
9
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI FMAX
MULTI F
SPECIFICATIONS
Multi F MAX Outdoor Units
Table 2: Multi F MAX Outdoor Unit General Data.
Model Number LMU480HV LMU540HV LMU600HV
Cooling Capacity (Btu/h) (Minimum ~ Rated ~ Maximum)114,400~48,000~58,000 14,400~52,500~63,200 15,600~60,000~68,000
Heating Capacity (Btu/h)(Minimum ~ Rated ~ Maximum)115,840~54,000~61,000 16,272~58,000~64,000 17,940~64,000~70,000
Operating Range
Cooling (°F DB) 147- 118 147- 118 147- 118
Heating (°F WB) -4 - 64 -4 - 64 -4 - 64
Compressor
Inverter Quantity Twin Rotary x 1 Twin Rotary x 1 Twin Rotary x 1
Oil Type FVC68D FVC68D FVC68D
Fan (Side Discharge)
Type Propeller Propeller Propeller
Motor Output (W) x Qty. 124.2 x 2 124.2 x 2 124.2 x 2
Motor/Drive Brushless Digitally Controlled/Direct
MaximumAir Volume (CFM) 2,119 x 2 2,119 x 2 2,119 x 2
Unit Data
Refrigerant Type R410A R410A R410A
Refrigerant Control/Location EEV / Outdoor Unit, Branch Distribution Unit
Min. Number Indoor Units/System2222
Max. Number Indoor Units/System2888
MaximumAllowable Total Indoor Unit Connected Capacity (Btu/h) 65,000 73,000 81,000
Sound Pressure ±3 dB(A)3(Cooling / Heating) 54 / 56 54 / 56 56 / 58
Net Unit Weight (lbs.) 214 214 223
Shipping Weight (lbs.) 236 236 249
Power/Communications Wiring Between ODU and BD Unit
(No. XAWG)4,5 4C X 16 4C X 16 4C x 16
Heat Exchanger
Material and Fin Coating Copper Tube /Aluminum Fin and GoldFin™/Hydrophilic
Rows/Columns/Fins per inch x Qty. (2 x 32 x 14) x 2 (2 x 32 x 14) x 2 (3 x 32 x 14) x 2
Piping
Liquid Line Connection (in., OD) x Qty. 3/8 x 1 3/8 x 1 3/8 x 1
Vapor Line Connection (in., OD) x Qty. 3/4 x 1 3/4 x 1 3/4 x 1
Factory Charge lbs. of R410A 9.7 9.7 12.3
Piping Lengths
Maximum Total System Piping (ft.)6475.7 475.7 475.7
Maximum Main Pipe Length (Outdoor Unit to BD Unit [ft.]) 180.4 180.4 180.4
Total Branch Piping (BD Units to all Indoor Units [ft.]) 295.3 295.3 295.3
Maximum Branch Pipe Length (Length between each
BDU and IDU [ft.]) 49.2 49.2 49.2
Maximum Outdoor Unit to Indoor Unit Pipe Length (ft.) 229.6 229.6 229.6
Max. Main Piping Length (NoAdditional Refrigerant (ft.) 16 16 16
Max. Branch Piping Length (NoAdditional Refrigerant (ft.) 131 131 147.6
Maximum Elevation between Outdoor Unit and Indoor Unit (ft.) 98.4 98.4 98.4
Maximum Elevation between Indoor Unit and Indoor Unit (ft.) 49.2 49.2 49.2
Maximum Elevation between BD Unit and Indoor Unit (ft.) 32.8 32.8 32.8
Maximum Elevation between BD Unit and BD Unit (ft.) 49.2 49.2 49.2
1Rated capacityapplied with non-ductedindoor units,and israted 0 ft.above sealevel with a0
ft. leveldifference betweenoutdoor andindoor units.All capacities arenet with acombination
ratiobetween 95 – 105%.
Rated coolingcapacity obtained withair enteringthe indoorunit at 80ºFdry bulb(DB) and 67ºF
wet bulb(WB) andoutdoor ambient conditionsof 95ºFdry bulb(DB) and75ºF wet bulb(WB).
Rated heatingcapacity obtained withair enteringthe indoorunit at 70ºFdry bulb(DB) and 60ºF
wetbulb (WB) and outdoorambient conditions of 47ºFdry bulb (DB) and43ºF wet bulb (WB).
2At least one Branch Distribution Unit is required for system operation; a maximum of two can
be installed per outdoor unit with use of Y-branch accessory (PMBL5620).At least two indoor
units should be connected. For allocated capacity information, see the combination tables in
the “Multi F / Multi F MAX Combination Data Manual” on www.lg-dfs.com. For performance
data, see “Multi F / Multi F MAX Performance Data Manual” on www.lg-dfs.com.
3Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
These values can increase due to ambient conditions during operation.
43RZHUZLULQJWRWKHRXWGRRUXQLWLV¿HOGVXSSOLHGVROLGRUVWUDQGHGDQGPXVWFRPSO\ZLWK
the applicable local and national codes. For detailed information, please refer to electrical
characteristics on page 11.
5All power wiring / communication cable to be minimum 16AWG from the outdoor unit to
the BD unit (Multi F MAX systems only), and 18AWG from the BD unit to the indoor unit,
stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the
outdoor unit only), and must comply with applicable local and national codes. For detailed
electrical information, please refer to electric characteristics on page 11.
6Piping lengths are equivalent.
7,QVWDOODWLRQRIDQRSWLRQDO/RZ$PELHQW:LQG%DIÀH.LWZLOODOORZRSHUDWLRQGRZQWR)LQ
cooling mode.