iv
Ambient temp.
CT Load: - 10 ~ 50℃(non-freezing)
VT Load: -10 ~ 40℃(non-freezing)
Note: Use below 80% of load when used under VT
Load at 50℃
Relative humidity 90% RH or less (non-condensing)
Storage temp. - 20 ~ 65 ℃
Location Protected from corrosive gas, combustible gas, oil
mist or dust
Altitude, Vibration Max. 1,000m above sea level, Max. 5.9m/sec2
(0.6G) or less
Environment
Atmospheric pressure 70 ~ 106 kPa
(2) Wiring
Do not connect a power factor correction capacitor, surge suppressor, or RFI filter to the output of
the inverter.
The connection orientation of the output cables U, V, W to the motor will affect the direction of
rotation of the motor.
Incorrect terminal wiring could result in the equipment damage.
Reversing connection of the input/output terminals(R,S,T / U,V,W) could damage the inverter.
Only authorized personnel familiar with LS inverter should perform wiring and inspections.
Always install the inverter before wiring. Otherwise, you may get an electric shock or have bodily
injury.
(3) Trial run
Check all parameters during operation. Changing parameter values might be required depending
on the load.
Always apply permissible range of voltage to the each terminal as indicated in this manual.
Otherwise, it could lead to inverter damage.
(4) Operation precautions
When the Auto restart function is selected, stay away from the equipment as a motor will restart
suddenly after an alarm stop.
The Stop key on the keypad is valid only when the appropriate function setting has been made.
Prepare an emergency stop switch separately.
If an alarm reset is made with the reference signal present, a sudden start will occur. Check that
the reference signal is turned off in advance. Otherwise an accident could occur.
Do not modify or alter anything inside the inverter.
Motor might not be protected by electronic thermal function of inverter.
Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.
Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic
equipment may be affected.
In case of input voltage unbalance, install AC reactor. Power Factor capacitors and generators may
become overheated and damaged due to potential high frequency noise transmitted from inverter.