LG DHA1260HL User manual

Dehumidifier
SERVICE MANUAL
MODEL: DHA1260HR/HL
DHA1660HR/HL
CAUTION
- BEFORE SERVICING THE UNIT,
READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
- ONLY FOR AUTHORIZED SERVICE.
website http://www.lgservice.com
e-mail http://www.lgeservice.com/techsup.html

—2—
1. PREFACE
1.1 SAFETY PRECAUTIONS...........................................................................................................................3
1.2 FEATURES.................................................................................................................................................3
1.3 DIMENSIONS.............................................................................................................................................3
1.4 SPECIFICATIONS......................................................................................................................................4
1.5 CONTROL ..................................................................................................................................................6
1.6 HOW TO OPERATE DEHUMIDIFIER........................................................................................................6
1.6.1 HOW DOES THE DEHUMIDIFIER WORK? .....................................................................................6
1.6.2 LOCATION FOR THE DEHUMIDIFIER.............................................................................................6
1.6.3 SWITCH ASSEMBLY, MICRO..........................................................................................................7
1.6.4 THERMOSTAT AND SOLENOID VALVE(Hot gas defrost) ..............................................................7
1.6.5 HUMIDISTAT.....................................................................................................................................7
1.6.6 DRYER ASSEMBLY..........................................................................................................................7
2. CIRCUIT DIAGRAM............................................................................................................................8
3.
DISASSEMBLY INSTRUCTIONS
3.1 MECHANICAL PARTS ...............................................................................................................................9
3.1.1 BUCKET AND AIR FILTER...............................................................................................................9
3.1.2 FRONT GRILLE.................................................................................................................................9
3.1.3 CONTROL PANEL AND CABINET...................................................................................................9
3.2 CONTROL PARTS AND CYCLE PARTS.................................................................................................10
3.2.1 ROTARY SWITCH AND HUMIDISTAT...........................................................................................10
3.2.2 NEON LAMP....................................................................................................................................10
3.2.3 FAN AND MOTOR...........................................................................................................................10
3.2.4 SHROUD.........................................................................................................................................10
3.2.5 DRAIN PAN.....................................................................................................................................11
3.2.6 TERMINAL BLOCK .........................................................................................................................11
3.2.7 MICRO SWICH ASSEMBLY ...........................................................................................................11
3.2.8 THERMOSTAT................................................................................................................................11
3.2.9 P.T.C. ASSEMBLY OR OVERLOAD PROTECTOR (O.L.P.) .........................................................12
3.2.10 COMPRESSOR ............................................................................................................................12
3.2.11 POWER CORD ASSEMBLY.........................................................................................................12
3.3 REFRIGERATING CYCLE .......................................................................................................................13
3.3.1 CONDENSER ASSEMBLY AND EVAPORATOR ASSEMBLY
(HEAT EXCHANGE ASSEMBLY)...................................................................................................13
3.3.2 CAPILLARY TUBE ASSEMBLY......................................................................................................13
3.4 HOW TO REPLACE REFRIGERATION SYSTEM...................................................................................14
4. TROUBLESHOOTING GUIDE...................................................................................................16
5. EXPLODED VIEW - INTRODUCTION..................................................................................19
6. REPLACEMENT PARTS LIST...................................................................................................23
CONTENTS

—3—
1. PREFACE
This Service Manual provides various service information, containing the mechanical and electrical parts etc.
This dehumidifier was manufactured and assembled under the strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precaution prior to servicing the unit.
1.1 SAFETY PRECAUTIONS
• Disconnect power supply before servicing or replacing any electrical or non-electrical component.
• Do not, under any circumstances, cut off the grounding prong or alter the plug in any manner.
1.2 FEATURES
• High efficiency
• Quiet
• Adjustable humidistat
• Hot gas defrost
• Automatic shut-off
• Water-full indicator light
• Easy roll casters
• Removable & large capacity bucket
• Washable air filter
• Fan speed: High/Low 2 fan speeds
• Drain hose connection.
• Power ON/OFF indicator light.
1.3 DIMENSIONS (mm/in)
320 (12 9/16) 340 (13 3/8)
530 (20 13/16)
320 (12 9/16)
530 (20 13/16)
HighLow
8
Humidity Control
Fan Speed O
1
2
3
456
7
9
Max.
L
o
w
H
i
g
h
Fan Speed
Dryness Control
N
o
r
m
a
l
D
r
y
n
e
s
s
MaxO
• DHA1260HR • DHA1260HL
• DHA1660HR • DHA1660HL

—4—
1.4 SPECIFICATIONS
DHA1260HL/HR
CAPACITY 32˚C 80% RH
(/Day) 27˚C 60% RH
POWER SUPPLY (Phase, V, Hz)
REFRIGERANT
REFRIGERANT CHARGE, g
THERMOSTAT
HUMIDISTAT
COMPRESSOR MODEL NO.
TYPE
RESISTANCE(at 25˚C)
TYPE
SWITCH, ROTARY
MOTOR ASSEMBLY, SINGLE
SWITCH ASSEMBLY, MICRO
NET WEIGHT, kg
MODELS
ITEMS
P.T.C.
ASSEMBLY
OUTSIDE DIMENSIONS
W x H x D, mm(in)
OVERLOAD
PROTECTOR
NOTE : Specifications are subject to minor change without notice for further improvement.
12
6
1ø, 220~240V, 50Hz
R134a
170
OPEN : -8˚C 1.5˚C
CLOSE : 3˚C 1.5˚C
CONTROL RANGE : 20% ~ 80% RH
NORMAL SETTING : 42 5% RH
NR45HAEG
P330MC/ MRA12091-9010
33 Ω
TI. No 4TM213SFB
OPENING TEMP.: 135˚C CLOSING TEMP.: 61˚C TRIP CURRENT: (60˚C) 1.7 ~ 2.1A
20A, 125/250VAC
4P, 19~23W, 0.11~0.13A, T.P: 17AM033A5-4(266°F/130°C)
6A, 250VAC
320 x 530 x 340 (12 9/16 x 20 13/16 x 13 3/8)
19

—5—
DHA1660HL/HR
CAPACITY 32˚C 80% RH
(/Day) 27˚C 60% RH
POWER SUPPLY (Phase, V, Hz)
REFRIGERANT
REFRIGERANT CHARGE, g
THERMOSTAT
HUMIDISTAT
COMPRESSOR MODEL NO.
TYPE
RESISTANCE
TYPE
SWITCH, ROTARY
MOTOR ASSEMBLY, SINGLE
SWITCH ASSEMBLY, MICRO
NET WEIGHT, kg
MODELS
ITEMS
P.T.C.
ASSEMBLY
OUTSIDE DIMENSIONS
W x H x D, mm(in)
OVERLOAD
PROTECTOR
NOTE : Specifications are subject to minor change without notice for further improvement.
16
8
1ø, 220~240V, 50Hz
R134a
190
OPEN : -10˚C 2˚C
CLOSE : 5˚C 2˚C
CONTROL RANGE : 20% ~ 80% RH
NORMAL SETTING : 42 5% RH
NR62HAEG
P330MC / MRA12091-9010
33 Ω
TI.NO. 4TM232VFB
OPENING TEMP.: 120˚C CLOSING TEMP.: 61˚C TRIP CURRENT: (70˚C) 2.3A
20A, 125/250VAC
4P, 19~23W, 0.11~0.13A, T.P: 17AM033A5(266°F/130°C)
6A, 250VAC
320 x 530 x 340 (12 9/16 x 20 13/16 x 13 3/8)
20

1.6.1 HOW DOES THE DEHUMIDIFIER WORK?
The dehumidifier, as shown in Figure 1, consists of a
small refrigerant system and a fan. The fan pulls
humid air from the room, across the cold evaporator
coil where the water drips off into a bucket or drain
hose.
1.6.2 LOCATION FOR THE DEHUMIDIFIER
1. In order for the unit to operate effectively, all doors,
windows and other openings should be closed.
Moisture-laden outdoor air will only add to the
dehumidifier's operating load.
2. Allow at least 12 inches of space on all sides of the
unit for good air circulation.
3. Install your dehumidifier on a floor, table, or shelf.
When installing the dehumidifier on a table or shelf,
make sure the table or shelf is strong enough to
support the weight of the dehumidifier with a full
bucket. Do not sit or stand on the dehumidifier.
NOTE: The height of a table or shelf might provide
a better position from which to handle the
bucket and help prevent icing of the coils
due to colder air near the floor (such as in a
basement).
Humidity Control
•The Humidity Control can be set anywhere between
Off and Max for normal operation. If you need more
dehumidification, turn the Humidity Control toward
Max. If you need less dehumidification, turn the
Humidity Control toward Off.
•Turn the Humidity Control to Off to stop the unit
manually.
Fan Speed
•If you want to control the speed of air flow, turn the
Fan Speed toward Low or High.
Auto Shut-Off
RED : BUCKET IS FULL, POWER OFF
GREEN : OPERATING
•When the bucket is full, operation automatically shuts
down and the lamp light changes too.
—6—
HighLow
8
Humidity Control
Fan Speed O
1
2
3
456
7
9
Max.
L
o
w
H
i
g
h
Fan Speed
Dryness Control
N
o
r
m
a
l
D
r
y
n
e
s
s
MaxO
Dry
Air Out Humid
Air In
Fan
Compressor
Side View
Bucket
Condenser
Assembly Evaporator
Assembly
Motor
Assembly
12"
Air In
Air Out
12"
Figure 1
Figure 2
1.6 HOW TO OPERATE DEHUMIDIFIER
1.5 CONTROL
•DHA1260HL, DHA1660HL
•DHA1260HR, DHA1660HR

1.6.5 HUMIDISTAT
Humidistat maintains the constant relative humidity in the
room automatically to satisfy particular need.
(When the relative humidity in the room increases to the
selected level, the dehumidifier starts automatically.) Once
the relative humidity drops to the selected level, the
dehumidifier stops automatically.
When first using the dehumidifier, it is recommended, for
the first three or four days, to operate the unit with the
humidistat control set at the MAX. At this setting, the unit
will run continuously.
When the sweating has stopped and the dampness odors
have gone, it is preferable to select the humidistat position
that will best suit local conditions.
The relative humidity range it can control is from 20 % to
80%. (See Figure 3)
NOTE: The relative humidity at the number is the
approximate value.
1.6.6 DRYER ASSEMBLY
Dryer is used to prevent water from overflowing in all tubes
and H/E assembly-condenser assembly and evaporator
assembly-and an acid, water and bad material from heating
oil. Also, dryer is used to remove corrosion of the
components.
NOTE: When dryer is replaced, proper injection to
capillary is needed. On opening the dryer, it
should be welded instantly. The oxidization of
dryer inside and all tubes inside after welding
can be prevented.
—7—
42% R.H 40%
7(30%)
6(35%)4(50%)
3(60%)
2(70%)
1(80%)
5(42%)
8(25%)
9(20%)
Max.ODEAD DIAL
Dryer
Figure 4
Figure 3
MODEL: DHA1260HL/HR, DHA1660HL/HR
1.6.3 SWITCH ASSEMBLY, MICRO
The micro switch assembly, which is located on the back of the unit, automatically shuts off the dehumidifier when the bucket is
full (note, the Auto Shut Off lights, to indicate bucket must be emptied). Once the bucket has been emptied and replaced, the
unit once again turns itself on.
1.6.4 THERMOSTAT AND SOLENOID VALVE (Hot gas defrost)
The THERMOSTAT senses frost build-up on the evaporator coil and automatically shuts off the fan. The compressor continues
to run, hot gas(solenoid valve is open) is supplied through the coil and melting the frost. When the coil is defrosted, the fan
automatically restarts, and hot gas valve is closed, and dehumidifying resumes.

—8—
2. CIRCUIT DIAGRAM
•MODEL : DHA1260HL/HR, DHA1660HL/HR
LAMP,
NEON
SOLENOID
VALVE
TERMINAL
BLOCK
P.T.C.
WIRING DIAGRAM
3854A20005A
O.L.P.
SWITCH,
ROTARY
SWITCH,
LAMP
C
YL
BL
BR
6
4
1
1
2
HUMIDISTAT
THERMOSTAT
1
2
SC
M
COMP.
RD
RD(BL)
BK
BK
BK RD
BR(L)BL(N)
GR/YL
BK
WH
WH
LH
C
BL
BL
N.O N.C
MOTOR
Q'TY
PER SET
1
1
1
1
1
1
1
1
1
1
1
1
RE-
MARKS
S
S
S
S
S
S
S
S
S
S
S
S
LOCATION
NO.
1
2
3
4
5
6
7
8
9
10
11
12
DESCRIPTION
POWER CORD ASSEMBLY
SWITCH, ROTARY
MOTOR ASSEMBLY, SINGLE
P.T.C. ASSEMBLY
COMPRESSOR
O.L.P.
LAMP, NEON
THERMOSTAT
HUMIDISTAT
SWITCH ASSEMBLY, MICRO
TERMINAL BLOCK
SOLENOID, COIL
DHA1260HL/HR DHA1660HL/HR
2H01159Y/ 6411A20001B
6600A20001A
4681A20002D
6748C-0003C
5416A20009A 5416A20009B
6750C-0005M
6912A30001B
2H01127E 2H01127F
5216A20001A
6600A30003B
3H00390A
6421A90001C
PART NO.
S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS
2H01159Y/ 6411A20001B
3H01652Q(For H.K)

3.1 MECHANICAL PARTS
3.1.1 BUCKET AND AIR FILTER
1. Disconnect the power supply.
2. Turn the Humidity Control off.
3. Remove the bucket (See Figure 5)
4. Flex the filter at the lower right corner and take it
off. (See Figure 5)
5. Replace the filter by referring to the removal
procedure above.
3.1.2 FRONT GRILLE
1. Remove 2 screws which fasten the front grille.
2. By pushing both sides front grille, pull the front grille
forward and upward. (See Figure 6)
3. Replace the front grille by referring to the removal
procedure above.
3.1.3. CONTROL PANEL AND CABINET
1. Remove the bucket, air filter, and front grille
according to the procedure above.
(Refer to 3.1.1/ 3.1.2)
2. Remove control panel by removing 3 screws.
(See Figure 7)
3. Remove 7 screws on all sides of the cabinet.
(See Figure 7)
4. Lift the cabinet from the base. (See Figure 8)
5. Replace the component by referring to the removal
procedure above.
—9—
3. DISASSEMBLY INSTRUCTIONS
1
2
Push
Push
Figure 5
Figure 6
Figure 7 Figure 8

3.2.1 ROTARY SWITCH AND HUMIDISTAT
1. Remove the cabinet (Refer to section 3.1.3)
2. Disconnect all leads of rotary switch and
humidistat.
3. Remove 4 screws which fasten the rotary switch
and humidistat. (See Figure 9)
4. Replace the components by referring to the
removal procedure above.
3.2.2 NEON LAMP
1. Remove the cabinet (Refer to section 3.1.3)
2. Disconnect two leads.
3. Pull neon lamp out. (See Figure 10)
4. Replace the cabinet by referring to the removal
procedure above.
3.2.3 FAN AND MOTOR
1. Remove the cabinet. (Refer to section 3.1.3)
2. Disconnect all the leads of control panel assembly.
3. Remove 4 screws which fasten the motor mount.
(See Figure 11)
4. Remove 2 nuts which secure the motor.
(See Figure 11)
5. Remove one nut which fastens the fan.
(See Figure 11)
6. Remove the fan forward carefully like, as shown by
the arrow. (See Figure 11)
7. Replace the components by referring to the
removal procedure above.
3.2.4 SHROUD
1. Remove the motor mount. (Refer to section 3.2.3)
2. Remove 4 screws which fasten the H/E assembly.
(See Figure 12)
3. Remove discharge and suction tube assembly.
4. Remove 4 screws which fasten the shroud.
(See Figure 12)
5. Remove the shroud from barrier. (See Figure 12)
6. Replace the component by referring to the removal
procedure above.
—10—
3.2 CONTROL PARTS AND CYCLE PARTS
Figure 9
Figure 10
Figure 11
Figure 12

3.2.5 DRAIN PAN
1. Remove the shroud. (Refer to section 3.2.4)
2. Remove 2 screws which fasten drain pan.
3. Remove drain pan by unhooking both sides slots.
(See Figure 13)
4. Replace the components by referring to the
removal procedure above.
3.2.6 TERMINAL BLOCK
1. Remove the cabinet. (Refer to section 3.1.3)
2. Disconnect all the leads terminal block.
3. Unfasten the screw which fastens the terminal
block. (See Figure 14)
4. Replace the components by referring to the
removal procedure above.
3.2.7 MICRO SWITCH ASSEMBLY
1. Remove the cabinet. (Refer to section 3.1.3)
2. Disconnect all the leads of micro switch assembly.
3. Turn the nut left and take off the micro switch
assembly. (See Figure 14)
4. Replace the components by referring to the
removal procedure above.
3.2.8 THERMOSTAT
1. Remove the cabinet. (Refer to section 3.1.3)
2. Disconnect all leads of thermostat.
3. Remove the THERMOSTAT. (See Figure 15)
4. Replace the components by referring to the
removal procedure above.
—11—
Push
Push
Thermostat
Figure 13
Figure 14
Figure 15

1. Remove the cabinet. (Refer to section 3.1.3)
2. Remove a screw or a nut which fastens the
terminal cover
3. Disconnect the lead wire from the overload
protector or P.T.C. assembly.
4. Remove the overload protector or P.T.C. assembly.
(See Figure 16)
5. Replace the component by referring to the removal
procedure above.
3.2.10 COMPRESSOR
1. Remove the cabinet. (Refer to section 3.1.3)
2. Discharge the refrigerant by using a refrigerant
Recovery System.
3. After purging the unit completely, unbrace the
suction and discharge tubes at the compressor
connections.
4. Remove the nuts and washers which fasten the
compressor. (See Figure 16)
5. Remove the compressor. (See Figure 16)
6. Replace the component by referring to the removal
procedure above.
3.2.11 POWER CORD ASSEMBLY
1. Remove the cabinet. (Refer to section 3.1.3)
2. Remove a screw which fastens the earth wire of the
power cord assembly. (See Figure 17)
3. Disconnect the lead wire from terminal block and
micro switch assembly.
4. Remove the power cord assembly. (See Figure 17)
5. Replace the component by referring to the removal
procedure above.
—12—
Figure 16
Figure 17
3.2.9 P.T.C. ASSEMBLY OR OVERLOAD PROTECTOR (O.L.P.)

—13—
3.3 REFRIGERATING CYCLE
1. Remove the motor mount. (Refer to 3.2.3)
2. Pierce the pinch-off tube to discharge the
refrigerant, using a FREONTM recovery system.
3. Remove the insulation on the H/E assembly
4. After discharging the refrigerant completely,
remove 4 screws between the shroud and H/E
assembly. (See Figure 18)
5. Unbrace two interconnecting tubes of the
compressor.
6. Remove the H/E assembly from the shroud.
(See Figure 19)
7. Unbrace the interconnecting tube at the
connections of each condenser and evaporator
assembly.
8. Remove 4 screws between condenser and
evaporator assembly. (See Figure 20)
9. Replace the component by refering to the note
above.
3.3.2 CAPILLARY TUBE ASSEMBLY
1. Remove the H/E assembly. (Refer to section 3.3.1)
2. After discharging the refrigerant completely,
unbrace the connecting pipes of capillary assembly
and pulling them outward. (See Figure 21)
3. Replace the component by referring to the note
above.
Figure 18
Figure 19
Figure 20
Figure 21
3.3.1 CONDENSER ASSEMBLY AND EVAPORATOR
ASSEMBLY(HEAT EXCHANGE ASSEMBLY)

—14—
1. When replacing the refrigeration cycle, be sure to
discharge the refrigerant system by using a
refrigerant recovery system.
2. After discharging the unit completely, remove the
desired component, and unbrace the pinch-off
tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Solder the pinch-off tubes with service valves.
5. After doing the above procedures, the valve must
be closed and left in place on the system for any
subsequent procedures.
6. Evacuate as follows.
1) Connect the vacuum pump, as illustrated in
Figure 22A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns
counterclockwise and leave the valves closed.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vacuum are obtained. Close
valves A and B, and observe vacuum gauge for
a few minutes. A rise in pressure would
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See Figure 22B.
Open valve C.
Discharge the line at the manifold connection.
5) The system is now ready for final charging.
7. Recharge as follows :
1) Refrigeration cycle systems are charged from the
High-side. If the total charge cannot be put
in the High-side, the balance will be put in the
suction line through the access valve which you
installed as the system was opened.
2) Connect the charging cylinder as shown in Figure
22B.
With valve C open, discharge the hose at the
manifold connection.
3) Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not
take it. Close valve A.
5) With the unit running, open valve B and add the
balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs.
c. Turn off valve B and allow pressure to drop.
d. Repeat steps B and C until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly,
use the pinch-off tool with the unit still running
and clamp on to the pinch-off tube. Using a tube
cutter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos solder and solder
pinch-off tube closed. Turn off the unit, allow it to
set for a while, and then test the leakage of the
pinch-off connection.
If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being drawn
into the vacuum pump.
CAUTION
3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM
NOTE: THE REFRIGERANT R134a IS
USED ONLY FOR THE MODEL
DHA1260HL/HR, DHA1660HL/HR.
When discharging refrigerant R134a, purging
instrument should be used only for R134a, without
mixing that of refrigerant R22.
When checking the leakage of refrigerant R134a,
leakage test tool should be used only for R134a.
The pump for discharging should be high efficiency.
Final discharging value must be managed below 0.5
Torr.
Maximum water should be less than quantity 150mg
in the cycle-all tubes and H/E assembly-system.
If water quantity is over 150mg, it causes acid or
corrosion in the cycle system and the capillary tube
to be clogged by water and harmful materials.
The model must use dryer to prevent water from
overflowing.

—15—
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment. pinch-off tool capable
of making a vapor-proof seal, leak detector, tubing cutter, hand tools to remove components, service valve.
A
B
COMPRESSOR
CAPILLARY
TUBE
COMPOUND GAUGE
MANIFOLD
GAUGE
SEE INSETS
BELOW
CONDENSER ASSEMBLY
(HIGH PRESSURE SIDE)
EVAPORATOR ASSEMBLY
(LOW PRESSURE SIDE)
EXTERNAL
VACUUM PUMP
CHARGING
CYLINDER
HILOW
A
BA
B
C
A
B
CAPILLARY TUBE
COMPOUND GAUGE
MANIFOLD
GAUGE
SEE INSETS
BELOW
CONDENSER ASSEMBLY
(HIGH PRESSURE SIDE)
EVAPORATOR ASSEMBLY
(LOW PRESSURE SIDE)
COMPRESSOR
Figure 22A-Pulling Vacuum Figure 22B-Charging

—16—
The dehumidifier does not
run. Check if humidistat is set to
a low level. Set humidistat on a higher
level.
Check if bucket full lamp
is lit ON. Empty the water in the
bucket.
Can not dehumidify.
Ineffective dehumidifying
Noisy
Repair gas leak.
Check circuit breaker. Turn the circuit breaker on.
Check if wiring fails. Replace wiring.
Check if the main unit is
securely positioned.
Check for gas leakage at
heat exchange Assembly
and connecting tube.
Set and use the
dehumidifier at a sturdy, flat,
and level place.
Clean the air filter.Check if the air filter
are clogged with dust.
Check if motor Assembly fails.
Replace motor Assembly.
Check if compressor fails. Replace compressor.
Check if thermostat fails. Replace thermostat.
Check if wiring fails. Replace wiring.
Check if wiring loose. Connect it tightly.
CONDITION CAUSE REMEDY
4. TROUBLESHOOTING GUIDE

CONDITION
1. Dehumidifier does not operate. (Both
compressor and fan motor do not
operate.)
2. Motor Assembly runs but compressor
does not run.
3. Thermostat does not start.
4. Insufficient dehumidification
CAUSE
No power
Poor plug contact at outlet.
Bucket is full.
Humidity control is at Off position
Wire disconnected or connection loose
Voltage (220 ~240V ± 10%)
Wiring
Rotary switch
Compressor
Overload protector (O.L.P.)
Thermostat is defective.
Low relative humidity
Poor air circulation
H/E Assembly clogged with dust and dirt
Air filter is dirty.
Motor Assembly is not operating.
REMEDY
C
heck power supply at outlet.
Correct if none.
Install plug properly or replace it.
If Auto Shut Off lights, empty the bucket.
Turn the humidity control switch toward
Max.
Connect wire. Refer to wiring diagram for
terminal identification. Repair or replace
loose terminal.
It must be between 198V and 264V. If not
within limits, call an electrician
Check the wire connections; If loose,
repair or replace the terminal. If the wires
are disconnected, refer to wiring diagram
for identification, and replace the wires.
Check the wire connections; If not
according to the wiring diagram, correct
the connections.
Check for continuity, refer to the wiring
diagram for terminal identification. Replace
the switch if the circuit is open.
Check the compressor for open circuit or
ground. If open or grounded, replace the
compressor.
Check the compressor O.L.P. if externally
mounted. Replace if open. (If the
compressor temperature is high, remove
O.L.P., cool, and retest.)
Check thermostat, replace it.
Turn dehumidifier off.
Move dehumidifier to obtain free and
unobstructed air circulation.
Clean evaporator and/or condenser assembly
Clean it.
Check Motor Assembly, repair or replace it.
—17—

—18—
CONDITION
5. Noisy operating
6. Water drips
7. Compressor cycles on overload
protector. (O.L.P.)
CAUSE
Fan
Foreign material plunged and rattle.
Tube hits frame.
Fan blade hits frame
Internal compressor noise.
Loose set screws
Worn bearings of Motor Assembly
The bucket is not installed properly.
Poor drain hose connection.
Leak in bucket
Water drips when bucket removed for
emptying.
Bucket overflows.
High or low line voltage.
(220~240V ± 10%)
Poor air circulation.
H/E Assembly clogged with dust or dirt.
Motor Assembly
Bad P.T.C. assembly
Short circuit or ground in electrical circuit
Unit pressures not equalized
Wiring
Refrigeration system
Stuck compressor
Overload protector (O.L.P.)
REMEDY
If cracked, out of balance, or partially
missing, replace it
Remove it.
Adjust tubing routine carefully.
Check Motor Mount. If loose, tighten it.
Replace compressor.
Tighten them.
If knocking sounds continue when running
or loose, replace the motor. If the motor
hums or noise appears to be internal while
running, replace motor assembly.
The bucket should be properly positioned
on the hangers of the drain pan.
Check connection and repair.
Replace bucket.
Before removing bucket, the unit should
be turned off.
Check micro switch.
Check line voltage. It must be between
198V and 264V volts.
If intermittent, provide new supply.
Move dehumidifier for free and
unobstructed air flow.
Clean dust or dirt on the H/E Assembly.
If not running, determine the cause.
Replace if required.
Check P.T.C. assembly, Repair.
Check electrical circuit. Repair.
Allow 2 or 3 minutes for pressure to
equalize before starting compressor.
Check the terminals. If loose, repair or
replace.
Check the system for a restriction.
Check compressor, replace compressor
Check O.L.P., if externally mounted.
Replace if open. (If the compressor
temperature is high, remove the O.L.P.,
cool, and retest.)

5. EXPLODED VIEW - INTRODUCTION
—19—
OUTER CASE PARTS
OUTER CASE PARTS
CONTROL PARTS
CYCLE PARTS

—20—
• OUTER CASE PARTS AND CONTROL PARTS
2 7
5
8
4
1
15
9
6
3
6
3
14
13
11
10
12
•MODEL: DHA1260HL
DHA1660HL
•MODEL: DHA1260HR
DHA1660HR
17
16
This manual suits for next models
3
Table of contents
Other LG Other manuals