manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. Power Supply
  8. •
  9. M-system M3DY User manual

M-system M3DY User manual

Other M-system Power Supply manuals

M-system Current Loop Supply M3LDY User manual

M-system

M-system Current Loop Supply M3LDY User manual

M-system MDC6 User manual

M-system

M-system MDC6 User manual

M-system W2DYH User manual

M-system

M-system W2DYH User manual

M-system M5DY User manual

M-system

M-system M5DY User manual

M-system Mini-M M2DYS User manual

M-system

M-system Mini-M M2DYS User manual

M-system R5-PS1 User manual

M-system

M-system R5-PS1 User manual

M-system JPS3 User manual

M-system

M-system JPS3 User manual

M-system R3Y-SS16N User manual

M-system

M-system R3Y-SS16N User manual

M-system R3-PS3 User manual

M-system

M-system R3-PS3 User manual

M-system M6SDY User manual

M-system

M-system M6SDY User manual

M-system MDC User manual

M-system

M-system MDC User manual

M-system 10DYH2 User manual

M-system

M-system 10DYH2 User manual

M-system W2DYH2 User manual

M-system

M-system W2DYH2 User manual

M-system 18KDY User manual

M-system

M-system 18KDY User manual

M-system M5DY-5-M User manual

M-system

M-system M5DY-5-M User manual

M-system KWDNY User manual

M-system

M-system KWDNY User manual

M-system ABF3 User manual

M-system

M-system ABF3 User manual

M-system Current Loop Supply M3LDY User manual

M-system

M-system Current Loop Supply M3LDY User manual

M-system 18DU User manual

M-system

M-system 18DU User manual

M-system 18DY User manual

M-system

M-system 18DY User manual

M-system DS User manual

M-system

M-system DS User manual

M-system 10DNY User manual

M-system

M-system 10DNY User manual

M-system R3-PS1 User manual

M-system

M-system R3-PS1 User manual

M-system 10DU User manual

M-system

M-system 10DU User manual

Popular Power Supply manuals by other brands

Videx 520MR Installation instruction

Videx

Videx 520MR Installation instruction

Poppstar 1008821 Instructions for use

Poppstar

Poppstar 1008821 Instructions for use

TDK-Lambda LZS-A1000-3 Installation, operation and maintenance manual

TDK-Lambda

TDK-Lambda LZS-A1000-3 Installation, operation and maintenance manual

TDK-Lambda 500A instruction manual

TDK-Lambda

TDK-Lambda 500A instruction manual

Calira EVS 17/07-DS/IU operating instructions

Calira

Calira EVS 17/07-DS/IU operating instructions

Monacor PS-12CCD instruction manual

Monacor

Monacor PS-12CCD instruction manual

VOLTIMA MagicBox 15 Installation and operating instructions

VOLTIMA

VOLTIMA MagicBox 15 Installation and operating instructions

Miller Auto Deltaweld 452 owner's manual

Miller

Miller Auto Deltaweld 452 owner's manual

BCP PUOUBK How to install

BCP

BCP PUOUBK How to install

HC 2210 manual

HC

HC 2210 manual

Agilent Technologies 6032A Service manual

Agilent Technologies

Agilent Technologies 6032A Service manual

Radial Engineering SB-48UB user guide

Radial Engineering

Radial Engineering SB-48UB user guide

Puls CT5.241 installation manual

Puls

Puls CT5.241 installation manual

OCZ ZX1250W Technical specifications

OCZ

OCZ ZX1250W Technical specifications

iseg ECH 238 manual

iseg

iseg ECH 238 manual

Agilent Technologies 6631B Service manual

Agilent Technologies

Agilent Technologies 6631B Service manual

Power XXL A Series instruction manual

Power

Power XXL A Series instruction manual

HP 6200B Operating and service manual

HP

HP 6200B Operating and service manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-2666 Rev.2 P. 1 / 3
INSTRUCTION MANUAL
CURRENT LOOP SUPPLY MODEL M3DY
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
•This equipment is suitable for Pollution Degree 2 and In-
stallation Category II (transient voltage 2500V). Rein-
forced insulation (signal input or output to power input:
300V) and basic insulation (signal input to output: 300V)
are maintained. Prior to installation, check that the insu-
lation class of this unit satisfies the system requirements.
•Altitude up to 2000 meters.
•The equipment must be mounted inside a panel.
•The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
•The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
•Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 90 – 264V, 47 – 66 Hz, approx. 3 – 5VA
24V DC rating: 24V ±10%, approx. 2W
24 – 240V DC rating: 21.6 – 264V, approx. 2W
■GENERAL PRECAUTION
•Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -20 to +55°C
(-4 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
•Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
•The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
•With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to
endure it without breakdown, however, it may shorten ap-
propriate life duration.
COMPONENT IDENTIFICATION
Specifications
(side)
Body
Power LED
ZERO Adj
SPAN Adj
■HOW TO SEPARATE THE EURO TYPE CONNECTOR
TERMINAL BLOCKS
When you need to separate the euro type connector termi-
nal blocks from the transmitter body for wiring, insert a mi-
nus driver between the euro type connector terminal block
and the housing body, pull up the driver and pull out the
euro type connector terminal block.
M3DY
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-2666 Rev.2 P. 2 / 3
INSTALLATION
■DIN RAIL MOUNTING
Set the unit so that its DIN rail adaptor is at the bottom.
Position the upper hook at the rear side of the unit on the
DIN rail and push in the lower. When removing the unit,
push down the DIN rail adaptor utilizing a minus screw-
driver and pull.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
10 11 12
456
123
789
106 (4.17)
18 (.71) 110.5 (4.35)
62 (2.44)
[5 (.20)]
DIN RAIL
35mm wide
• When mounting, no extra space is needed between units.
■CONNECTION DIAGRAM
+
–
OUTPUT
7
8
11
12
POWER
+
–
1
2
4
5
+
–
2-WIRE
TRANSMITTER
+
–
–
+
V
MONITOR
■ When Used as DC Supply ■ When Used as Isolator
4
1
5
2250Ω
+
–
+
–
2-WIRE
TRANSMITTER
+
–
4
1
5
2250Ω
+
–
+
–
INPUT
U (+)
V (–)
1
-
5 V DC
M3DY
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-2666 Rev.2 P. 3 / 3
■WIRING INSTRUCTIONS
 •Applicablewiresize
Solid: 0.2 to 2.5 mm2(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm2
Tinning wire ends may cause contact failure
and therefore is not recommended.
Ferruled: 0.2 to 1.5 mm2(0.55 to 1.35 dia.)
The following Phoenix Contact terminals are
recommended:
AI 0,25-8YE 0.2 to 0.25 mm2
AI 0,34-8TQ 0.25 to 0.34 mm2
AI 0,5-8WH 0.34 to 0.5 mm2
AI 0,75-8GY 0.5 to 0.75 mm2
AI 1,0-8RD 0.75 to 1.0 mm2
AI 1,5-8BK 1.0 to 1.5 mm2
 •Exposewireconductorsby8mm(0.31”).
8 mm 8 mm
4 mm dia.
max.
4 mm dia.
max.
Wire exposure Recommended
ferruled wire
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
11 – 12 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENTPROCEDURE”explainedearlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.