Love Controls C Series User manual

5011643800-DWC0
2006-02-15
C Series Temperature Controller
Instruction Sheet
Thank you very much for purchasing a Love Controls Series C Temperature Controller. Please read this instruction sheet before using
your controller to ensure proper operation and please keep this instruction sheet handy for quick reference.
1 Precaution
DANGER! Caution! Electric Shock!
1. Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure power is disconnected while checking the unit inside.
3. The symbol indicates this Controller is protected throughout by DOUBLE INSULATION or REINFORCED INSULATION
(equivalent to Class II of IEC 536).
WARNING!
Mount the controller in a location that will not be subject to excessive temperature, shock, or vibration. All models are designed for
mounting in an enclosed panel..
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm, hole diameter 3.2mm).
Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). Applicable wire:
Solid/twisted wire of 2 mm2, 12AWG to 24AWG. Please be sure to tighten them properly.
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. Do not connect anything to the “Not used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. Do not install and/or use the controller in places subject to: Dust or corrosive gases and liquid, high humidity and high radiation,
vibration and shock, high voltage and high frequency
7. Power must be off when wiring and changing a temperature sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Please use wires with resistance when extending or connecting a platinum resistance sensor (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance sensor (RTD) to the controller and please route
power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water,
corrosive materials, airborne dust and electric shock or vibration.
12. Please make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise
serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric
shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit
within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install the protection
close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse
17. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent protection
device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A
suitable disconnecting device should be provided near the controller in the end-use installation.
2 Display, LED, and Pushbuttons
Bulletin E-90-C
PV displays process value
SV displays setpoint value.
INDEX: advances the display to the next menu item.
UP ARROW: Increments a value or changes a menu item.
DOWN ARROW: Increments a value or changes a menu item.
ENTER: stores the value or item change.

3 Temperature Sensor Type and Temperature Range
Input Temperature Sensor Type Register Value LED Display Temperature Range
Platinum resistance (Pt100) type3 15 0.0 to 100.0 oC
Platinum resistance (Pt100) type2 14 -20.0 to 500.0 oC
Platinum resistance (Pt100) type1 13 -200 to 600 oC
Platinum resistance (JPt100) type2 12 0.0 to 100.0 oC
Platinum resistance (JPt100) type1 11 -20.0 to 400.0 oC
Thermocouple (TC) B type 10 100 to 1800 oC
Thermocouple (TC) S type 9 0 to 1700 oC
Thermocouple (TC) R type 8 0 to 1700 oC
Thermocouple (TC) N type 7 -200 to 1300 oC
Thermocouple (TC) E type 6 0 to 600 oC
Thermocouple (TC) T type2 5 -20.0 to 400.0 oC
Thermocouple (TC) T type1 4 -200 to 400 oC
Thermocouple (TC) J type2 3 -20.0 to 400.0 oC
Thermocouple (TC) J type1 2 -100 to 850 oC
Thermocouple (TC) K type2 1 -20.0 to 500.0 oC
Thermocouple (TC) K type1 0 -200 to 1300 oC
Thermocouple (TC) L type 16 -200 to 850 oC
Thermocouple (TC) U type 17 -200 to 500 oC
Thermocouple (TC) Txk type 18 -200 to 800 oC
4 Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, the controller will default to the
operation mode. Press the key to switch to regulation mode. If the key is pressed for more than 3 seconds, the controller will
switch to the initial setting mode. Pressing the key while in the regulation mode or initial setting mode, forces the controller to return
to the operation mode. PV/SV : Sets the temperature set point and displays the temperature process value. Use the and keys to
set the temperature set point.
Setting method: While in any function mode, press the key to select the desired function and use the and keys to change
settings. Press key to save the changes. Menu items are listed below.
Regulation Mode
Operation Mode
Initial Setting Mode
Set input type
Use key to
set temperature set point
Auto-tuning
(Set in PID control and RUN mode)
Press
Press
Press
Set proportional band (Kp)
(in PID control)
Press
Set temperature unit
do not display when analog input
Press
Control setting RUN or STOP
Press
Set integral time (Ki)
(in PID control)
Press
Set upper-limit of
temperature range
Upper-limit alarm 1
(This parameter is available only when
ALA1 function enables)
Press
Press
Set derivative time (Kt)
(in PID control)
Press
Set lower-limit of
temperature range
Lower-limit alarm 1
(This parameter is available only when
ALA1 function enables)
Press
Press
or P/PD control offset (when
PID control is ON and Ki=0 set the value of
PdoF. If Ki≠0, AT (auto-tuning, will
automatically set the value of ioF.
Press
Upper-limit alarm 2
(This parameter is available only when
ALA2 function enables)
Press
Sets Control Method: on/off, PID, or
manual.
or Heating/Cooling hysteresis.
(in ON/OFF control)
Press
Lower-limit alarm 2
(This parameter is available only when
ALA2 function enables)
Press
Select heating or cooling control.
Press

or Heating/Cooling
control cycle setting
(Set in PID control mode)
Press
Setting lock mode
Press
Alarm 1 mode setting
Press
Press
Regulate temperature
deviation value
Display and adjust output value.
Press
Press
Alarm 2 mode setting
(The setting display when analog output)
Regulate upper-limit of analog
output value
Communication write function
enable/disable
Press
Press
Press
Regulate lower-limit of analog
output value
(The setting display when analog output)
to return to auto-tuning mode
Communication address
setting
Press
Communication baud
rate setting
Press
Data length setting
Press
Parity bit setting
Press
Stop bit setting
Press to return input type setting
Parameters List
1. Operation Mode: The default mode after start-up
LED Ex
p
lanation Default
RUN/STOP: Control setting. Run ( ) or Stop ( ) mode on the SV display. RUN
ALARM 1 HIGH: Upper limit for alarm 1. (Only available when alarm is set in the initial setting mode). 4.0 oC
ALARM 1 LOW: Lower limit for alarm 1. (Only available when alarm is set in the initial setting mode). 4.0 oC
ALARM 2 HIGH: Upper limit for alarm 2. (Only available when alarm is set in the initial setting mode). 4.0 oC
ALARM 2 LOW: Lower limit for alarm 2. (Only available when alarm is set in the initial setting mode). 4.0 oC
Lock Function Setting: LoC1, LoC2, or OFF. LoC1 mode will lock all settings, LoC2 locks everything
except the setpoint value, and OFF will not lock any settings. Press and keys simultaneously, to
release the lock status.
OFF
OUT: The Output value adjustment and display in manual tuning control. (Not available in ON/OFF or
Auto-tuning control). 0
2. Regulation Mode: Control parameters Settings
LED Ex
p
lanation Default
AT (Auto-Tuning): ON or OFF, when set ON, the execution of the auto-tuning function in PID control
mode is automatically started. (Only available when PID control is selected in initial settings) OFF
P (Proportional Band in PID control): Sets P value. 47.6
I (Integral Time in PID control): Sets I value. 260
D (Derivative Time in PID control): Sets D value. 41
PdoF: Offset output when P or PD control function is on. PID in initial settings is selected and the value
of Ki (Integral Time in regulation mode) is equal to zero. 0
ioF: Default value of integral volume when PID control is ON and the Ki (Integral Time in regulation
mode) is not equal to zero. AT function can automatically set this parameter when PID control is active
and Ki≠0.
0
HtS (Heating Hysteresis): Available only in ON/OFF control. Sets the value the heating hysteresis. 0
CtS (Cooling Hysteresis): Available only in ON/OFF control. Sets the value the cooling hysteresis. 0
HtPd: PID heating control cycle setting. Only available when a PID control is selected in the initial
settings.
ClPd: PID cooling control cycle setting. Only available when a PID control is selected in the initial
settings.
Output Selection:
Voltage: 4 sec.
Relay : 20 sec.
TPoF: Regulates the temperature deviation value. 0
CrHi: Regulates the 20 mA output deviation value. 0
CrLo: Regulates the 4 mA output deviation value. 0
HtS (Heating Hysteresis): Available only in ON/OFF control. Sets the value the heating hysteresis. 0

3. Initial Setting Mode: Initial settings of the controller and communication parameters
LED Ex
p
lanation Default
INPUT: Select input temperature sensor type
(Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail) PT2
Engineering Unit(°F or °C): Select engineering unit F or C. oC
T-High: Upper limit for temperature range. 500.0
T-Low: Lower limit for temperature range. -20.0
CONTROL METHOD (ON/OFF, PID, or manual tuning [ ]): Sets the control method for the set
point value. PID
Control Action (Direct or Reverse Acting): Cooling [Cool] or heating [HEAT]. HEAT
ALARM 1: Alarm 1 setting. (See Alarm Output Section for set values and descriptions). 0
ALARM 2: Alarm 2 setting. (See Alarm Output Section for set values and descriptions). 0
C WE: Write-in function disabled/enabled. Can be set only when unit is equipped with serial
communication. OFF
C NO: Address setting. Can be set only when unit is equipped with serial communication. 1
BPS: Baud rate setting. Can be set only when unit is equipped with serial communication. 9600
Length: Data length setting. Can be set only when unit is equipped with serial communication. 7
Parity: Parity bit setting. Can be set only when unit is equipped with serial communication. E
Stop Bit: Stop bit setting. Can be set only when unit is equipped with serial communication. 1
Execution :
The programming execution is initiated through in the operation mode.
When is set to , the program will start to execute in order from the step 0 of the start pattern.
When is set to , the program will stop and the control output is disabled
5 Heating and Cooling
Temperature control can be achieved either by heating or cooling. Please refer to the following for the operation: Settings for heat or
cool operation are found in the initial settings mode under .
Select , for heating (reverse) control on Output 1.
Select , for cooling (forward) control on Output 1
Input Error Indication
Setting
value Temperature sensor is not connected Measured temperature value exceeds
the temperature range Unknown input
PV
SV
6 Alarm Outputs
Depending on the controller model, there can be up to two alarm outputs. Each alarm output can be configured for an alarm type
listed below. Alarm types are set in the initial setting mode. The alarm output is activated whenever the process temperature value
(PV) is getting higher or lower than the set point of alarm limit.
Set
Value Alarm Type Alarm Output Operation
0 Alarm function disabled Out
p
ut OFF
1
Deviation upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value
SV+(AL-H) or lower than the setting value SV-(AL-L).
ON
OFF
SV-(AL-L) SV SV+(AL-H)
2
Deviation upper-limit:
This alarm output operates when PV value is higher than the setting value
SV+(AL-H).
ON
OFF
SV SV+(AL-H)
3
Deviation lower-limit:
This alarm output operates when PV value is lower than the setting value
SV-(AL-L).
ON
OFF
SV
SV-(AL-L)
4
Reverse deviation upper- and lower-limit:
This alarm output operates when PV value is in the range of the setting value
SV+(AL-H) and SV-(AL-L).
ON
OFF
SV
SV-(AL-L) SV+(AL-H)

5
Absolute value upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value
AL-H or lower than setting value AL-L.
ON
OFF
AL-L AL-H
6
Absolute value upper-limit:
This alarm output operates when PV value is higher than the setting value
AL-H.
ON
OFF
AL-H
7
Absolute value lower-limit:
This alarm output operates when PV value is lower than the setting value AL-
L.
ON
OFF
AL-L
8
Deviation upper- and lower-limit with standby sequence:
This alarm output operates when PV value reaches set point (SV value) and
the value is higher than the setting value SV+(AL-H) or lower than the setting
value SV-(AL-L).
ON
OFF
SV
SV-(AL-L) SV+(AL-H)
9
Deviation upper-limit with standby sequence:
This alarm output operates when PV value reaches set point (SV value) and
the reached value is higher than the setting value SV+(AL-H).
ON
OFF
SV SV+(AL-H)
10
Deviation lower-limit with standby sequence:
This alarm output operates when PV value reaches the set point (SV value)
and the reached value is lower than the setting value SV-(AL-L).
SV-(AL-L)
ON
OFF
SV
11
Hysteresis alarm output:
Heating control: This alarm output operates if PV value is higher than the
setting value SV+(AL-H). This alarm output is OFF when PV value is lower
than the setting value SV+(AL-L).
ON
OFF
AL-L
SV AL-H
12
Hysteresis alarm output:
Cooling control: This alarm output operates if PV value is lower than the
setting value SV-(AL-H). This alarm output is OFF when PV value is higher
than the setting value SV-(AL-L).
ON
OFF
AL-H AL-L SV
(Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L)
With the standby sequence, the alarm output will be temporarily disabled until the PV value reaches the set value. Then, the alarm
output will operate. Once the alarming output operation is activated, there is a 1.5 sec. delay time to avoid any malfunction.
7 Specification
Input Voltage 100 to 240VAC 50/60Hz
Operation Voltage Range 85% to 110% of rated voltage
Power Consumption 5VA max.
Memory Protection EEPROM 4K bit (non-volatile memory (number of writes: 100,000)
Display Method 2 line x 4 character 7-segment LED display Process value(PV): Red color, Set point(SV): Green
color
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Sensor Type 3-wire Platinum RTD: Pt100, JPt100
Control Mode PID, ON/OFF, Manual or Auto-tuning.
Relay output: SPDT (SPST on the 1/16 DIN size series16C), Max. load 250VAC, 5A resistive load
Voltage pulse output: DC 14V, Max. output current 40mA
Control Output
Current output: DC 4 ~ 20m A output (Load resistance: Max. 600Ω)
Display Accuracy 0.1% of measuring range.
Sampling Rate 0.5 sec.
RS-485 Communication MODBUS ASCII communication protocol (only on models designated with serial communication).
Vibration Resistance 10 to 55Hz, 10m/s2for 10min, each in X, Y and Z directions
Shock Resistance Max. 300m/ s2, 3 times in each 3 axes, 6 directions
Ambient Temperature 32 oF to 122 oF (0 oC to +50 oC)
Storage Temperature -4 oF to 150 oF (-20 oC to +65 oC)
Altitude 2000m or less
Relative Humidity 0% to 80% (non-condensing)

8 Plan Cutout and External Dimensions
Panel Cutout [dimensions are in mm (in.)]
Terminals Identification
16C
65.0 min.
(2.56)
45.0
(1.77)
45.0
(1.77)
60.0min.
(2.36)
+0.6
-0
+0.02
-0
+0.6
-0
+0.02
-0
mm
(in)
1
4
3
2
5
Tc
+
-
RTD
7
6
9
8
10
14V
DC
DATA-
DATA+
RS-485
11
14
15
13
12
AC100~240V
50/60 Hz
5VA
3A
250Vac
ALM2
ALM1
COM
3A
250Vac
NO
OUT1
14V
or
4~20mA
or
0~10V
DC
+
-
COM NO
COM
+
-
IN
OUT2/
ALM3
+
-
L
N
8C
1
2
5
6
8
7
4
3
9
12
13
14
15
11
10
5A 250Vac
RTD
Tc
+
-
or
DATA-
DATA+
RS-485
ALM1
ALM2
3A 250Vac
3A 250Vac
16
18
17
19
20
AC 100~240V
50~60Hz /5VA
DC4~20mA
COM
COM
14Vdc
NC
NO
COM +
-
L
N
4C
1
2
5
6
8
7
4
3
9
12
13
14
15
11
10
5A 250Vac
RTD
Tc
+
-
or
DATA-
DATA+
RS-485
ALM1
ALM2
3A 250Vac
3A 250Vac
16
18
17
19
20
AC 100~240V
50~60Hz /5VA
DC4~20mA
COM
COM
14Vdc
NC
NO
COM +
-
L
N

9 External Dimensions
Dimensions are in millimeter (inch)
16C
4C
8C
10 Mountin
g
Mounting Method
Step 1: Insert the controller through the panel cutout.
Step 2: Insert the mounting bracket into the mounting groove at
the top and bottom of the controller
Step 3: Push the mounting bracket forward until the bracket stops
at panel wall.
Step 4: Insert and tighten screws on bracket to secure the
controller in place. (The screw torque should be 0.8kgf-cm to
1.5kgf-cm)
16C/8C/4C Mounting Method:
Mounting Bracket Installation
Table of contents
Other Love Controls Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Honeywell
Honeywell T991A Specifications

red lion
red lion TCU product manual

LK Armatur
LK Armatur SmartBio LK 160 instruction manual

Jung
Jung TR 231 Series operating instructions

Sub-Zero
Sub-Zero SZ-7524T operating instructions

Greenheck
Greenheck Vari-Green Control 475573 Installation, operation and maintenance manual