
Installation and maintenance
R438
A.V.R.
3971 en - 11.2006 / c
LEROY-SOMER
9
the voltage between E+ and E- (approx.
10V D.C.). The best response times are
obtained at the limit of the instability. If no
stable position can be obtained, try
disconnecting or replacing the ST2 jumper
(normal/fast).
h
) Check LAM operation :
ST5
closed.
i)
Vary the frequency (speed) around 48 or
58 Hz according to the operating
frequency, and check the change in voltage
from that observed previously (~ 15%).
j
) Readjust the speed of the unit to its rated
no-load value.
Adjustments in parallel operation
Before any intervention on the
alternator, make sure that the speed
droop is identical for all engines
.
k
) Preset for parallel operation (with C.T.
connected to S1, S2)
- Potentiometer P1 (quadrature droop) in
centre position.
Apply the rated load (cos
ϕ
= 0.8 inductive).
The voltage should drop by 2 to 3%. If it
increases, check that V and W and also S1
and S2 have not been reversed.
l
) The no-load voltages should be identical
for all the alternators intended to run in
parallel.
- Couple the machines in parallel.
- By adjusting the
speed
, try to obtain
0 KW
power exchange.
- By altering the voltage setting P2 on one
of the machines, try to cancel (or minimise)
the current
circulating between the
machines.
- From now on, do not touch the voltage
settings.
m
) Apply the available load (the setting is only
correct if a
reactive
load is available)
- By altering the
speed
, match the
kW
(or
divide the rated power of the units
proportionally)
- By altering the quadrature droop
potentiometer
P1
, match or divide the
currents
.
3.2.2 - Max. excitation setting (excitation
ceiling)
Static adjustment of the current limit,
potentiometer P5 (factory setting: 7.5 A,
fuse rating: 8 A - 10 seconds).
The maximum factory setting corresponds
to that of the excitation current required to
obtain a 3-phase short-circuit current of
approximately 3 IN at 50 Hz for industrial
power, unless otherwise specified(*).
A static method can be used to reduce this
value or adapt the Isc to the actual
operating power (derated machine), which
is safer for the alternator and the
installation. Disconnect power supply wires
X1,X2 and Z1,Z2 and the voltage reference
(0-110V-220V-380V) on the alternator.
Connect the mains power supply using a
transformer (200-240V) as indicated
(X1,X2 : 48V). Install a 10A D.C. ammeter
in series with the exciter field. Turn P5 fully
anti-clockwise and activate the power
supply. If there is no output current from the
AVR, turn potentiometer P2 (voltage)
clockwise until the ammeter indicates a
stable current. Switch the power supply off,
then on again, turn P5 clockwise until the
required max. current is obtained (no more
than 8 A).
Checking the internal protection
:
Open switch (D) : the excitation current
should increase to its preset ceiling, remain
at that level for
≥
10 seconds and then drop
to < 1A.
Depending on
the mains frequency Main
(50/60 Hz supply)
Max. excitation
Voltage
Field
~ 5 ohms
X2
Z1
X1
Z2
E+
E-
0V
110 V
220 V
380 V
50Hz 60Hz
P2
P3
P5
ST3
10 A CC/DC
48 V
110/220/380 V
R 438
ST4
A+
–
A
D
3971c_NotRegR438_en.fm Page 9 Jeudi, 9. novembre 2006 10:13 10