Lucent Technologies J85568E-1 User manual

Lineage®2000
Secondary DC Distribution Bay
(Mini-Distribution Bay)
J85568E-1
Product Manual
Select Code 157-005-102
Comcode 107098840
Issue 4
January 1999
©1999 Lucent Technologies


Product Manual
J85568E-1
Select Code 157-005-102
Comcode 107098840
Issue 4
January 1999
Lucent Technologies
Lineage®2000
Secondary DC Distribution Bay
(Mini-Distribution Bay)
Notice:
Every effort was made to ensure that the information in this
document was complete and accurate at the time of printing.
However, information is subject to change.
©1999 Lucent Technologies
All Rights Reserved
Printed in U.S.A.


Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999 Table of Contents - 1
Table of Contents
1 Introduction
General 1 - 1
Additional Information 1 - 1
Customer Training 1 - 2
Customer Service 1 - 2
Technical Support 1 - 2
Product Repair and Return 1 - 2
Warranty Service 1 - 2
2 Product Description
Overview 2 - 1
Features 2 - 1
Physical Specifications 2 - 2
3 Ordering Information
List Structure 3 - 1
Terminal Lugs 3 - 2
Bay Extenders 3 - 4
Sample Order 3 - 4
Documentation 3 - 4
4Safety
Admonishments 4 - 1
Safety Statements 4 - 1
Precautions 4 - 2
Warning Statements and Safety Symbols 4 - 3
Electrostatic Discharge (ESD) 4 - 5
5 Installation
Safety 5 - 1
Tools and Materials Required 5 - 1
Unpacking, Handling, and Frame Installation 5 - 2
Connecting Load and Distribution Cabling 5 - 5

Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999 List of Figures - 1
List of Figures
Figure 2-1: J85568E-1 Mini-Distribution Bay
(four fuse panels shown) 2 - 3
Figure 2-2: J85568E-1 Mini-Distribution Bay Factory
Installed in ED8C800-50 G5 Framework
(four fuse panels shown) 2 - 4
Figure 5-1: Typical Floor Mounting Detail 5 - 3
Figure 5-2: Floor Mounting Template 5 - 3
Figure 5-3: Rear View of Mini-Distribution Bay and
A/B Load Connections (four fuse panels shown) 5 - 4
Figure 5-4A: List C Fuse Panel for J85568E-1
Mini-Distribution Bay 5 - 7
Figure 5-4B: List D Circuit Breaker Panel for J85568E-1
Mini-Distribution Bay 5 - 8
Figure 5-5: Fuse Sizes and Ordering Comcodes for
Mini-Distribution Bay 5 - 8
Figure 5-6: Alarm Termination Board 5 - 11
Figure 5-7: Installation Information Label (Rear of
Mini-Distribution Bay) 5 - 12


Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999 List of Tables - 1
List of Tables
Table 3-A: J85568E-1 Mini-Distribution Bay
Ordering Information 3 - 1
Table 3-B: Recommended Double Hole Terminal Lugs
for Terminating Load Cables (750KCMIL Maximum) 3 - 3
Table 3-C: Recommended Double Hole Terminal Lugs
for Terminating to Discharge Return Bus or Frame
Ground 3 - 3
Table 3-D: Recommended Single Hole 90° Terminal Lugs
for Terminating to Fuse Block 3 - 3
Table 3-E: Recommended Single Hole Terminal Lugs
for Terminating to Circuit Breakers 3 - 4
Table 3-F: Bay Extenders 3 - 4
Table 5-A: DIP Switch Settings and Alarm Connections
for Generating Frame Alarms 5 - 11


Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999 Introduction 1 - 1
1 Introduction
General This product manual (Select Code 157-005-102) describes the
J85568E-1 Secondary DC Distribution Mini-Bay. This unit is
also known as a Mini-Battery Distribution Fuse Bay
(Mini-BDFB) or Mini-Battery Distribution Circuit Breaker Bay
(Mini-BDCBB). Complementing the 7-foot, 9-foot and
11.5-foot J85568C-1 series of DC Power Distribution Bays, the
Mini-BDFB/BDCBB is a fully assembled rack-mountable unit
that distributes -48 volt dc power in a two-load (A/B)
arrangement.
The Mini-Distribution Bay is a secondary fuse distribution
center for dc power delivered from a central office battery plant
to the using equipment. When floor space is minimized, the
Mini-Bay provides a cost-effective solution for distributing
power without sacrificing reliability or features. It is ideal for a
small central office or customer premise power system
application. It is also well suited for power transition or
modernization projects or for satisfying co-location
requirements for RBOCs to provide dc power access to
Inter-Exchange Carriers (IXCs).
Additional
Information Additional copies of this manual or any other Lucent
Technologies document may be obtained by calling Lucent
Technologies Customer Service at 1-800-THE-1PWR
(1-800-843-1797). Specify the code number for manuals or the
drawing numbers for drawings.

Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
1 - 2 Introduction Issue 4 January 1999
Customer
Training Lucent Technologies offers customer training on many Power
Systems products. For information call 1-972-284-2163. This
numberisansweredfrom 8:00a.m. until4:30p.m.,CentralTime
Zone (Zone 6), Monday through Friday.
Customer
Service Forcustomers in the United States,Canada, Puerto Rico, and the
US Virgin Islands, call 1-800-THE-1PWR (1-800-843-1797).
Services provided through this contact include initiating the
spare parts procurement process for out of service emergencies,
ordering Lucent Technologies documents, and providing other
product and service information.
For other customers worldwide, call 001-972-840-0382. This
numberis answeredfrom 8:00a.m. until4:30p.m.,CentralTime
Zone (Zone 6), Monday through Friday.
Technical
Support Technical support for Lucent Technologies customers is
available around the world during the normal product warranty
period and also while specific contractual agreements extend
this service.
For customers in the United States,Canada, Puerto Rico, and the
US Virgin Islands, call 1-800-CAL-RTAC (1-800-225-7822) to
contact a product specialist to answer your technical questions
and assist in troubleshooting problems.
For other customers worldwide, contact your local field support
center or your sales representative to discuss your specific needs.
Product Repair
and Return Repair and return service is provided for Lucent Technologies
customers around the world. For customers in the United States,
Canada, Puerto Rico, and the US Virgin Islands, call
1-800-255-1402 for information on returning of products for
repair.
For other customers worldwide, contact your sales
representative to discuss your particular circumstances.
Warranty
Service For warranty service worldwide, contact your Warranty Service
Manager (WSM). The WSM serves specific customer-groups,
who have taken ownership of the product. For product

Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999 Introduction 1 - 3
conformance issues prior to customer ownership, contact your
local customer service.


Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999 Product Description 2 - 1
2 Product Description
Overview TheJ85568E-1 Mini-DistributionBay (Power DistributionBay)
distributes -48Vdc power in a two-load arrangement, with a
300-ampere capacity per load. There are four fuse or circuit
breaker panel positions. Load Bus A connects the top two fuse
or circuit breaker panels. Load Bus B connects the bottom two
fuse or circuit breaker panels. All panel positions must be
equipped with either a fuse or circuit breaker panel or a blank
panel. Each fuse panel is equipped with twelve fuse blocks for
0-60A fuses. Each circuit breaker panel has 12 empty positions
for up to 12 circuit breakers.
This Mini-Distribution Bay is designed to mount in a 23-inch
relay rack. See Figure 2-1. It can also be factory installed in an
ED8C800-50
7′framework. See Figure 2-2. If the Mini-Distribution Bay is
installed in a 7′framework that will be located in a 9′or 11′-6″
environment, bay extenders are available. Ordering information
for the extenders is given in Section 3. Note: Do not mount
Mini-Distribution Bay onto bay extenders. Other equipment
can be added to this framework, which saves valuable floor
space.
The Mini-Distribution Bay offers the same fusing and alarm
monitoring features as the J85568C-series distribution bay, but
in a more compact design. It provides another Lucent
Technologies alternative to secondary distribution requirements.
Features The following is a list of features provided with this product:
• Fully assembled unit for simplified installation
• Lexan rear protective cover

Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
2 - 2 Product Description Issue 4 January 1999
• Internal 2-hole return bus
• Digital current meter
• Visual alarm indication per panel
– Red LED - Fuse Alarm
– Green LED - Power On
– GMT alarm fuse per fuse block
• Remote alarm indication
– (3) Form-C fuse or circuit breaker alarm contacts per
panel
– (1) Form-C power loss alarm contact per panel
– Switch selectable frame alarms
Physical
Specifications Height 33 inches (838mm)
84 inches (2134mm) in framework
Width 23.3 inches (592mm)
Depth 12 inches (305mm)
Weight 112 pounds (4 fuse or circuit breaker panels)
220 pounds in framework

Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999 Product Description 2 - 3
Figure 2-1: J85568E-1 Mini-Distribution Bay (four fuse panels shown)
Panel
Position
1
2
3
4
33.00
12.00
23.33
22.33
Central Office
White Color

Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
2 - 4 Product Description Issue 4 January 1999
Figure 2-2: J85568E-1 Mini-Distribution Bay Factory Installed in ED8C800-50 G5 Framework (four
fuse panels shown)
84.00
25.94
ED8C800-50 G5
Framework, List A
(Soft Blue Color)

Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999 Ordering Information 3 - 1
3 Ordering Information
List Structure Table 3-A describes the list structure of the J85568E-1
Mini-Distribution Bay. List 2 provides the assembly with four
empty panelpositions. Panel positions 1 and 3 must be equipped
with a fuse or circuit breaker panel to support bus bars. Panel
positions 2 and 4 must be equipped with either a List C fuse
panel, a List D circuit breaker panel or a List B blank panel.
If a relay rack is required, order List A and the factory will install
the Mini-Distribution Bay in a ED8C800-50 framework, as
shown in Figure 2-2.
Table 3-A: J85568E-1 Mini-Distribution Bay Ordering
Information
Description List
Assembly, wiring, and equipment for one 33-inch
-48V battery distribution unit for mounting in a
23-inch relay rack. Provides one meter and alarm
termination panel and space for four fuse or circuit
breaker panels in a two-load (A/B) arrangement.
Optional equipment in addition to List 2 for a
23-inch relay rack mounted in a ED8C800-50 G5
framework (soft blue finish).
Optional equipment in addition to List 2 for a blank
panel for panel positions two or four.
Optional equipment in addition to List 2 for a fuse
panel equipped with 12 fuse blocks for 3-60A fuses.
Optional equipment in addition to List 2 for a circuit
breaker panel to hold up to 12 circuit breakers.
2
A
B
C
D

Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
3 - 2 Ordering Information Issue 4 January 1999
1. The engineer must furnish all terminal lugs for load and
return leads. Hardware for terminating load leads, load
return leads, input battery and return cabling, and frame
ground is provided with List 2.
2. This Mini-Distribution Bay is configured with two load
buses. Load Bus A connects the top two fuse or circuit
breaker panels. Load Bus B connects the bottom two fuse
or circuit breaker panels. Battery cabling is connected to
each load bus at the top of the unit. A 300A shunt and bus
bar assembly connects battery cabling to each fuse or
circuit breaker panel as required.
3. A digital meter and switch assembly is provided with List
2 in accordance with ED83127-30 Group 14 to monitor the
300A shunts associated with each load.
4. This Mini-Distribution Bay is recommended for top load
feed applications. When bottom load feed is required, the
J85568C-1 bay is recommended because it provides for
cable routing to the floor.
Terminal Lugs Table 3-B lists recommended terminal lugs for different cable
sizes. Hardware for terminating the terminal lugs is provided
with the Mini-Distribution Bay. Recommended torque for these
connections is 260 in. lbs.
Refer to Table 3-C for recommended terminal lugs for the frame
ground connection. Hardware for connecting the frame ground
is furnished with the Mini-Distribution Bay.
Table 3-D provides recommended terminal lugs for terminating
to the fuse block for List C.
Table 3-D provides recommended terminal lugs for terminating
to the circuit breakers for List D.
The information in these tables is also given on a label on the
back of the Mini-Distribution Bay. The label is replicated in
Figure 5-7.