1949319 V1.4 June 2019
Installation:
The LP Weatherproof Supalite (CWFLED-IPREM) is Surface Mounted. The Control gear and
Lamp Heads are housed in weatherproof enclosures. The enclosures are attached to the wall
using screws installed through the 4 isolated holes. Please follow the steps belowto install the
Weatherproof fitting.
Control Gear
•Remove the Control Gear cover.
•Remove the gear tray.
•Determine power entry.
•Drill power access hole in the box base.
•Position the box base in the mounting position.
•Mark the 4 holes for mounting. Install the base using appropriate fixings (not supplied).
•Connect the 240VAC supply to the terminal block on the Gear Tray.
•Reinstall the gear tray.
Remote Lamps
•Remove the enclosure cover.
•Determine cable entry point for LED cable from the Control Gear.
•Drill appropriate hole and install an appropriate cable gland.
•Position the box and mark out the mounting holes. Install the box using appropriate
fixings.
•Route and connect the LED drive cables from the Control Gear (LED+, LED-) using
appropriate weatherproof glands between the Control Gear and the Lamp Heads to
maintain the IP65 rating.
•If the CTP capabilities are activated, please affix the CTP status Label to a visible
surface
Networking:
When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply
insert the relevant Smart Node PCA.
Images and Dimensions:
Testing:
When the Supalite unit is connected to the un-switched active, it must be allowed to charge
the battery for at least 24 hours. The emergency lamp only illuminates during a power fail.
Conduct the following tests:
•The emergency lamps must illuminate for at least 2 hours after disconnection from the
mains. The results of all tests are required to be recorded in a service logbook, which is
to be kept on-site at all times. If the unit fails to illuminate for the requisite time, remedial
action must be taken to repair the situation and once completed, the unit must pass a
subsequent test.
•Press and hold Test Button or switch Off Mains Supply, check that the emergency
lamps are On.
•Release the Test Button or Switch On Mains Supply, check that the emergency lamps
are Off (Non-maintained operation).
Below are a list of common problems and their possible causes:
Fault: The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer
to spacing tables for installation positions):
N/A –refer to the IES file when doing computer aided design or request spacing guidance
from Clevertronics.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis
during construction. As a result, any Supalite Units on these circuits, will have their batteries
discharged or “cycled”. The battery in the Supalite has been selected to give excellent long-
life performance in a controlled IEC 60598-2-22 testing environment. Excessive battery
cycling will reduce through-life performance and may lead to premature battery failure.
Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from
Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our
website http://clevertronics.com.au/terms-conditions-sale-australia-nz/