Tyco TY-B Series User manual

Series TY-B – 5.6 K-factor
Horizontal and Vertical Sidewall Sprinklers
Standard Response, Standard Coverage
Page 1 of 6 NOVEMBER 2014 TFP161
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
plicable approval agencies, the test-
ing is not representative of all possible
corrosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
NOTICE
The Series TY-B Sprinklers described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association,
in addition to the standards of any oth-
er authorities having jurisdiction. Failure
to do so may impair the performance of
these devices.
The owner is responsible for maintaining
their fire protection system and devices
in proper operating condition. Contact
the installing contractor or product man-
ufacturer with any questions.
Sprinkler
Identification
Numbers
TY3351 – Horizontal Sidewall
TY3451 – Vertical Sidewall
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
LPCB Approved
VdS Approved
NYC Approved
(Refer to Table A for complete approval
information, including corrosion-resis-
tant status.)
Maximum Working Pressure
Refer to Table B.
Discharge Coefficient
K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Ratings
Refer to Table A.
Finishes
Sprinkler: Refer to Table C.
Recessed Escutcheon: Signal or Pure
White, Jet Black, Chrome Plated, or
Natural Brass
Physical Characteristics
Frame ................... Bronze
Button..............Brass/Copper
Sealing Assembly...Beryllium Nickel
w/TEFLON
Bulb ......................Glass
Compression Screw. . . . . . . . Bronze
HSW Deector . . . . . . . . . . . . Bronze
VSW Deector . . . . . . . . . . . . Copper
General
Description
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprin-
klers described in this technical data
sheet are standard response, standard
coverage decorative 5 mm glass bulb
type spray sprinklers designed for use
in light and ordinary hazard, commercial
occupancies such as banks, hotels, and
shopping malls.
They are designed for installation along
a wall or the side of a beam and just
beneath a smooth ceiling. Sidewall
sprinklers are commonly used instead
of pendent or upright sprinklers due to
aesthetics or building construction con-
siderations, where piping across the
ceiling is not desirable.
The recessed version of the Series TY-B
Horizontal Sidewall Sprinkler is intend-
ed for use in areas with a nished wall.
It uses a two-piece Style 10 Recessed
Escutcheon. The Recessed Escutcheon
provides 1/2 inch (12,7 mm) of recessed
adjustment or up to 3/4 inch (19,1 mm)
of total adjustment from the ush side-
wall position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the xed pipe
nipples to the sprinklers must be cut.
Corrosion-resistant coatings, where
applicable, are utilized to extend
the life of copper alloy sprinklers
beyond that which would otherwise be
obtained when exposed to corrosive
atmospheres. Although corrosion re-
sistant coated sprinklers have passed
the standard corrosion tests of the ap-

TFP161
Page 2 of 6
Operation
The glass bulb contains a uid which
expands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter the
glass bulb, allowing the sprinkler to ac-
tivate and water to ow.
Design
Criteria
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprin-
klers are intended for re protection
systems designed in accordance with
the standard installation rules recog-
nized by the applicable Listing or Ap-
proval agency (for example, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of the FM Loss Preven-
tion Data Sheets). Only the Style 10
Recessed Escutcheon, as applicable,
is to be used for recessed horizontal
installations.
Installation
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprin-
klers must be installed in accordance
with this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) to 3/32
inch (2,4 mm) for the 360°F (182°C) tem-
perature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insuf-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler tting to suit.
Vertical Sidewall Sprinklers
The Series TY-B Horizontal and Ver-
tical Sidewall Sprinklers must be in-
stalled in accordance with the following
instructions.
Step 1. Horizontal sidewall sprinklers in-
stall in the horizontal position with their
centerline of waterway perpendicular to
the back wall and parallel to the ceiling.
The word “TOP” on the Deector is to
face towards the ceiling.
Vertical sidewall sprinklers install in the
pendent or upright position with the ar-
row on the Deector pointing away from
the wall.
Step 2. With pipe thread sealant applied
to the pipe threads, hand-tighten the
sprinkler into the sprinkler tting.
Step 3. Tighten the sprinkler into the
sprinkler tting using only the W-Type
6 Sprinkler Wrench (Figure 4). For wax-
coated sprinklers, use an 8 or 10 inch
adjustable Crescent wrench. With refer-
ence to Figure 1 or 2, apply the W-Type
6 Sprinkler Wrench or the Crescent
wrench, as applicable, to the wrench
ats.
When installing wax-coated sprinklers
with the adjustable Crescent wrench,
exercise care to prevent damage to the
wax coating on the sprinkler wrench
ats or frame arms and, consequent-
ly, exposure of bare metal to the cor-
rosive environment. Open the jaws of
the wrench sufciently wide to pass
over the wrench ats without damaging
the wax coating. Before wrench-tight-
**
*
*
**
*
ESCUTCHEON
PLATE SEATING
SURFACE
1-13/16"
(46,0 mm)
CENTERLINE
OF SPRINKLER
WATERWAY
2-7/8" DIA.
(73,0 mm)
STYLE 10
RECESSED
ESCUTCHEON
2-3/16"
(55,6 mm)
1-1/2"
(38,1 mm)
DEFLECTOR
HAT
9/16"
(14,3 mm)
6
WRENCH
FLATS
4
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2
5
3
1/2"
NPT
1
Pipe thread
connections per
ISO 7-1 can be
provided on
special request.
Temperature rating
is indicated on
Deector.
1
2
Sealing
Assembly
Button
Frame
-
-
Bulb
3-
4-
6-Deector
Compression
Screw
5-
FIGURE 1
SERIES TY-B HORIZONTAL SIDEWALL (TY3351) SPRINKLER
5.6 K-FACTOR STANDARD RESPONSE

TFP161
Page 3 of 6
ening the sprinkler, adjust the jaws of
the wrench to contact only the sprinkler
wrench ats. After wrench tightening the
sprinkler, loosen the wrench jaws before
removing the wrench.
After installation, inspect the sprinkler
wrench ats and frame arms and re-
touch (repair) the wax coating when-
ever the coating has been damaged
and bare metal is exposed. Retouch
the wax coating on the wrench ats by
gently applying a heated 1/8 inch diam-
eter steel rod to the damaged areas of
wax to smooth it back over areas where
bare metal is exposed.
NOTICE
Only retouching of the wax coating ap-
plied to the wrench flats and frame arms
is permitted, and the retouching is to be
performed only at the time of the initial
sprinkler installation.
The steel rod should be heated only to
the point at which it can begin to melt
the wax, and appropriate precautions
need to be taken when handling the
heated rod in order to prevent the in-
staller from being burned.
**
* **
*
*
PENDENT UPRIGHT SECTION
CROSSSHOWN SHOWN
1-1/2"
(38,1 mm)
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16"
(55,6 mm)
WRENCH
FLATS
1/2"
NPT
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
ARROW MUST
POINT AWAY
FROM AND BE
PERPENDICULAR
TO THE BACK
WALL SURFACE
7
2-3/16"
(55,6 mm)
3
1
6
5
2
4
Pipe thread
connections
per ISO 7-1 can
be provided on
special request.
Temperature
rating is
indicated on
Deector.
1
2
Sealing
Assembly
Button
Frame
-
-Bulb
3-
4-
6-Deector
Compression
Screw
5-
FLOW
Ejection
Spring
7-
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
2-7/8" DIA.
(73,0 mm)
MOUNTING
SURFACE
CLOSURE
1-1/4" (31,8 mm)
3/4" (19,1 mm)
SERIES
TY-B
MOUNTING
PLATE
3/4" (19,1 mm)
1/8"
(3,2 mm)
1/4" (6,4 mm)
FACE OF
SPRINKLER
FITTING
5/8±1/4"
(15,9±6,4 mm)
2-1/4" DIA.
(57,2 mm)
FIGURE 2
SERIES TY-B VERTICAL SIDEWALL (TY3451) SPRINKLER
5.6 K-FACTOR, STANDARD RESPONSE
FIGURE 4
W-TYPE 6
SPRINKLER WRENCH
FIGURE 5
W-TYPE 7 RECESSED
SPRINKLER WRENCH
FIGURE 3
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON, 5.6 K-FACTOR, 1/2 INCH NPT

TFP161
Page 4 of 6
Horizontal Sidewall Sprinklers
The TYCO Series TY-B Recessed Hori-
zontal Sidewall Sprinklers must be in-
stalled in accordance with the following
instructions.
Step A. Install recessed horizontal side-
wall sprinklers in the horizontal position
with their centerline of waterway per-
pendicular to the back wall and parallel
to the ceiling. The word “TOP” on the
Deector is to face towards the ceiling.
Step B. After installing the Style 10
Mounting Plate over the sprinkler
threads, hand-tighten the sprinkler into
the sprinkler tting.
Step C. Tighten the sprinkler into the
sprinkler tting using only the W-Type 7
Recessed Sprinkler Wrench (Ref. Figure
5). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench ats.
Step D. After the ceiling is installed or
the nish coat is applied, slide on the
Style 10 Closure over the Series TY-B
Sprinkler and push the Closure over the
Mounting Plate until its ange comes in
contact with the ceiling.
KSPRINKLER
TYPE TEMPERATURE
RATING
BULB
LIQUID
COLOR
SPRINKLER FINISH (10)
NATURAL
BRASS CHROME
PLATED POLYESTER*** LEAD
COATED WAX
COATED WAX-OVER-LEAD
COATED
5.6
1/2˝
NPT
HORIZONTAL
SIDEWALL
(TY3351)
Figure 1
135°F (57°C) Orange
1, 2, 3, 4, 9 1, 2, 3, 9 1, 2, 3, 9
1, 2, 3, 9
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue 1**, 2**, 3**, 9**
360°F (182°C) Mauve 1, 2, 4, 9 1, 2, 9 N/A
RECESSED
HORIZONTAL
SIDEWALL
(TY3351)*
Figure 3
135°F (57°C) Orange
1, 2, 3, 9 N/A
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
5.6
1/2˝
NPT
VERTICAL
SIDEWALL
(TY3451)
PENDENT
or
UPRIGHT
Figure 2
135°F (57°C) Orange
4, 5, 6, 7, 8, 9 5, 6, 7, 9
5, 6, 7, 9
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue 5**, 6**, 7**, 9**
360°F (182°C) Mauve 4, 5, 6, 8, 9 N/A
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deector-to-ceiling distance
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deector-to-ceiling
distance
3. Approved by FM Global (FM Approvals) for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deector-to-ceiling distance
4. Approved by the Loss Prevention Certication Board (LPCB Ref. No. 094a/05 & 007k/03) at a 4 to 6 inch (100 to 150 mm) deector-to-ceiling distance
5. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies
6. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) for use in Light and Ordinary Hazard Occupancies
7. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies
8. Approved by the Loss Prevention Certication Board (LPCB Ref. No. 094a/05 & 007k/03)
9. Approved by the City of New York under MEA 354-01-E
10. Where Polyester Coated, Lead Coated, Wax Coated, and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corro-
sion-resistant sprinklers. Where Lead Coated, Wax Coated, and Wax-over-Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as corrosion-
resistant sprinklers.
* Installed with Style 10 (1/2˝ NPT) or Style 40 (3/4˝ NPT) 3/4˝ Total Adjustment Recessed Escutcheon, as applicable
** 150°F (66°C) maximum ceiling temperature
*** Frame and deector only
N/A – Not Applicable
TABLE A
SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS
LABORATORY LISTINGS AND APPROVALS

TFP161
Page 5 of 6
Care and
Maintenance
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprin-
klers must be maintained and serviced
in accordance with this section.
Before closing a re protection sys-
tem main control valve for maintenance
work on the re protection system that
it controls, obtain permission to shut
down the affected re protection sys-
tem from the proper authorities and no-
tify all personnel who may be affected
by this action.
The owner must assure that the sprin-
klers are not used for hanging any ob-
jects and that the sprinklers are only
cleaned by means of gently dusting with
a feather duster; otherwise, non-opera-
tion in the event of a re or inadvertent
operation may result.
Absence of an escutcheon, which is
used to cover a clearance, may delay
the time to sprinkler operation in a re
situation.
Sprinklers which are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
ed sprinklers must be replaced. Sprin-
klers that have been exposed to corro-
sive products of combustion, but have
not operated, should be replaced if they
cannot be completely cleaned by wiping
the sprinkler with a cloth or by brushing
it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb. (Refer to Installation Section.)
The owner is responsible for the inspec-
tion, testing, and maintenance of their
re protection system and devices in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association
(e.g., NFPA 25), in addition to the stan-
dards of any other authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinklers are recommended
to be inspected, tested, and maintained
by a qualied Inspection Service in ac-
cordance with local requirements and/
or national codes.
KSPRINKLER
TYPE
SPRINKLER FINISH
NATURAL
BRASS CHROME
PLATED POLYESTER* LEAD
COATED WAX
COATED WAX-OVER-LEAD
COATED
5.6
1/2˝
NPT
HORIZONTAL SIDEWALL
(TY3351) 250 psi (17,2 bar) (a)
OR
175 psi (12,1 bar)
RECESSED
HORIZONTAL SIDEWALL
(TY3351)
VERTICAL SIDEWALL
(TY3451) 175 psi (12,1 bar)
Note:
a. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL), the Listing by Underwriters
Laboratories, Inc. for use in Canada (C-UL), and the Approval by the City of New York.
* Frame and deector only
TABLE B
SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS
MAXIMUM WORKING PRESSURE

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP161
Page 6 of 6
Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of the DuPont Corporation.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series TY-B (specify SIN),
(specify K-factor), (specify Horizontal or
Vertical Sidewall) Sprinklers with (spec-
ify) temperature rating, (specify) nish or
coating, P/N (Refer to Table C)
Recessed Escutcheon
Specify: Style 10 Recessed Escutcheon
with (specify) nish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Wax Sticks
(for retouching wrench-damaged
wax coating)
Specify: (specify color, below) Colored
Coded Wax Stick for retouching (specify
temperature rating) temperature-rated
Series TY-B Sprinklers, P/N (specify)
Black for 135°F (57°C) ...... P/N 56-065-1-135
Red for 155°F (68°C)........ P/N 56-065-1-155
Yellow for 175°F (79°C) ..... P/N 56-065-1-175
Blue for 200°F (93°C) and
286°F (141°C) ............ P/N 56-065-1-286
Note: Each wax stick is suitable for
retouching up to 25 sprinklers.
Note: The wax used for 286°F (141°C)
sprinklers is the same as for 200°F (93°C)
sprinklers,and,therefore, the 286°F(141°C)
sprinkler is limited to the same maximum
ceiling temperature as the 200°F (93°C)
sprinkler (i.e., 150°F [66°C]).
Notes:
* Eastern Hemisphere sales only
** Available only for 155°F (68°C) or 200°F (93°C) tem-
perature rated sprinklers
*** Available only for horizontal sidewall
TY3351 for use in Deluge Systems (“OPEN”
indicates sprinkler assembly without glass bulb,
button, and sealing assembly)
P/N 57 – XXX – X – XXX
SIN
578 HORIZONTAL SIDEWALL TY3351
575 VERTICAL SIDEWALL TY3451
TEMPERATURE
RATING
135 135°F (57°C)
155 155°F (68°C)
175 175°F (79°C)
200 200°F (93°C)
286 286°F (141°C)
360 360°F (182°C)
000 OPEN***
SPRINKLER
FINISH
1NATURAL BRASS
3PURE WHITE (RAL9010)*
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
5JET BLACK (RAL9005)**
POLYESTER
6WA X COATED
286°F (141°C) MAX
7LEAD COATED
8WAX-OVER-LEAD
286°F (141°C) MAX
9CHROME PLATED
TABLE C
SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
PART NUMBER SELECTION
Other manuals for TY-B Series
22
This manual suits for next models
2
Table of contents
Other Tyco Irrigation System manuals

Tyco
Tyco ESFR-22 User manual

Tyco
Tyco DS-8 Series User manual

Tyco
Tyco ESFR-25 Operating and maintenance instructions

Tyco
Tyco TY-QRF User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco DS-1 Series User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco ILLUSION User manual

Tyco
Tyco DSB-1 User manual

Tyco
Tyco ELOC User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco TY-FRB Series User manual

Tyco
Tyco Ultra K17 K-factor User manual

Tyco
Tyco LFII Series User manual

Tyco
Tyco EC-25 User manual

Tyco
Tyco TY-FRL Series User manual

Tyco
Tyco RFII Series User manual