LS iP5A User manual

Fan and Pump AC Drive
0.75~30kW(1~40HP) 3-Phase 200~230V
0.75~450kW(1~700HP) 3-Phase 380~480V
5.5~110kW(7.5~150HP) 3-Phase 525~600V
iP5A
•
For your safety, please read user's manual thoroughly before operating.
•
Contact the nearest authorized service facility for examination, repair, or adjustment.
•
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself
!
•
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
Safety Instructions
■ Overseas Branches
•LSIS Shanghai Office (China)
Tel: 86-21-5237-9977(609) Fax: 86-21-5237-7189 E-Mail:ygeo@lsis.com
•LSIS Beijing Office (China)
Tel: 86-10-5761-3127 Fax:86-10-5761-3128 E-Mail:htroh@lsis.com
•LSIS Guangzhou Office (China)
Tel: 86-20-8326-6784 Fax:86-20-8326-6287 E-Mail:sojhtroh@lsis.com
•LSIS Qingdao Office (China)
Tel: 86-532-8501-6058 Fax:86-532-8501-6057 E-Mail: htroh@lsis.com
•LSIS Chengdu Office (China)
Tel: 86-28-8670-3200 Fax:86-28-8670-3203 E-Mail: yangcf@lsis.com
•LSIS ShenYang Office (China)
Tel:86-24-2321-9050 Fax:86-24-8386-7210 E-Mail: yangcf@lsis.com
•LSIS Jinan Office (China)
Tel: 86-531-8699-7826 Fax:86-531-8697-7628 E-Mail: yangcf@lsis.com
•LSIS Co., Ltd. Tokyo Office (Japan)
Tel: 81-3-6268-8241 Fax:81-3-6268-8240 E-Mail: jschuna@lsis.com
•LSIS Co., Ltd. Rep.Office (Vietnam)
Tel: 84-8-3823-7890 E-Mail: sjbaik@lsis.com
•LSIS Moscow Office (Russia)
Tel: 7-499 682 6130 E-Mail:info@lsis-ru.com
•LSIS Jakarta Office (Indonesia)
Tel: 62-21-293-7614 E-Mail: dioh@lsis.com
■ Head Quarter
LS-ro 127(Hogye-dong) Dongan-gu, Anyang-si, Gyeonggi-Do, 14119, Korea
Tel: 82-2-2034-4620 mswoo@lsis.com
Tel: 82-2-2034-4907 hjchoid@lsis.com
■ Overseas Subsidiaries
•LSIS(Dalian) Co., Ltd. (Dalian, China)
Tel: 86-411-8730-7510 Fax: 86-411-8730-7560 E-Mail: dskim@lsis.com
•LSIS(Wuxi) Co., Ltd. (Wuxi, China)
Tel: 86-510-8534-6666-8005 Fax: 86-510-8534-4078 E-Mail: sojin@lsis.com
•LS VINAIndustrial Systems Co., Ltd. (Hanoi, Vietnam)
Tel: 84-4-6275-8055 Fax: 84-4-3882-0220 E-Mail: hjchoid@lsis.com
•LSIS Middle East FZE(Dubai, U.A.E.)
Tel: 971-4-886-5360 Fax: 971-4-886-5361 E-Mail: shunlee@lsis.com
•LSIS Europe B.V. (Amsterdam, Netherlands)
Tel: 31-20-654-1420 Fax: 31-20-654-1429 E-Mail: europartner@lsis.com
•LSIS Japan Co., Ltd. (Tokyo, Japan)
Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: jschuna@lsis.com
•LSIS USAInc. (Chicago, U.S.A.)
Tel: 1-800-891-2941 Fax: 1-847-383-6543 E-Mail: sales.us@lsis.com
2017. 09
2006. 08 LSIS Co., Ltd. All Rights Reserved. / (23) 2017.09 Pacomkorea

STARVERT iP5A
LS Starvert SV-iP5A has been specifically designed
and created to provide competitive solutions for fan
and pump applications
2 55
Drive Starvert iP5A Series
Industrial Drive for Fan and Pump STARVERT iP5A
iP5A
MEMO

Overview
Model & Type
Standard Specifications
Wiring
Terminal Configurations (Power Circuit Terminal)
Terminal Configurations (Control Circuit Terminal)
Programming Keypad
Programming Keypad (Parameter Navigation)
Parameter Description
Trial Run
Dimensions
DB (Dynamic Braking) Unit
External DB Resistor / Peripheral Device
4
8
9
13
17
19
22
23
24
37
39
45
50
Contents
Industrial Drive for Fan and Pump STARVERT iP5A
STARVERT
iP5A
Marine Type
Certification
From DNV
Specialized
Functions for
Fan and Pump
Energy
Saving and High
Efficiency
User-friendly
Interface
and Easy
Maintenance
Intelligent
Control
Mechanism
3
Drive Starvert iP5A Series

iP5AiP5A
Specialized Functions for Fan and Pump
The iP5A, specifically designed for HVAC application, provides stable and cost-effective system
performance.
In the centrifugal fan and pump field, PID control is provided as a standard function in order to maintain a constant
control of pressure, flow and oil level. This function includes Pre-PID, Sleep and Wake up and output inverse sub-
functions.
PID Control
Where external or cascaded PID control is required, the built-in dual PID
algorithm of the iP5A can be utilized to satisfy various system requirements.
Dual PID
Multi Motor Control (0.75~450kW)
The iP5A MMC function provides cost-effective, simultaneous control of up to eight motors, without requiring external
controllers.
Marine Type Certification From DNV
The iP5A has been tested and certified by DNV to comply with International Marine
requirements
4

0.75
0.50
0.40
0.25
0.20
0.10
010 20 30 40 50 60 70
Load %
Conventional
drive control
iP5A
Damper control
Reduction percentage
600RPM V/F
30% manual
energy saving
Automatic
energy saving
Energy Saving and High Efficiency
The iP5A, specifically designed for fan and pump applications, guarantees energy savings by optimizing the
system.
Load change may incur energy losses but the optimized flux control of iP5A results in more outstanding energy saving
compared to previous models.
Automatic Energy Saving
Energy savings are obtained through the Sleep and Wake-Up functions of the iP5A, which enable the drive to
automatically switch off during user-programmed low-load conditions and then to start up again when process demand
increases.
Sleep and Wake-up Function
When using the drive in damp conditions, this function protects both the motor and the drive's output
Pre Heating Function
When 2 or more fans, or a high inertia load are connected to the drive, the iP5A detects the motor speed after a
momentary power failure, enabling the motors to be smoothly reaccelerated without mechanical and electrical shock-
loading to the system.
Flying Start Function
PID reference
PID feedback
Run command
Output frequency
Wake-up mode
Returning to
normal state
Sleep mode
Adjusting output
with detecting load
(Energy saving)
Industrial Drive for Fan and Pump STARVERT iP5A
5
Drive Starvert iP5A Series

iP5A
During unexpected power failure conditions, the iP5A can bring the load to a controlled stop, by utilizing the inertial
energy. This can prevent further process problems or accidents.
Safety Stop
This algorithm reduces deceleration time, thereby improving system efficiency.
Flux Braking Algorithm
Intelligent Control
By taking ambient temperature into account, the iP5A can automatically adjust the Carrier (Modulation) Frequency.
Automatic Carrier Frequency Change
The iP5A has optimized protective functions, such as safety stop and pre-excitation of the motor, amongst others.
Protection
Because of effectual functions and protection algorithms, the iP5A provides constant performance,
in spite of external power fluctuations.
During Power Dips or Momentary Power Outage, the drive output can be maintained by utilizing the residual mechanical
energy in the load as a regenerative source. The duration of the power-dip ride-through depends on the load
characteristics.
Improved System Management during Power Dips and Momentary Power Outages
In spite of external voltage fluctuations and lightning surges, the iP5A optimizes motor performance.
Constant and Stable Performance
Under damp conditions, leakage currents can occur when
using drives. These currents can cause a system failure.
The iP5A low-leakage PWM algorithm reduces these
leakage currents to ensure reliability of operation.
Current Leakage Reduction Algorithm
Zero vector Zero vector
Valid vector
PWM
Valid vector
Power failure for 1 second
Power failure for 3 seconds
Mecha
-nical
energy
Load
Mechanical
energy
Consumed
energy
Emitted energy
The mechanical energy
stored during blackout can
be used for driveユs power.
iP5A
6

Easy Start
When pushing ‘STOP’key for
2~3 seconds in case drive
turns on, the drive turns into
‘Easy Start Mode’with FWD,
REV, and STOP command.
‘SHIFT/ESC’can return it to
previous mode.
Control method: V/F
Control frequency: Jog
User-friendly Keypad & Easy Maintenance
NPN/PNP Input
iP5A has both NPN and PNP input, and you can select
one of them easily.
Abundant I/O Suggestion
iP5A serves abundant I/O.
Various Units of I/O Display
The iP5A display can be calibrated in many different types
of process units.
Built-in RS485 and Optional Communication
The built-In RS485 allows for communication without external option.
However, the optional communication boards enable the iP5A to talk
to BMS and most Industrial Systems
Long-life Condenser and Simple Framework
iP5A adopts long-life condenser and enables easy maintenance in
simple framework.
Consumption Time Display
iP5A displays consumption time of components so that users can
replace them in time.
Others
•
Removable terminal board
•
External fan available
•
Cooling fan on/off control
3
1 4
5
6
7
2
3
8
4
1
2 6
The iP5A construction allows for easy maintenance, with ease-of-access to all components.
5
7 9
Digital Input/Output
Analog Input (Voltage + Current)/Output
Pulse Input
NTC/PTC Input
8 points / 4 points
(1+1) points /4 points
1 point
1 point
Industrial Drive for Fan and Pump STARVERT iP5A
7
Drive Starvert iP5A Series

iP5AiP5A
SV
SV055iP5A-2NE
055
iP5A
2
-- NE
200~230V Class 380~480V Class
Motor Rating
0.75kW (1HP)
1.5kW (2HP)
2.2kW (3HP)
3.7kW (5HP)
5.5kW (7.5HP)
7.5kW (10HP)
11kW (15HP)
15kW (20HP)
18.5kW (25HP)
22kW (30HP)
30kW (40HP)
37kW (50HP)
45kW (60HP)
55kW (75HP)
75kW (100HP)
90kW (125HP)
110kW (150HP)
132kW (200HP)
160kW (250HP)
220kW (300HP)
280kW (350HP)
315kW (400HP)
375kW (500HP)
450kW (600HP)
SV008iP5A-4NE
SV015iP5A-4NE
SV022iP5A-4NE
SV037iP5A-4NE
SV055iP5A-4NE
SV075iP5A-4NE
SV110iP5A-4NE
SV150iP5A-4NO
SV185iP5A-4NO
SV220iP5A-4NO
SV300iP5A-4NO
SV370iP5A-4O
SV450iP5A-4O
SV550iP5A-4O
SV750iP5A-4O
SV900iP5A-4O
SV1100iP5A-4OL
SV1320iP5A-4OL
SV1600iP5A-4OL
SV2200iP5A-4OL
SV2800iP5A-4OL
SV3150iP5A-4O
SV3750iP5A-4O
SV4500iP5A-4O
380~480V Class
(Classification)
SV055iP5A-4NE (CLASS)
SV075iP5A-4NE (CLASS)
SV110iP5A-4NE (CLASS)
SV150iP5A-4NOL (CLASS)
SV185iP5A-4NOL (CLASS)
SV220iP5A-4NOL (CLASS)
SV300iP5A-4NOL (CLASS)
SV370iP5A-4OL (CLASS)
SV450iP5A-4OL (CLASS)
SV550iP5A-4OL (CLASS)
SV750iP5A-4OL (CLASS)
SV900iP5A-4OL (CLASS)
SV1100iP5A-4OL (CLASS)
SV1320iP5A-4OL (CLASS)
SV1800iP5A-4OL (CLASS)
SV2200iP5A-4OL (CLASS)
SV2800iP5A-4OL (CLASS)
SV3150iP5A-4O (CLASS)
SV3750iP5A-4O (CLASS)
SV4500iP5A-4O (CLASS)
525~600V Class
SV055iP5A-6
SV075iP5A-6
SV110iP5A-6
SV150iP5A-6
SV185iP5A-6
SV220iP5A-6
SV300iP5A-6
SV370iP5A 6
SV450iP5A-6
SV550iP5A-6
SV750iP5A-6
SV900iP5A-6
SV1100iP5A-6
SV008iP5A-2NE
SV015iP5A-2NE
SV022iP5A-2NE
SV037iP5A-2NE
SV055iP5A-2NE
SV075iP5A-2NE
SV110iP5A-2NE
SV150iP5A-2NO
SV185iP5A-2NO
SV220iP5A-2NO
SV300iP5A-2NO
Model Number
Input Rating
Output Rating
Protection Degree
Bar Cord
Serial Number
INPUT 200-230 V 3 Phase
25A 50/60HZ
OUTPUT 0-Input V 3 Phase
24A 0.01-120HZ
9.1KVA, Enclosed Type 1
Model & Type
(CLASS)
Marine Approved Drives
needs additional ordering.
N: No Keypad
O: UL Open Type
E: UL Enclosed Type 1
L: Built-in DC Reactor
(15~90kW : Option / 110~280kW : Standard)
200-230V
380-480V
525-600V
2
4
6
Input Voltage
5.5 kW
90 kW
055
900
Motor Rating
iP5A
Series Name Classification
8

Industrial Drive for Fan and Pump STARVERT iP5A
Standard Specifications
Note 1) Rated capacity (v 3。。V。。I) is based on 220V for 200V class and 460V for 400V class. 2) Indicates the maximum applicable capacity when using a 4-Pole LS motor.
3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary.
4) IP20/UL Type1 with optional conduit, it can be modified to UL Type1.
380~480V Class (0.75~90kW / 1~125HP)
Model Number (SV iP5A-4)008 015 022 037 055 075 110 150 185 220 300 370 450 550 750 900
2.0 3.2 4.8 6.4
9.6 12.7 19.1 23.9 31.1 35.9 48.6 59.8 72.5 87.6 121.1 145.8
1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
2.5 4 6 8 12 16 24 30 39 45 61 75 91 110 152 183
110% 1 Minute (Normal Duty)
0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
1.25 2.5 4 6 8.8 12 16 22/24 28/30 34/39 44/45 - - - - -
150% 1 Minute (Heavy Duty)
0.01~120 Hz
380~480V
3Ø380~480V (-15%~+10%)
50/60 Hz (±5%)
IP20 / UL Type1 IP00 / UL Open
4.1(9.0) 4.2(9.3) 4.2(9.3) 4.9(10.8) 4.9 (10.8) 6 (13.2) 6 (13.2)
12.5 (27.6)
13 (28.7) 20 (44.1) 20 (44.1) 27 (59.5) 27 (59.5) 29 (64) 42 (92.6) 43 (94.8)
- - - - - - - 19.5 (43.9)
19.5 (42.9)
26.5 (58.3)
26.5 (58.3)
39 (86) 40 (88.2) 42 (92.6)
67 (147.4)
68 (149.9)
Note3)
Note4)
Capacity [kVA]
Motor rating (HP)
Fan or (kW)
pump load Current [A]
(110% over current)
Output Motor rating (HP)
ratings General (kW)
load Current [A]
(150% over current)
Frequency
Voltage
Input Voltage
ratings Frequency
Protection degree
Weight [kg (lbs.)] Standard Type
Built-in DCL Type
Note1)
Note2)
200~230V Class (0.75~30kW / 1~40HP)
Model Number (SV iP5A-2)008 015 022 037 055 075 110 150 185 220 300
1.9
3.0
4.6
6.1
9.1 12.2 17.5 22.9 28.2 33.5 43.8
1 2 3 5 7.5 10 15 20 25 30 40
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30
5 8 12 16 24 32 46 60 74 88 115
110% 1 Minute (Normal Duty)
0.5 1 2 3 5 7.5 10 15 20 25 30
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
2.5 5 8 12 17 23 33 44 54 68 84
150% 1 Minute (Heavy Duty)
0.01~120 Hz
200~230V
3Ø200~230V (-15%~+10%)
50/60 Hz (±5%)
IP20 / UL Type1 IP00 / UL Open
4.1(9.0) 4.2(9.3) 4.2(9.3) 4.9(10.8) 4.9 (10.8) 6 (13.2) 6 (13.2) 13 (28.7) 13.5 (29.8) 20 (44.1) 20 (44,1)
Note3)
Note4)
Capacity [kVA]
Motor rating (HP)
Fan or (kW)
pump load Current [A]
(110% over current)
Output Motor rating (HP)
ratings General (kW)
load Current [A]
(150% over current)
Frequency
Voltage
Input Voltage
ratings Frequency
Protection degree
Weight [kg (lbs.)]
Note1)
Note2)
9
Drive Starvert iP5A Series

iP5AiP5A
Standard Specifications
380~480V Class (110~450kW / 50~125HP)
Model Number (SV iP5A-4)1100 1320 1600 2200 2800 3150 3750 4500
178 210 259 344 436 488 582 699
150 200 250 350 400 500 600 700
110 132 160 220 280 315 375 450
223 264 325 432 547 613 731 877
110% 1 Minute (Normal Duty)
125 150 200 250 350 400 500 600
90 110 132 160 220 280 315 375
183 223 264 325 432 547 613 731
150% 1 Minute (Heavy Duty)
0.01~120 Hz
380~480V
3Ø380~480V (-15%~+10%)
50/60 Hz (±5%)
IP00 / UL Open
Built-in External Option
101 (222.7) 101 (222.7) 114 (251.3) 200 (441.9) 200 (441.9) 243 (535.7) 380 (837.7) 380 (837.7)
Note3)
Note4)
Capacity [kVA]
Motor rating (HP)
Fan or (kW)
pump load Current [A]
(110% over current)
Output Motor rating (HP)
ratings General (kW)
load Current [A]
(150% over current)
Frequency
Voltage
Input Voltage
ratings Frequency
Protection degree
DCL
Weight [kg (lbs.)]
Note1)
Note2)
525~600V Class (5.5~110kW /7.5~150HP)
Model Number (SV iP5A-6)055 075 110 150 185 220 300 370 450 550 750 900 1100
9.6 12.7 19.1 23.9 31.1 35.9 48.6 59.8 72.5 87.6 121.1 145.8 178
7.5 10 15 20 25 30 40 50 60 75 100 125 150
5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110
9 12 17 23 27 34 43 55 64 80 104 128 150
110% 1Minute (Normal Duty)
5.5 7.5 10 15 20 25 30 40 50 60 75 100 125
3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
6.1 9 12 17 23 27 34 43 55 64 80 104 128
150% 1 Minute (Heavy Duty)
0.01~120 Hz
525 ~600V
3f 525~600V (-15% ~ +10 %)
50/60 Hz (±5 %)
IP20 / UL Type1 IP00 / UL Open
6.5 7.0 7.0 11.7 11.7 18.9 18.9 32 32 32 46 46 101
(14.4) (15.5) (15.5) (25.8) (25.8) (41.7) (41.7) (70.65) (70.65) (70.65) (101.5) (101.5) (223)
Note3)
Note4)
Capacity [kVA]
Motor rating (HP)
Fan or (kW)
pump load Current [A]
(110% over current)
Output Motor rating (HP)
ratings General (kW)
load Current [A]
(150% over current)
Frequency
Voltage
Input Voltage
ratings Frequency
Protection degree
Weight [kg (lbs.)] Standard Type
Note 1) Rated capacity (v 3 X V X I) is based on 220V for 200V class and 460V for 400V class. 2) Indicates the maximum applicable capacity when using a 4-Pole LS motor.
3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary.
4) IP20/UL Type1 with optional conduit, it can be modified to UL Type1.
10

Industrial Drive for Fan and Pump STARVERT iP5A
(1) Rated capacity (√3×V×I) is based on 220V for 200V class and 460V for 400V class. (2) Indicates the maximum applicable capacity when using a 4-Pole standard motor.
(3) IP20 or UL Enclosed Type1 can be provided by the option. (4) IP20 or UL Enclosed Type1 is not provided.
(5) Overload rating 120%, 1 min is based on ambient 25℃
Forced air cooling (Self-cooling for below 1.5kW-2, 2.2kW-4)
V/F, Sensorless Vector, Slip Compensation, Easy Start Selectable
Digital Reference: 0.01 Hz (Below 100 Hz), 0.1 Hz (Over 100 Hz)
Analog Reference: 0.01 Hz / 60 Hz
Digital: 0.01% of the max frequency
Analog: 0.1% of the max frequency
Linear, Squared Pattern, User V/F
110% per 1 min, 120% per 1 min
Note5)
Manual Torque Boost (0 ~ 15 %), Auto Torque Boost
Keypad / Terminal / Communication Operation
Analog: 0 ~ 12V / -12V ~ 12V / 0~20mA/ Pulse / Ext-PID
Digital: Keypad
Forward, Reverse
Up to 18 Speeds can be set including Jog (Use Programmable Digital Input Terminal,Including Jog/Dwell )
0.1~ 6,000 sec, Max 4 types can be set via Multi- Function Terminal. Accel/Decel Pattern: Linear,
U-Curve, S-Curve Selectable
Interrupts the Output of Drive
Jog Operation
Fault Reset
Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Low Voltage, Drive Overheating/
Running/ Stopping/ Const ant running, Drive By-Pass, Speed Searching
Contact Output (3A, 3C, 3B) - AC 250V 1A, DC 30V 1A
Choose 2 from Output Frequency, Output Current, Output Voltage, DC Link Voltage
(Output Voltage: 0 ~ 10V)
DC Braking, Frequency Limit, Frequency Jump, 2nd Function, Slip Compensation, Reverse Rotation
Prevention, Auto Restart, Invert By-Pass Auto-Tuning PID Control Start Stop Braking leakage Pre-PID
Dual-PID MMC Start Prer By Pass, Auto Tuning, Control, Flying Start, Safety Stop, Flux Braking,
Low leakage, Pre PID, Dual PID, MMC, Easy Start, e-heater
Over Voltage, Low Voltage, Over Current, Ground Fault, Drive Overheat, Motor Overheat, Output Phase
Open, Overload Protection, External Fault 1, 2, Communication Error, Loss of Speed Command,
Hardware Fault, Option Fault etc
Stall Prevention, Overload Alarm, Thermal Sensor Fault
Output Frequency, Output Current, Output Voltage, Frequency Set Value, Operating Speed, DC Voltage,
Integrating Wattmeter, Fan ON time, Run-time, Last Trip Time
Trips Indication when the Protection Function activates.
Max. 5 Faults are saved.
Last Trip Time.
-10℃~ 50℃(14℉~ 122℉)
Decrease 2% of rated current for every 1℃increase in above 40℃
-20℃~ 65℃(-4℉~ 149℉)
Below 90 % RH Max. (Non-Condensing)
Below 1,000m (From 1000 to 4000m, the rated input voltage and rated output current of the drive must be
derated by 1% for every 100m.), Below 5.9m/sec2 (0.6g)
Pollution degree 2, No Corrosive Gas, Combustible Gas, Oil Mist, or Dust
Common Specifications
Cooling method
Control Method
Frequency Setting Resolution
Frequency Accuracy
V/F Pattern
Overload Capacity
Torque Boost
Operation Method
Frequency Setting
Start Signal
Multi-Step
Multi Step Accel/Decel Time
Emergency Stop
Jog
Fault Reset
Operating Status
Fault Output
Indicator
Operation Function
Drive Trip
Drive Alarm
Operation Information
Trip Information
Ambient Temperature
Storage Temperature
Ambient Humidity
Altitude-Vibration
Application Site
Keypad
Output signal
Input Signal
Environment
Display
Protection
Operation Control
11
Drive Starvert iP5A Series

iP5AiP5A
Standard Specifications
LCD
32 character display
All units
keypad Download and Upload available
Remote cable
2m, 3m and 5m long keypad cable enables users
Optional
to control the drive from a distant area
DB resistor
To enhance the regenerative braking performance,
it makes the drive to accelerate/decelerate rapidly According to drive
DB unit
If it need a regenerative braking, it is used with DB resistor
capacity
Conduit for
Install it to fit for NEMA TYPE 1 Enclosure or IP20
15~90kW
NEMA TYPE 1 (20~125HP)
DEVICENET DEVICENET optional communication card
All series
(Above S/W V10)
PROFIBUS PROFIBUS optional communication card
All series
(Above S/W V10)
LS485/MODBUS_RTU LS485/MODBUS_RTU optional communication card
All series
(Above S/W V10)
LonWorks Lonworks optional communication card
All series
(Above S/W V10)
BACNet BACNet optional communication card
All series
(Above S/W V10)
MODBUS_TCP MODBUS_TCP optional communication card
All series
(Above S/W V10)
Metasys_N2 Metasys_N2 optional communication card
All series
(Above S/W V10)
CCLink CCLink optional communication card
All series
(Above S/W V10)
CANopen CANopen optional communication card
All series
(Above S/W V10)
Common Specifications (External)
Keypad
Remote
Dynamic braking
Conduit option
Communication
option card
12

Industrial Drive for Fan and Pump STARVERT iP5A
Note 1) 5G is Common Ground for Analog Input / Output. (Only applied to 0.75 ~ 30kW products)
2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.
3) To add DC reactor, Remove DC Bus Choke and connect to P1(+), P2(+).
4) SA, SB terminal is proovided with 600V class model only.
Wiring
M1
M2
M3
M4
M5
M6
M7
M8
CM
Programmable Digital Input 1 (Speed L)
Programmable Digital Input 2 (Speed M)
Programmable Digital Input 3 (Speed H)
Fault Reset (RST)
Drive Disable (BX)
Jog Frequency Reference (JOG)
Forward Run Command (FX)
Reverse Run Command (RX)
Common Terminal
Analog Power Source (+12V)
Frequency Reference (0~12V, V1S: -12~12V)
Frequency Reference Common Terminal
Frequency Reference (0~20mA or 4~20mA)
Analog Power Source (-12V)
Fault Contact Output
less than AC250V (DC30V), 1A
Frequency Reference (Pulse: 0~100kHz)
Common for Frequency Reference (Pulse)
External Motor Thermal Detection
MCCB (Option)
R (L1)
S (L2)
T (L3)
G
U
V
W
Main Power Circuit Dynamic
Braking Unit
(Optional) DB Unit (Optional)
DB Resistor
DC Bus Choke
(Optional)
Control Circuit
DC Bus Choke DB Resistor
3Ø
AC Input
50/60 Hz
Motor
A1
C1
A2
C2
A3
C3
A4
C4
C-
C+
CM
NT
5G
A0
B0
5G
3A
3C
3B
S0
S1
5G
V+
V1
5G
I
V-
+
-
+
-
P1 (+)
P N B1 B2
P2 (+) N (-)
RS485 Signal
RS485 Common
Programmable Digital Output
Output Frequency Meter
Output Voltage Meter
Common for Output Meter Signal
For 0.75~30kW (1~40HP)
13
Drive Starvert iP5A Series

iP5AiP5A
Wiring
Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET). CM is Common Ground for Analog input.
2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.
3) To add DC reactor, remove DC Bus Choke and connect to P1(+), P2(+).
4) SA, SB terminal is provided with 600V class model only.
For 37~90kW (50~125HP) / 315~450kW (400~600HP)
M1
M2
M3
M4
M5
M6
M7
M8
CM
Programmable Digital Input 1 (Speed L)
Programmable Digital Input 2 (Speed M)
Programmable Digital Input 3 (Speed H)
Fault Reset (RST)
Drive Disable (BX)
Jog Frequency Reference (JOG)
Forward Run Command (FX)
Reverse Run Command (RX)
Common Terminal
Fault Contact Output
less than AC250V (DC30V), 1A
Frequency Reference (Pulse: 0~100kHz)
Common for Frequency Reference (Pulse)
External Motor Thermal Detection
MCCB (Option)
R (L1)
S (L2)
T (L3)
G
U
V
W
Main Power Circuit
Dynamic
Braking Unit
(Optional) DB Unit (Optional)
DB Resistor
DC Bus Choke
(Optional )
Control Circuit
DC Bus Choke DB Resistor
3Ø
AC Input
50/60 Hz
Motor
A1
C1
A2
C2
A3
C3
A4
C4
C-
C+
CM
ET
5G
A0
B0
CM
3A
3C
3B
S0
S1
5G
V+
V1
CM
I
V-
+
-
+
-
P1 (+)
P N B1 B2
P2 (+) N (-)
RS485 Signal
RS485 Common
Programmable Digital Output
Output Frequency Meter
Output Voltage Meter
Common for Output Meter Signal
Analog Power Source (+12V)
Frequency Reference (0~12V, V1S: -12~12V)
Frequency Reference Common Terminal
Frequency Reference (0~20mA or 4~20mA)
Analog Power Source (-12V)
14

Industrial Drive for Fan and Pump STARVERT iP5A
For 110~280kW (150~350HP)
M1
M2
M3
M4
M5
M6
M7
M8
CM
Programmable Digital Input 1 (Speed L)
Programmable Digital Input 2 (Speed M)
Programmable Digital Input 3 (Speed H)
Fault Reset (RST)
Drive Disable (BX)
Jog Frequency Reference (JOG)
Forward Run Command (FX)
Reverse Run Command (RX)
Common Terminal
Analog Power Source (+12V)
Frequency Reference (0~12V,V1S: -12~12V)
Frequency Reference Common Terminal
Frequency Reference (0~20mA or 4~20mA)
Analog Power Source (-12V)
Fault Contact Output
less than AC250V (DC30V), 1A
Frequency Reference (Pulse: 0~100kHz)
Common for Frequency Reference (Pulse)
External Motor Thermal Detection
MCCB (Option)
R (L1)
S (L2)
T (L3)
G
U
V
W
Main Power Circuit
Dynamic
Braking Unit
(Optional) DB Unit (Optional)
DB Resistor
DC Reactor (Built-in)
DB Resistor
3Ø
AC Input
50/60 Hz
Motor
A1
C1
A2
C2
A3
C3
A4
C4
C-
C+
CM
ET
5G
A0
B0
CM
3A
3C
3B
S0
S1
5G
V+
V1
CM
I
V-
+
-
+
-
P2 (+) N (-)
P N B1 B2
RS485 Signal
RS485 Common
Programmable Digital Output
Output Frequency Meter
Output Voltage Meter
Common for Output Meter Signal
Control Circuit
Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET). CM is Common Ground for Analog input.
2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.
3) DC Reactor is built basically in the inverters for 110~280kW(150~350HP)
4) SA, SB terminal is provided with 600V class model only.
15
Drive Starvert iP5A Series

iP5AiP5A
For 15~30kW (20~40HP) Built-in DCL Type
For 37~90kW (50~125HP) Built-in DCL Type
Wiring
Note) P1 (+) is not provided for wiring.
R (L1)
S (L2)
T (L3)
G
U
V
W
DC Reactor
DB Resistor
3Ø
AC Input
50/60 Hz
Motor
P (+)
P N B1 B2
N (-)
R (L1)
S (L2)
T (L3)
G
U
V
W
DC Reactor
DB Resistor
3Ø
AC Input
50/60 Hz
Motor
P1 (+)
P N B1 B2
P2 (+) N (-)
16

Industrial Drive for Fan and Pump STARVERT iP5A
Jumper
Jumper
Terminal Configurations (Power Circuit Terminal)
Symbol Description
R, S, T (L1, L2, L3) AC Line Voltage Input
G Earth Ground
P1 (+), P2 (+) External DC Reactor [P1 (+)-P2 (+)] Connection Terminals (Jumper must be removed).
P2 (+), N (-) or P (+), N (-) DB Unit [P2 (+)-N (-)] Connection Terminals
U, V, W 3 Phase Power Output Terminals to Motor
0.75~30kW (1~40HP) <200V/400V/600V Class>
37~90kW (50~125HP) / 315~450kW (400~600HP) <400V/600V Class>
R(L1)
(+) (+) (--)
(+) (+) (--)
S(L2)T(L3)G P1 P2 N U V W
R(L1)S(L2)T(L3)P1 P2 N U V W
15~18.5kW (20~25HP) <Built-in DC Reactor Type, 400V Class>
(+) (--)
R(L1)
G S(L2)T(L3)P N U V W G
22~30kW (30~40HP) <Built-in DC Reactor Type, 400V Class>
(+) (-)
R(L1)S(L2)T(L3)P N U V W
37~90kW (50~125HP) / 110 ~280kW (150~350HP) <Built-in DC Reactor Type, 400V Class>
(+) (--)
R(L1)S(L2)T(L3)P2 N U V W
Note) P1 (+) is not provided for wiring.
17
Drive Starvert iP5A Series

iP5AiP5A
Grounding
Terminal Configurations (Power Circuit Terminal)
Drive Capacity Grounding wire Sizes, AWG or kcmil (mm2)
kW HP 200V Class 400V Class 600V Class
5.5 ~ 7.5 7.5 ~ 10 10 (5.5) 12 (3.5) 14 (2.5)
11 ~ 15 15 ~ 20 6 (14) 8 (8) 12 (3.5)
18.5 ~ 30 25 ~ 40 4 (22) 6 (14) 8 (8)
37 ~ 55 50 ~ 75 - 4 (22) 6 (14)
75 ~ 90 100 ~ 125 - 2 (38) 4 (22)
110 ~ 132 150 ~ 200 - 1/0 (60) 2 (38)
160 ~ 280 250 ~ 350 - 4/0 (100)
315 ~ 375 400 ~ 600 - 300 (150)
450 700 - 400 (200)
* Apply the rated torque to terminal screws. * Loose screws can cause of short circuit or malfunction. Tightening the screw too much can damage the terminals and cause a short circuit or malfunction.
* Use copper wires only with 600V, 75℃ratings. For 7.5~11kW 240V type drives, R(L1), S(L2), T(L3) and U, V, W terminals are only for use with insulated ring type connector.
200V
Class
400V
Class
600V
Class
Wires & Terminal lugs
Refer to below for wires, terminal lugs, and screws used to connect the drive power input and output.
Wire size
Drive capacity Terminal Screw torque R(L1), S(L2), T(L3) U, V, W
screw size Kgf·cm Ib·in mm2AWG or mm2AWG or
kcmil kcmil
7.1 ~12.2 6.2 ~10.6 2.5 14 2.5 14
7.1 ~12.2 6.2 ~10.6 2.5 14 2.5 14
7.1 ~12.2 6.2 ~10.6 2.5 14 2.5 14
7.1 ~12.2 6.2 ~10.6 4 12 4 12
7.1 ~12.2 6.2~10.6 5.5 10 5.5 10
24.5 ~31.8 21.2~27.6 8 8 8 8
14 6 14 6
30.6 ~38.2 26.6~33.2 22 4 22 4
38 2 38 2
61.2 ~91.8 53.1~79.7 38 2 38 2
60 1/0 60 1/0
7.1 ~12.2 6.2 ~10.6 2.5 14 2.5 14
7.1 ~12.2 6.2 ~10.6 2.5 14 2.5 14
7.1 ~12.2 6.2 ~10.6 2.5 14 2.5 14
7.1 ~12.2 6.2 ~10.6 2.5 14 2.5 14
3.5 12 3.5 12
7.1 ~12.2 6.2~10.6 3.5 12 3.5 12
5.5 10 5.5 10
30.6~38.2 26.6~33.2 8 8 8 8
14 6 14 6
61.2~91.8 53.1~79.7 22 4 22 4
38 2 38 2
89.7~122.0 77.9~105.9 60 1/0 60 1/0
100 4/0 100 4/0
150 300 150 300
200 400 200 400
182.4~215.0 158.3~186.6 250 500 250 500
325 700 325 700
2×200 2×400 2×200 2×400
2×250 2×500 2×250 2×500
3.5 12 3.5 12
7.1 ~12.2 6.2~10.6 3.5 12 3.5 12
5.5 10 5.5 10
30.6~38.2 26.6~33.2
8 8 8 8
14 6 14 6
61.2~91.8 53.1~79.7 22 4 22 4
38 2 38 2
89.7~122.0 77.9~105.9 60 1/0 60 1/0
182.4~215.0 158.3~186.6 100 4/0 100 4/0
M4
M4
M4
M4
M4
M5
M5
M6
M6
M8
M8
M4
M4
M4
M4
M4
M4
M4
M6
M6
M8
M8
M10
M12
M12
M12
M12
M12
M12
M12
M4
M4
M4
M6
M6
M8
M8
M10
M12
0.75kW(1HP)
1.5kW(2HP)
2.2kW(3HP)
3.7kW(5HP)
5.5kW(7.5HP)
7.5kW(10HP)
11kW(15HP)
15kW(20HP)
18.5kW(25HP)
22kW(30HP)
30kW(40HP)
0.75kW(1HP)
1.5kW(2HP)
2.2kW(3HP)
3.7kW(5HP)
5.5kW(7.5HP)
7.5KW(10HP)
11 kW(15HP)
15 kW(20HP)
18.5kW(25HP)
22~30kW(30~40HP)
37~55kW(50~75HP)
75~90kW(100~125HP)
110~132kW(150~200HP)
160kW(250HP)
220kW(300HP)
280kW(350HP)
315kW(400HP)
375kW(500HP)
450kW(600HP)
5.5kW(7.5HP)
7.5KW(10HP)
11 kW(15HP)
15 kW(20HP)
18.5kW(25HP)
22~30kW(30~40HP)
37~55kW(50~75HP)
75~90kW(100~125HP)
110~132kW(150~200HP)
18

Industrial Drive for Fan and Pump STARVERT iP5A
Terminal Configurations (Control Circuit Terminal)
0.75~30kW / 1~40HP (200V/400V Class)
37~450 kW/50~600HP (400V Class)
3A 3C 3B A1 C1 A2 C2 A3 C3 A4 C4 M1 CM M2 M3 24 M4 M5 V+ V1 5G V- I NT
A0 B0 5G 5G S0 S1C+ CM C- M6 24 M7 M8
3A 3C 3B A1 C1 A2 C2 A3 C3 A4 C4 M1 CM M2 M3 24 M4 M5
C+ CM C- M6 24 M7 M8
V+ V1 CM V- 1 A0 B0
CM NC 5G 5G ET S0 S1
19
Drive Starvert iP5A Series

iP5AiP5A
Terminal Configurations (Control Circuit Terminal)
M1, M2, M3 Programmable
Digital Input 1, 2, 3
FX [M7] Forward Run
Command
RX [M8] Reverse Run
Command
JOG [M6] Jog Frequency
Starting Reference
Contact
Function BX [M5] Emergency Stop
Select
RST [M4] Fault Reset
CM Sequence Common
(NPN)
24 Sequence Common
(PNP)
V+, V- Analog Power Source
(+12V,-12V)
V1 Frequency Reference
(Voltage)
Analog I Frequency Reference
Frequency (Current)
Setting A0, B0 Frequency Reference
(Pulse)
5G (~30kW) Frequency Reference
CM (37kW~) Common Terminal
External NT (~30kW) External Motor
Motor Thermal ET (37kW~) Thermal Detection
Detection 5G Common for
NT (or ET)
C+, C- RS485 signal
High, Low
CM RS485 common
Programmable
Analog Output S0, S1, Voltage Output
5G
Analog Common Terminal
Fault Contact
3A, 3C, 3B Output
Contact
A1~4, C1~4 Programmable
Digital Output
Note) NC terminal is unavailable
Defines programmable digital inputs
(Factory setting : Multi-step frequency 1,2,3)
Forward run when closed and stopped when open
Reverse run when closed and stopped when open
Runs at jog frequency when the jog signal is on.
The direction is set by the FX (or RX) signal
When the BX signal is ON, the output of the drive is turned off.
When motor uses an electrical brake to stop, BX is used to turned off the output signal.
Take caution when BX signal is off (Not turned off by latching) and FX signal (or RX signal) is on.
Under these conditions, the motor will run!
Used for fault reset.
Common terminal for NPN contact.
Common 24V terminal for PNP contact input.
Maximum output : +24V, 100mA
Power supply for analog frequency setting.
Maximum output : +12V, 100mA, -12V, 100mA
Used by a DC 0~12V or -12~12V input to set the frequency reference.
(Input impedance is 20kΩ)
Used by a 0-20mA input to set the frequency reference.
(Input impedance is 249Ω)
Used by a pulse input to set the frequency reference.
Common terminal for analog frequency reference signal
Motor thermal sensor input. Used to prevent motor from overheating by using a NTC or
PTC thermal sensor.
Common terminal for external motor thermal detection
RS485 signal (See RS485 communication in manual for more details.)
Common ground. Terminal for RS485 interface.
Voltage output for one of the following : Output frequency, output current, output voltage, DC link voltage.
Default is set to output frequency.
(Maximum output voltage and output current are 0-12V and 1mA)
Common terminal for analog output (S0, S1)
Energizes when a fault is present. (AC250V, 1A; DC30V, 1A)
Fault : 3A-3C closed (3B-3C open)
Normal : 3B-3C Closed (3A-3C open)
Defined by programmable digital output terminal settings
(AC250V, 1A or less; DC30V, 1A or less)
Type Symbol Name Description
Input SignalOutput Signal
Built-in RS485 Terminal
20
Other manuals for iP5A
1
This manual suits for next models
8
Table of contents
Other LS DC Drive manuals
Popular DC Drive manuals by other brands

SEW-Eurodrive
SEW-Eurodrive BMG T Series operating instructions

DART Controls
DART Controls EZ VFD CONTROL Series instruction manual

INVT
INVT Goodrive200A Series Operation manual

Control Techniques
Control Techniques Unidrive M300 quick start guide

diytube
diytube Poseidon Driver Instructions for assembly and operation

WEG
WEG CFW100 series Programming manual