Lindsay GrowSmart Multi-Control User manual

Multi-Control
Operation Manual
P/N 1604010 Rev D (ECN 35207)


GS-1 Standard Controls
General Safety Instructions
General Safety Instructions for Controls
WARNING
Personal Safety: Through out this manual and on all safety signs, the precautionary statements
(“DANGER”, “WARNING”, “CAUTION” and “NOTICE”) can be found, followed by a hazard description
and preventative actions to be taken. These precautions are intended for the personal safety of the operator and
those within the vicinity of the machinery. Please take time to read these precautions.
Hazard Severity Panels
Background
Color of
Panel
Contrast
Color
Meaning/Use Hazard Severity Panel Illustration
Red White Indicates a hazardous situation, that, if not
avoided, will result in death or serious injury.
Orange Black Indicates a hazardous situation, that, if not
avoided, could result in death or serious injury.
Yellow Black Indicates a hazardous situation, that, if not
avoided, could result in minor or moderate
injury.
Blue White Indicates information considered important, but
not hazard- related (e.g. messages relating to
property damage).
NOTICE
Machine Integrity: Additional precautionary statements (“ATTENTION” and “IMPORTANT”) are intended
for machine integrity and are followed by specic instructions.
ATTENTION: The word “ATTENTION” is used to warn the operator of potential machine damage if a certain pro-
cedure is not followed.
IMPORTANT: The word “IMPORTANT” is used to provide the reader with information necessary to prevent minor
machine damage if a certain procedure is not followed.
WARNING: All maintenance and service must be performed by a Lindsay Dealer.

GS-2 Standard Controls
General Safety Instructions
WARNING
Lock Out/Tag Out: Disconnect all sources of energy and lock out machine before doing any
maintenance or repairs to the machine. Proper Lock Out procedures will prevent the energy source from
starting the machine or allowing parts to move unexpectedly
as well as prevent the machinery from being accidentally
turned on or restarted. Shut off and Lock Out all sources of
potential or kinetic energy. These may include, but are not
limited to, electrical, mechanical or hydro energy sources.
Lock Out is a procedure used for placing an actual locking de-
vice on the power source, preventing unexpected start up or
accidental release of energy. Lock Out is the preferred method
of accident prevention.
Tag Out procedure is used when the power can not be discon-
nected. Tag Out’s do not shut down the power source, Tag
Out’s only provide a warning about the danger of activating the machine.
Never try to operate machinery that is locked out or tagged out. Never attempt to remove these locks or tags on
machinery. Doing so will result in injury to personnel working on the machine. Only the initiator of the Lock Out or
Tag Out procedure may remove locks and tags.
WARNING
Main Disconnect: The main power disconnect is located at the main service breaker or
generator. The disconnect at the panel is not the main disconnect. A fusible service disconnect device
must be placed previous to this panel with the fuses sized for the load being supplied and installed in
accordance to NEC codes.
It is important to understand the differences between the Pivot Enable switch (if installed), High Voltage On/Off
switch and the service breaker On/Off throw switch.
The power company service disconnect provides the ability to turn off or return full service to the equipment from
the power company service line. This switch must be turned off and locked out when performing maintenance and
repairs on the system.
The High Voltage On/Off provides the ability to turn off or return power to the equipment from the service discon-
nect. This switch must be turned off and locked out in conjunction with the service disconnect switch. The High
Voltage switch only disconnects the power in the control panel, as energy is still coming in from the main power
line.
The Pivot Enable switch (if installed) provides power to the system controls. When enabled, the entire system and
the controls will power up. When turned off, the controls and system will not be energized. However, there will be
power in the panel circuitry. The Pivot Enable switch is NOT a disconnect and should not be treated as such.

GS-3 Standard Controls
General Safety Instructions
WARNING
Training: All individuals involved in the installation, operation or maintenance of this equipment must
receive and understand training in the safe and proper methods of performing all duties assigned to them
at the time of the initial assignment and at least annually thereafter. Safety messages and appropriate
response procedures to emergencies or other situations which may arise should be fully understood.
WARNING
Follow Safety Instructions: Carefully
read all safety messages in this manual and safety
signs on the machinery. Keep safety signs in legible
condition. Replace any missing or damaged safety signs.
Learn how to operate the machine and controls properly. Do
not allow anyone to operate the machinery without proper
instructions.
Keep the machine in proper working condition. Only have the
machine serviced by a trained service technician on a routine basis. Unauthorized modications to the machine
may impair the function and/or safety and reduce the life of the machine.
CAUTION
Practice Safe Maintenance: Understand maintenance procedures before doing work.
Always follow proper Lock Out/Tag Out procedures before performing any maintenance.
Never lubricate or service machine while it is moving. Keep hands, feet and loose clothing from power-driven
parts. Disengage all power and operator controls to relieve pressure. Allow all heat-generating units to cool.
Keep all parts in good condition. Remove any build up of grease, oil and debris. Ensure that all parts have been
properly installed by a certied technician.
Tower alignment, pressure switch adjustment and tower control switch adjustment must be performed by a quali-
ed service technician.
WARNING
Electric Shock: Follow these precautions to prevent serious injury or death.
DO NOT allow moisture to enter the main panel. Moisture can allow voltage to conduct across surfaces, creating a
shock potential.
Dangerous voltage potential may be present at lightning arrester. Visually inspect arrester before each operation.
If lightning arrester shows signs of impairment, contact a Lindsay Dealer.
WARNING
Electrical Connections: Keep all sparks and ames away from battery, as gases given off by
electrolyte are explosive. Avoid sparks by connecting the ground cable last and disconnecting it rst.
CAUTION
Weather Conditions: Always be aware of weather conditions (extreme heat/cold, snow, rain,
sleet, heavy precipitation and high winds). Schedule work or maintenance only when the weather condi-
tions are mild and dress appropriately for the climate.

GS-4 Standard Controls
General Safety Instructions
CAUTION
Lightning Strikes: Do not attempt to access the system if lightning or thunder have been de-
tected in the area. Wait 30 minutes after the last sighting of lightning or sound of thunder before access-
ing the system.
WARNING
Inspecting the System Prior to Operation: Always inspect the system before
operation. If the system appears impaired, do not operate the machinery and contact a Lindsay Dealer.
CAUTION
Wear Proper PPE: Always wear appropriate (NFPA 70E and
OSHA Compliant) Personal Protective Equipment (PPE) for the task
being performed. At a MINIMUM, the following are required equipment:
Ear Protection:
Prolonged exposure to loud noise can cause impairment or loss of hearing.
Wear a suitable hearing protective device such as earmuffs or earplugs to pro-
tect against uncomfortably loud noises.
The A-weighted emission sound pressure level at the pivot point does not ex-
ceed 70 dB.
Eye Protection:
Sharp Objects, debris and explosions can cause severe eye damage or blind-
ness. Wear Safety Standard approved protection that fully shields the eyes.
Additionally, wear a clear plastic face shield that fully surrounds the face from
brow to chin and covers the entire width of the face.
Foot Protection:
Prevent damage from falling or dropped objects on the feet by wearing steel-
toe shoes/boots with metatarsal protection.
Head Protection:
Prevent damage from falling or dropped objects on the head by wearing a Class G Hard Hat for head protection.
Gloves
Prevent electrical shock hazards, cuts and burns to the hands by wearing protective rubber gloves-class 0 with
leather protector and cloth liner.
CAUTION
Proper Work Platform: Provide a good work/standing platform for personnel to access the
machine. Elevated platforms and ladders must have restraints or railings in place before climbing or
lifting.
CAUTION
Proper Area Lighting: The owner shall provide area lighting as may be required.

GS-5 Standard Controls
General Safety Instructions
WARNING
Repairing the System: In the event that the Zimmatic System needs to be repaired;
disconnect the power source, depressurize the system and contact the Lindsay Dealer.
Only a Lindsay Dealer should make necessary repairs to the system.
Ensure that only Genuine Lindsay Parts are used on the system.
WARNING
Overhead Maintenance: Overhead maintenance should be performed by a Lindsay Dealer.
Never attempt to climb on an irrigation machine for any reason.
WARNING
Lifting Components: Extreme care is needed for lifting components during installation/
assembly. Only a Lindsay Dealer using the proper lifting equipment may perform this task.
Use caution when lifting heavy objects. Components weighing in excess of 50 lbs. (22.7 kg.) must be lifted with
the assistance of another individual or mechanical lifting device.
Do not work or stand under system or components during assembly. Due to the weights involved, severe injury or
death can result if components should fall.
WARNING
Dismantling the System: If it is ever necessary to dismantle a Zimmatic System, extreme
care must be taken. As with installation and assembly, dismantling must only be performed by a Lindsay
Dealer.
WARNING
Impaired Safety Protection: Do not attempt to operate if protection may be impaired. If the
equipment appears to have been changed or operates abnormally, protective devices may be impaired.
Do not attempt to operate and have the equipment serviced by a Lindsay Dealer.
WARNING: Ensure that power is turned off/disconnected before removing any protective covers.
WARNING: Do not use this product in a manner not specied in this manual.
CAUTION
Prepare for Emergencies; Be prepared for any emergency that may occur. Keep emergency
numbers for doctors, hospital, ambulance service and re department near your telephone.

GS-6 Standard Controls
General Safety Instructions
Earth Ground Protective Earth Ground Frame or Chassis Ground
The following symbols indicate grounding connections that can be found on irrigation systems.

P/N 1604010 Rev D (ECN 35207) Multi-Control Operation Manual
Table of Contents
Table of Contents
General Safety Instructions for Controls .............GS-1
Section 1- Specications and Compliance ............. 1-1
Requirements for Electrical Service ......................................................1-1
Compliance Standards.................................................... 1-1
Federal Communications Commission (FCC) Statement ....................1-1
Industry Canada Compliance Statement...............................................1-1
WEEE Statement......................................................................................1-1
Product Specications............................................................................1-2
Dimensional Data and Weight ................................................................1-3
Service .............................................................................. 1-4
Panels & Panel ID Locations........................................... 1-5
Micro-Controller Panel ............................................................................1-5
Expansion Panel ......................................................................................1-6
Wireless Switch .......................................................................................1-7
Section 2 - Operation ................................................ 2-1
Introduction to Multi-Control (MC) ................................. 2-1
Panel Controls.................................................................. 2-2
Section 3 - Service..................................................... 3-1
System Alerts ................................................................... 3-1
Seasonal Maintenance .................................................... 3-3
Start of Season ........................................................................................3-3
End of Season..........................................................................................3-3

P/N 1604010 Rev D (ECN 35207) Multi-Control Operation Manual
Table of Contents

P/N 1604010 Rev D (ECN 35207) 1-1 Multi-Control Operation Manual
Section 1- Specications and Compliance
Section 1- Specications and Compliance
Requirements for Electrical Service
All electrical equipment shall be installed by a qualied electrician. As a result, a correct installation will allow the
irrigation system to protect itself from overloads and ground faults with minimal downtime, or possible damage and
hazards.
Refer to ANSI, ASAE Standard S397.2 (latest revision) Electrical Service and Equipment for Irrigation for exact
requirements.
Compliance Standards
Federal Communications Commission (FCC) Statement
NOTE: This equipment has been tested and found to comply within the limits for a Class B digital device pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interfer-
ence when the equipment is operated in a commercial environment. This equipment generates, uses and radiates
radio frequency energy and, if not used in accordance with the manufacturer’s instruction manual, may cause
harmful interference with radio communications.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
These limits are designed to provide reasonable protection against harmful interference. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interfer-
ence with radio or television reception, which can be determined by turning the equipment on and off, try to cor-
rect the interference by one or more of the following measures:
• Reorient or relocate the antenna of the radio/television receiver.
• Increase the separation between this equipment and the radio/television receiver.
• Plug the equipment into a different outlet so that the equipment and the radio/television receiver are on different
power main branch circuits.
• Consult a representative of Lindsay Corporation for additional suggestions.
Industry Canada Compliance Statement
This Class B digital apparatus meets the requirements of the Canadian Interference-Causing Equipment Regula-
tions.
Cet appareil numerique de la Classe B respecte toutes les exigences du Relement sur le Materiel Brouilleur du
Canada.
WEEE Statement
Lindsay Manufacturing, LLC products: D012-007-20 MC Panel; D012-007-11 MC Panel, 2.4 GHz; D012-007-14
MC Expansion Panel; D012-007-22 WS Panel and D012-007-13 WS Panel, 2.4 GHz are sold and distributed in
the European Union only by:
Lindsay Europe SAS
L’Epinglerie
72 300 La Chapelle d’Aligne
France
Phone: 33 (0)2 43480205

P/N 1604010 Rev D (ECN 35207) 1-2 Multi-Control Operation Manual
Section 1- Specications and Compliance
The WEEE directive places an obligation on all EU-based manufacturers and importers to take back electronic
products at the end of the useful life. Lindsay accepts its responsibility to nance the cost of treatment and recov-
ery of redundant WEEE in accordance with the specic WEEE recycling requirements.
The “Do not use regular disposal containers” symbol (shown below) is placed on MC Panels, MC Expansion
Panels and WS Panels indicating this product must not be disposed of with other waste. Instead, it is the user’s re-
sponsibility to dispose of their waste electrical and electronic equipment by handing it over to an approved re-pro-
cessor, or by returning it to Lindsay for reprocessing. More information about waste equipment recycling locations
is available at local City Government Ofces or by contacting Lindsay Europe SAS.
Contact Lindsay Europe SAS with any questions or assistance with returning MC Panels, MC Expansion Panels
or WS Panels.
Product Specications
Regulatory Compliance Standards
United States & Canada
UL 61010-1
FCC Part 15
2014/35/EU-LVD
• IEC/EN 61010-1
• IEC/EN 60529: 1992+A2:2013
2014/30/EU-EMCD
• EN 61326-1
• CISPR 22 Class A
2014/53/EU-RED
• ETSI EN 301 489-1 V1.9.2
• ETSI EN 301 489-17 V1.3.2
2012/19/EU-WEEE
RCM
• AS/NZS 3820:2009
Multi-Control (MC) Panel Ratings:
2000 Meters Altitude
120/230 ~ 60/50-60 Hz 1.5/0.75 Amps
Class III Control (IEC 60730-1)
IP44
Operating Temperature (C): 0T 40
Storage Temperature (C): -40T 75
Pollutions Degree 1
FCCID: (900MHz) MCQ-XB900HP, (2.4 GHz) OUR-XBEEPRO
IC: (900MHz) 1846A-XB900HP, (2.4 GHz) 4214A-XBEEPRO
Protocol: Proprietary
Operating Frequency (MHz): 900 MHz/2.4 GHz
Inputs:
I/O Buss: 8 Pin Molex mini-t, 1000 ft/304.8 m
USB: USB Host Port: Type A/Female
Non-Latching Valve Controls Outputs 1-10 (J1-J5): 24~/0.5A 50/60 Hz or a total sum output load of 60VA between
all outputs.

P/N 1604010 Rev D (ECN 35207) 1-3 Multi-Control Operation Manual
Section 1- Specications and Compliance
Analog Inputs (J6-J8): 0-6
Digital Inputs (J9-J10): Dry Contact Closure (Open circuit voltage is 5 )
Insulation: All input and output devices shall have a minimum basic insulation.
Antenna Connector: N-Type Female; 50 Ohms Impedance; Nickle Plated Brass Material.
Expansion Panel Ratings:
2000 Meters Altitude
120/230 ~ 60/50-60 Hz 1.5/0.75 Amps
IP44
Operating Temperature (C): 0T 40
Storage Temperature (C): -40T 75
Pollutions Degree 1
Inputs:
Buss: 6 Pin Molex mini-t, 1000 ft/304.8 m
USB: USB Host Port: Type A/Female
Non-Latching Valve Controls Outputs 1-10 (J1-J5): 24~/0.5A 50/60 Hz or a total sum output load of 60VA between
all outputs.
Analog Inputs (J6-J8): 0-6V
Digital Inputs (J9-J10): Dry Contact Closure (Open circuit voltage is 5V)
Insulation: All input and output devices shall have a minimum basic insulation.
Wireless Switch (WS) Panel Ratings:
2000 Meters Altitude
3.3 1 Amps
Lithium Iron Phosphate (LiFePPO4), 3.2V, 10.2 Watt Hours
IP44
Operating Temperature (C): 0T 40
Storage Temperature (C): -40T 75
Pollutions Degree 1
FCCID: (900MHz) MCQ-XB900HP, (2.4 GHz) OUR-XBEEPRO
IC: (900MHz) 1846A-XB900HP, (2.4 GHz) 4214A-XBEEPRO
Protocol: Proprietary
Operating Frequency (MHz): 900 MHz/2.4 GHz
Inputs:
Latching Valve Controls Outputs 1-4: Polarized Momentary (Minimum valve resistance of 4Ω); Maximum voltage
of 15 ; Maximum current of 3.75 Amps.
Insulation: All output devices shall have a minimum basic insulation.
Antenna Connector: N-Type Female; 50 Ohms Impedance; Nickle Plated Brass Material.
Dimensional Data and Weight
Multi-Control Panel
Height x Weight x Depth:
16” x 14” x 8” (41 x 35.5 x 20.5 cm)
Weight: 22 lbs (10 kg)
Expansion Panel
Height x Weight x Depth:
16” x 14” x 8” (41 x 35.5 x 20.5 cm)
Weight: 22 lbs (10 kg)
Wireless Switch
Height x Weight x Depth:
10” x 8” x 5” (25.4 x 20.3 x 10.2 cm)
Weight: 5.1 lbs (2.3 kg)

P/N 1604010 Rev D (ECN 35207) 1-4 Multi-Control Operation Manual
Section 1- Specications and Compliance
Service
For locations of the nearest Lindsay Dealer, visit www.zimmatic.com or write:
Service Department
Lindsay Manufacturing, LLC
214 East Second Street
Lindsay, NE, USA 68644
Zimmatic Customer Service call:
(800) 829-5300 (LAN lines require a local country code)
FieldNET Customer Service:
866-MYFIELD (866-693-4353) (local country codes may apply)
or email eldnet@lindsay.com

P/N 1604010 Rev D (ECN 35207) 1-5 Multi-Control Operation Manual
Section 1- Specications and Compliance
Panels & Panel ID Locations
Micro-Controller Panel

P/N 1604010 Rev D (ECN 35207) 1-6 Multi-Control Operation Manual
Section 1- Specications and Compliance
Expansion Panel

P/N 1604010 Rev D (ECN 35207) 1-7 Multi-Control Operation Manual
Section 1- Specications and Compliance
Wireless Switch

P/N 1604010 Rev D (ECN 35207) 1-8 Multi-Control Operation Manual
Section 1- Specications and Compliance

P/N 1604010 Rev D (ECN 35207) 2-1 Multi-Control Operation Manual
Section 2 - Operation
Section 2 - Operation
Introduction to Multi-Control (MC)
The microprocessor based GrowSmart Multi-Control provides the latest technologies in combining distribution
network management with control of major components used throughout a micro-irrigation application.
Using both wired and wireless networking, the controller communicates output controls and zone irrigation sched-
uling. Integrating these components provides the benets of efcient water and chemical delivery, sensor monitor-
ing, temperature protection, and system awareness.
The Micro-Control allows for establishing multiple irrigation plans and remote control through FieldNET (Lindsay’s
integrated irrigation management platform, available on the web or on Apple iOS and Google Andriod mobile
devices).
A typical Micro-Irrigation System is made up of the following components. The GrowSmart Micro-Control is ca-
pable of monitoring all of these system functions.
Typical System layout
• Head System
• Multi-Control
• Water Supply
• System Flow Meter
• System Pressure Sensor
• Chemical Injection System
• Injector Flow Meter
• Filtration System
• Post-Filter Pressure Sensor
• Distribution Network
• Pipes
• Pipe Fittings
• Sprinklers and Valves

P/N 1604010 Rev D (ECN 35207) 2-2 Multi-Control Operation Manual
Section 2 - Operation
Panel Controls
Upon opening the outer door to the Micro-Control panel, the following operator panel is available. Pressing the
Operation Mode button will toggle the control in a loop between Auto (Run), Stop, Service, Stop and back to Auto
again. Indicator lights in the “Mode” quadrant of the status center will illuminate with the proper status color when
the mode button is pressed (see the status center diagram shown later in this section).
The following diagram shows the sequence for stepping though the operation modes. One press of the mode but-
ton will advance through one step of the cycle.
Changing the mode will take effect after three seconds from the last button press. The mode can also be changed
remotely through the FieldNET interface.
Upon any reboot, the controller defaults to the Stop mode.
Status Center
Mode Button
QR Codes for installing the
FieldNET Mobile App
Table of contents
Other Lindsay Irrigation System manuals
Popular Irrigation System manuals by other brands

Autopot
Autopot 48Pot System Set-up guidelines

Victaulic
Victaulic VicFlex Style AB6 quick start guide

Reliable
Reliable DDX Type D Instructions for installation, operation care and maintenance

Viking
Viking 14073AC Technical data

Tyco
Tyco TFP PH2 quick start guide

Tyco Fire Product
Tyco Fire Product Gem A instruction manual