- ---
3640 45 16,31 3,58 0,69 --- ---
5200 70 16,46 3,68 0,69 --- ---
40 °C
2540 30 15,33 3,00 0,70 --- ---
3640 45 15,55 3,13 0,70 --- ---
5200 70 15,72 3,21 0,70 --- ---
AWH 015 2.450 m3/h
AWH 018 2.800 m3/h
AQUALEAN - AWC/AWH - MIL118E-1407 / 10-2013
GENERAL CHARACTERISTICS
1.8.- CAPACITY TABLES
Water flow
Water
pressure drop
AWC/AWH
COOLING CAPACITY AWH
HEATING CAPACITY
Total capacity EER Sensible/Total Total capacity
Total absorbed
power
Water inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Water flow
Water
pressure drop
AWC/AWH
COOLING CAPACITY AWH
HEATING CAPACITY
Total capacity EER Sensible/Total Total capacity
Total absorbed
power
Water inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Nominal operating conditions:
Exchanger air inlet temperature: 27ºC DB/19ºC WB in cooling mode and 20ºC WB
in heating mode.
(DW:dry bulb / WB:wet bulb)
For another working conditions use correction factor tables.
Nominal airflow rate
Nominal airflow rate