Lock Control ST-980 Series Specification sheet

#*
VER 13.11.21
ST-980 Series
NETWORK PROXIMITY ACCESS CONTROL OPERATION
AND INSTALLATION MANUAL
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be
Lock Control - Zwaluwstraat 132 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

(01)
(02)
(04)
(05)
(08)
(10)
(18)
(21)
(22)
(82) Card Number Door Open Mode
(00)
7.Installation instructions
(1) Reader connector
(2)
(3)
(4)
(5)
(6)
(7)
ATTENTIONS
1.Features
3.Front panel and types of cards
6.Setting modes & functions
Add New Card
Door detection wiring
wiring
Door open point with external
8.Precautions
9.Troubleshooting
10.Installation of the unit
Hollow Door
Solid Door
2.Installation Procedures
4.Operation instructions
Turn on the unit
Proximity
Proximity and Password Door Opening
Anti-duress
Setup Mode
5.Quick setting
Delete Card
Shunt Time
Door Open Mode
Change System Password
Reader ID Number
Main Reader Location
Anti-duress AlarmMode
Door Sensing Mode
Instant Door Open
Wiring of electric lock
Anti-duress alarm
Alarm
RELAY
Wiring connection for linking with computer
2
3
6
9
8
1
4
5
5
5
5
5
5
5
6
6
7
7
8
9
10
10
11
12
12
13
14
14
16
14
17
15
17
15
16
19
CONTENTS
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

ATTENTIONS
1234567890
1234567890 18838:00722
Card number in the back of the card
Example of the card
The last 8-digit number of 1234567890 is 34567890.
125KHz(EM)
Card number
1.Power Supply requirement: DC 12V 500mA and above.
2.Door opening or alarm connector output: Maximum load of 1A@30VDC or
3A@24VDC.(Page )
Connect with external RELAY to control higher voltage or current .
3.Electric Lock: Fail-safe or fail-secure type (Refer to p ).
Please note: In order to protect the proximity unit, please connect one Diode
between two power supply connectors of electric lock to absorb surge.
4.Avoid installing the unit at the following environment: A. Machines with the same
frequency as the proximity unit around the neighborhood. B. In the area of a base
station with radio or wireless transmission. C. On metal wall (proximity distance will
be shorten).
5.It is suggested to separate the power supply of electric lock and proximity unit in order
to stabalize the power supply.
6.It is IP65 waterproof and its surface is completely waterproof. Please apply waterproof
silicone on its base if it is mounted on rough surface to make sure its base is waterproof.
15
13
Chip serial number
(non-serial) Card number
(serial)
+
Electric lock
Diode
Electric Locks
13.56MHz(MIFARE)
24AWG
Wires
#*
#*
#*
Wall
Too close
Too close Sharing the same
power supply
Proximity distance
becomes short
Metal
XXX
DC 12V
XX
~
~AC
Communication wire
500mA
Power supply
DC 12V
1
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

1.Features
Water proof design (except Relay panel) It is suitable for both indoor or outdoor use.
Polycarbonate fireproof material for casing (white or dark-gray) , durable buttons.
LED indicator. It shows reader's status( Open door, error, setting modes, and etc.)
Frequency:125KHz .
Proximity range: 3~7cm according to the types of card and frequency use.
Dimensions: 135L 43W 25H(mm)
Power supply : DC12V, Power consumption: 140mA (standby); 180mA (operation).
0~70, 85%Rh Max.
When connecting with computer , it can be used for data inquiry and function setting
simultaneously . (Door open/close, activate alarm system, etc). It can also operate
solely to manage access control.
Function setting can be done by computer or reader itself. (Single registration or
deletion, door open time, etc).
The capacity data input/output can reach up to 4,500 by single reader operation . When
linking with computer , its data input/output capacity is unlimited.
Main reader has 2,000 card registrations capability. Each card is able to do self-setting
for personal password and effective in/out time.
Main reader has 48 units of time zone. Each time zone unit also has 5 time ranges for
user to set.
Example: It can be set from"G" hour "H" minute to "I" hour "J" minute on Mondays,
Wednesdays, Saturdays in periodical of "A" year "B" month "C" day to
"D" year "E" month "F" day as effective in/out time range.
Equipped with hardware self-testing function
Internal batteries will provide power supply when power cut occurred to prevent any
data from being erased and system time can operate as normal. (Valid power of the
internal batteries is approximately 3 months according to the length of time of power cut.)
Main reader access control's range:
Card number - It must be registered before use.
Password - Personal password has to key in to open the door.
Time zone - Setting the effective year, month, day, time range, Monday-Sunday.
Special holidays- User could set any holidays as to prevent any unauthorized access.
Error control - Alarm will activate when"N" times of consecutive error password
entering occurred.
Main reader's sensing range:
Anti-tamper - When the reader is tampered , alarm will be activated.
Anti-duress - It will operate when password and duress code are entered to send help
signal to the nearest police station. It must be done manually to disable anti-duress
function.
Door open button sensing - Door will open immediately when the button is pushed.
Anti-theft - Alarm will be activated when sensing any abnormal operations.
Exceed door shut time - Alarm will be activated, when door is not closed exceeding
initial time setting control.
Operation temperature : Humidity:
2
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

3
2.Installation Procedures
Mount the unit(Page 17)
Wiring(Page 12~15)
Power supply to the reader
Enter setting mode
Adding new cards(standalone)(Page 6)
If not, disconnect the
power supply immediately.
Ensure the adapter's voltage
and polarity are correct.
Enter system password ( 5678 ),then a beep sound
and yellow indicator light flashes to enter into setting mode.
If there isn't any action, this system will automatically escape
from the setting mode.
Default reader number is 001. Enter 10 and then 3-digit
reader number to change reader number(each reader
has its own reader number for software to recognise).
Operation with
computer online
Standalone
mode
Deleting Cards
(standalone)
(Page 6)
Enter 01 and proximity card or enter
card number.One beep sound to
complete registration.
Press button to escape.
Enter 02 and proximity card or enter card number.
One beep sound to complete deletion.
Press button to escape.
Completion of setting
NO
NO
YES
YES
Check if power
(RED)indicator is on.
Completion
of setting
Press button to exit setting mode
Activate the software
(default account:USER,password:0000)
Add new user and reader
Send all settings to the reader
Send all data to the reader when all settings are
completed in order to operate.
Data which need to be sent are:1.Time 2.User's data
3.Time Zone 4.Parameter
Please refer to the software manual for detailed operation.
1.Default reader number is 1 and communication interface is
Com.1 when entering into the software.
2.Reader number 1 will respond when both interface and time
are correct. Please check the wiring and its interface and
reader number when there is no response from the reader.
3.Click Basic Information Setting ->User->Add New User
Information / Data.
4.Click Basic Information Setting ->Reader->Add New Reader.
Reader number or change reader
number(Page 8)
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

12
34
56
78
90
#*
Orange light: Error/ Communicating(Blinking)
Proximity and password door opening mode
(Orange light is on)
3.Front panel and types of cards
Power Indicator Light
Standby (Red)
Beeper
Proximity card correct (Green light is on)
Enter setting mode (Green light flashing)
Clear or escape key(CLR/ESC)
(ENTER)
:Confirmation key
Types of proximity card
Model series
Front panel
ST-980 :125KHz EM-Marin format
ST-980MF:13.56MHz Mifare SOCAformat
ST-980MH:13.56MHz Mifare SOCA V.2 format
ST-980M :13.56MHz Mifare format
SC-30
Key tag, dimensions: 51L X 32W X 7.8H (mm).
Ultrasonic connection, waterproof,
shock- proof. Read range :
EM 125KHz 2~3.5cm
Mifare 13.56MHz:1.5~2.5cm
12345678
SC-20
Thick card, thickness of 1.78 mm, ISO standard
card dimensions. Read range :
EM 125KHz : 5 7cm
12345678
SC-10
Thin card, thickness of 0.8 mm, ISO standard
card dimensions. It can be printed directly
from card printer. Read range :
EM 125KHz 5~ 7cm
Mifare 13.56MHz:3~5cm
SC-50
Key tag, dimensions: 46L X 25W X 7H (mm).
Ultrasonic connection, waterproof,
shock- proof. Read range :
Mifare 13.56MHz:1.5~2.5cm
The above read range stated is for reference and it is varied according to
the different environment it is used. 4
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

4.Operation instructions
5.Quick setting
Turn on the unit : The unit itself does self -testing when the power is on.
Current time is shown on display screen when self-testing is completed.
Proximity : Sense the card near the unit. The following States are shown below.
(A)OK (Green) light is on to indicate registered card to gain access.
(B)DENY (Red) light is on and consecutive beeping sound is on to indicate unregistered card
or use under unauthorized time zone.
(Please refer to Troubleshooting if none of the above occurred)
Proximity and Password Door Opening : Door Open mode is set as 3. Sense the card and
enter 4-digit password and then press # button to open door .
Anti-duress : When under duress, user may press button before keying in password to
activate alarm. (Duress code presetting is , it can be changed by user)
Example : anti-duress code is 1, password is 1 2 3 4, then to activate
anti-duress alarm, the user should key in 1 2 3 4 .
Note : This function is only available for Door Open Mode 3-proximity and password mode.
Setup Mode :
User must get into setting mode first before changing any system functions. User must
enter system password for system function selection. System password is being
set as 5 6 7 8 (default).
(Example: User can get into the set up mode by keying 5 6 7 8 ).
P16
Add new card : enter 0 1 and then enter 0 0 0 0 0 0 0 1 or proximity card .
8-digit card number
Delete card : enter 0 2 and then enter 0 0 0 0 0 0 0 1
8-digit card number
Shunt time : enter 0 4 and then enter the seconds 0 0 3
Seconds
Reader ID number : enter 1 0 and then enter the reader number 0 0 2
Door open mode : enter 0 5 and then enter the mode code 2
Door open mode
User will get into the setup mode as the right diagram shown for any setting to be made.
Reader number
5
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

6
6.Setting modes & functions
FUNCTION (01) Add New Card
Either key in 8-digit card number or use proximity card to register, both can be accepted
but should be registered before use.
Enter 01
Enter 02
Enter 8-digit card number
manually or by proximity
Press # button after entering.
Enter 8-digit card number
manually or by proximity.
Press # button after entering.
Registration completed,
one long beep sound.
Registration completed,
one long beep sound.
Repeated registration,
continuous beep sound.
Error.
Continuous beep sound.
Enter to go
back to system function selection.
Enter to go
back to system function selection.
Enter
# system password #
Enter
# system password #
Function (02) Delete Card
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

Function (04) Shunt Time
Enter shunt time(0~255)
Press # button after entering.
Enter
# system password #
Enter
# system password #
Enter 04
Enter 05
Back to system function selection.
Back to system function selection.
Registration completed,
one long beep sound.
Registration completed,
one long beep sound.
Error.
Continuous beep sound.
Error.
Continuous beep sound.
Function (05) Door Open Mode
Reader has 2 types of identification modes. (Default value as 2 )
Mode (2). Card proximity door open: The door opens, when the card is sensed.
Mode (3). Door open by proximity card and password: The door opens by entering
additional 4-digit password after sensing the registered card.
Enter door open mode
Press # button after entering.
Nothing is entered
Enter
Nothing is entered
Enter
Setting of Relay's ON time in the proximity reader can be set from 0-255 seconds.
Set 000 as toggle function. Door is always open until second proximity to close it.
( default value as 003 )
7
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

8
Function (08) Change System Password
The reader's password is being set as 5678(default).
In order to enter into system setting mode for the first time, user must enter the default
system password 5 6 7 8 . User may change the system password after entering into
system setting mode.(4~6-digit password to set)
Enter 08
Enter
# system password #
Nothing is entered
Enter
Back to system function selection.
Enter new system password (4~6 digits)
Press # button after entering.
Confirm the new password
Registration completed,
one long beep sound.
Error.
Continuous beep sound.
Back to the display screen.
Function (10) Reader ID Number default number is 001, range 1-255.
Nothing is entered
Enter
Enter 1-255
Press # button after entering.
Enter 10
Back to system function selection.
Enter
# system password #
Setting completed, one
long beep sound occurred.
Error.
Continuous beep sound.
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

Function (18) Main Reader Location
Function (21) Anti-duress Alarm Mode
To show the location of the reader: (0) Indoor, (1) Outdoor. (default location is 1 )
Enter main reader location code.
Press # button after entering.
Enter anti-duress mode.
Press # button after entering.
Enter 18
Enter 21
Enter
# system password #
Enter
# system password #
Nothing is entered
Enter
Back to system function selection.
Back to system function selection.
Setting completed, one
long beep sound occurred.
Error.
Continuous beep sound.
(0) shows "ON" ,(1) shows "OFF",(default value is 1 ).
9
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be
Nothing is entered
Enter
Setting completed, one
long beep sound occurred.
Error.
Continuous beep sound.

Function (22) Door Sensing Mode
(0) shows "ON", (1) shows "OFF", (default value is 1 ).
Enter door sensing mode .(0~1)
Press # button after entering.
Enter
Press # button after entering.
Card Number Door Open Mode.
Enter 22
Enter 82
Enter
# system password #
Enter
# system password #
Nothing is entered
Enter
Nothing is entered
Enter
Back to system function selection.
Back to system function selection.
Setting completed, one
long beep sound occurred.
Setting completed, one
long beep sound occurred.
Error.
Continuous beep sound.
Error.
Continuous beep sound.
10
Function (82)
Card Number Door Open Mode: (0)ON, (1)OFF.
(default value as 1 ) Enter registered card's 8-digit card number to
open door when the function is set as ON.
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

Function (00) Instant Door Open
Enter door open input mode.
Press # button after entering.
Instant
Enter 00
Enter
# system password #
Nothing is entered
Enter
Back to
system function selection.
Open door
Setting completed, one
long beep sound occurred.
Error.
Continuous beep sound.
Back to the display screen.
11
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be
Lock Control - Zwaluwstraat 132 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

P.S. Door open and Alarm relay contact 1A/30VDC or 3A/24VDC. Please connect with
a RELAY to control units with higher load in order to prevent internal damages (please
refer to P15 for wiring examples.)
7.Installation instructions
#*
PBRVINGND
NCDOOR
COM
NOP.SNC
COMN0
ALARM
Y
GR
Original wiring connection as 30cm. Extend the wires
when its length is not enough.
User may extend the wires when it is not long enough. It is suggested not to
extend its wires more than 10m which may cause insufficient of the voltage.
Gray
Yellow
Purple
Black
Red
Green
White
Blue
Orange
(1) Reader connector
GND
+12VDC
PBRVINGND
NCDOOR
COM
NOP.SNC
COMN0
ALARM
Y
GR
AP-55
R
Gra
Y
Pu
Bla
W:Anti-duress output terminal
Blu:Signal (data+) transmitter
G:Signal (data-) receiver
O:Door sensing terminal
Door control REALY. Dry contact N.O
Door control REALY. Dry contact COM
Door control REALY. Dry contact N.C
Exit push button
Alarm output RELAY. Dry contact N.O
Alarm output RELAY. Dry contact COM
Alarm output RELAY. Dry contact N.C
12
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be
Lock Control - Zwaluwstraat 132 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

+
+
PB R VIN GND
NC DOOR
COM
NO P.S NC
COM N0
ALARM
Y
GR
AP-10
DC 12V
AP-10
DC 12V
AP-10
DC 12V
AP-10
DC 12V
AP-10
DC 12V
AP-10
DC 12V
+
+
PBRVINGND
NCDOOR
COM
NOP.SNC
COMN0
ALARM
Y
GR
+
+
PBRVINGND
NCDOOR
COM
NOP.SNC
COMN0
ALARM
Y
GR
OR
Br
A. "N.O connector
Suitable for: Fail-secure electric lock or any electric lock that requires N.O Connector.
B. "N.C" Connector
Suitable for: Fail-safe electric lock such as electromagnetic lock.
Example: Microcontroller Fail-safe electric lock (use of N.O point to trigger).
Example: Fail-secure lock (use of N.O point to trigger).
Push Button
Push Button
Push Button
Electric Lock
(2) Wiring of electric lock:
Different wiring for different electric lock. There are two types of wiring as below:
Diode's white terminal
Diode's white terminal
13
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be
Lock Control - Zwaluwstraat 132 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

(4) Anti-duress alarm
White
Red
PBRVINGND
NCDOOR
COM
NOP.SNC
COMN0
ALARM
Y
GR
++
+
+
+
--
-
-
-
Alarm power
NC
NO COM
Eternal Relay
(Optional)
(5) Alarm wiring
(3) Door detection wiring
N.C Reed Switch
Orange
Black
Diode's white terminal
DC12V
#*
#*
14
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

(7) Wiring connection for linking with computer
PBRVINGND
NCDOOR
COM
NOP.SNC
COMN0
ALARM
Y
GR
AP30 CONVERTER
RS-232 to RS-485
RS-232
VCC
GND
DT +
DT +
DT
DT
DC12V
Device 1 Device 2 Device N
POWER TXD RXD
PC
-
+
Load
External power
(Voltage > DC24V or Current > 3A)
CNT+ CNT-
Eternal Relay
(6) Door Open point with external RELAY
RS-232
communication line
RS-485 interface transit connector
Diode's white terminal
Precautions
Maximum load of the door open RELAY as DC 24V / 3A . Please connect an external RELAY for
high voltage or current to prevent any damage to the internal parts(optional of AP-51 is available).
Examples of the wiring in this manual are for reference. Please refer to the electric lock's
manual for the actual wiring.
If the loading of the door open RELAY is not being used by an electric lock but for lift,
automatic door, please make sure its voltage loading range. If user is unable to specify its range,
it is suggested to connect an external RELAY.
Please connect a Diode for the external RELAY to absorb surge (please make sure its direction).
#*
#*
#*
GreenGreen Green
BlueBlue Blue
15
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be
Lock Control - Zwaluwstraat 132 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

9.Troubleshooting
1. Card sensed but the door lock didn't work.
Solution:(1) Please check if the power supply of both proximity reader and electric lock
are connected and turned on.
(2) If (1) is checked, please check if power supply and connecting points of
the electric lock are correct.
(3) Please check the card if it is registered.
(4) Continuous proximity. Please remove the card from the reader and try
again.
(5) Please check if the door opening mode is being set correctly.
2. System password is entered but unable to enter into various functional selection of
the setting mode.
Solution: (1) Incomplete input of system password. Please check if the format has
been entered correctly: #XXXX#(XXXX represents system
password).
(2) Bad wiring affects the system.
Please make sure all power and control wires are arranged in the back of
the display screen(the space for wiring) to avoid the wires pressing on
the PC board which may cause bad connection, short circuit and
interference to the system.
3. How to disable anti-tamper or duress alarm ?
Solution: Enter into the system setting mode or open the door.
8.Precautions
1.Please the make sure voltage and polarity of the power supply before installation to
prevent any wrong connection that causes damages to the reader.
2.Do not share electric current with electric lock and reader to avoid interference.
3.Do not try to fix or modify the reader without authorized electrician.
4.The reader is guaranteed for one year.
16
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be
4.Continuous beep sounds (error) occurred during batch registration.
Additional note:Maximum card capacity is 2,000. Cards will not be registered when
exceeding its maximum card capacity.
For example: The unit will only register the first 1900 cards when 2000 cards area
registered with Batch Registration function and the last 100 cards will
not be registered if the unit has registered 100 cards previously.

17
Hollow Door
Step1 Step2
10.Installation of the unit
Use attached screwdriver
to unscrew the screws
Separate the panel base
from the unit.
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be
Lock Control - Zwaluwstraat 132 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be

Step3
Step5
Step4
Step6
Screw the base panel
tight on the wall.
Place pin wire through the base
panel and connect with the external
RELAY (please refer to the wiring
diagram for wiring). Insert both
RELAY panel and wires into the
door frame.
Screw the unit tight.
Place the unit on the base
panel and push it upward to the
upper slot to complete.
18
Lock Control - Kouterbaan 63 - 1840 Malderen - Belgium - Tel. +32 52 57 43 02 - [email protected] - www.lockcontrol.be