manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. Transducer
  8. •
  9. M-system TPV User manual

M-system TPV User manual

Other M-system Transducer manuals

M-system L3PK User manual

M-system

M-system L3PK User manual

M-system LTWTN User manual

M-system

M-system LTWTN User manual

M-system W2PV User manual

M-system

M-system W2PV User manual

M-system BPV User manual

M-system

M-system BPV User manual

M-system 18PA User manual

M-system

M-system 18PA User manual

M-system Mini-M M2PV User manual

M-system

M-system Mini-M M2PV User manual

M-system 18PF User manual

M-system

M-system 18PF User manual

M-system M5XWTU User manual

M-system

M-system M5XWTU User manual

M-system 18HZ User manual

M-system

M-system 18HZ User manual

M-system LWT User manual

M-system

M-system LWT User manual

M-system LTHZ User manual

M-system

M-system LTHZ User manual

M-system LT-UNIT Series User manual

M-system

M-system LT-UNIT Series User manual

M-system LTCE User manual

M-system

M-system LTCE User manual

M-system LTCE User manual

M-system

M-system LTCE User manual

M-system L2CA User manual

M-system

M-system L2CA User manual

M-system LECA User manual

M-system

M-system LECA User manual

M-system L2PA User manual

M-system

M-system L2PA User manual

M-system HVPN User manual

M-system

M-system HVPN User manual

M-system LTCNE User manual

M-system

M-system LTCNE User manual

M-system LT-UNIT Series User manual

M-system

M-system LT-UNIT Series User manual

M-system 18RP User manual

M-system

M-system 18RP User manual

M-system KUWEN User manual

M-system

M-system KUWEN User manual

M-system L3CK User manual

M-system

M-system L3CK User manual

M-system PV User manual

M-system

M-system PV User manual

Popular Transducer manuals by other brands

LEM DK series installation guide

LEM

LEM DK series installation guide

HBM AD101B quick start guide

HBM

HBM AD101B quick start guide

Camille Bauer SINEAX F534 operating instructions

Camille Bauer

Camille Bauer SINEAX F534 operating instructions

Trane KIT 16724 Installer's guide

Trane

Trane KIT 16724 Installer's guide

Lumel P18 user manual

Lumel

Lumel P18 user manual

B&C Speakers DE75PTN datasheet

B&C Speakers

B&C Speakers DE75PTN datasheet

Mianyang Weibo Electronic WB Series user manual

Mianyang Weibo Electronic

Mianyang Weibo Electronic WB Series user manual

ProMinent Dulcometer DMT operating instructions

ProMinent

ProMinent Dulcometer DMT operating instructions

Camille Bauer SIRAX CH-5610 operating instructions

Camille Bauer

Camille Bauer SIRAX CH-5610 operating instructions

Veris Industries PW Series installation guide

Veris Industries

Veris Industries PW Series installation guide

HBM TJ1-S6 installation manual

HBM

HBM TJ1-S6 installation manual

Simrad ES120-7C -  REV D Dimensions

Simrad

Simrad ES120-7C - REV D Dimensions

HBM C18 Mounting instructions

HBM

HBM C18 Mounting instructions

Spirax Sarco ITV1030 Installation and maintenance instructions

Spirax Sarco

Spirax Sarco ITV1030 Installation and maintenance instructions

MAMAC SYSTEMS PR-243 technical information

MAMAC SYSTEMS

MAMAC SYSTEMS PR-243 technical information

Balluff BTL5-P user guide

Balluff

Balluff BTL5-P user guide

MKS MicroPirani 925 Series Short form manual

MKS

MKS MicroPirani 925 Series Short form manual

WIKA WU-20 operating instructions

WIKA

WIKA WU-20 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-3220 Rev.6 P. 1 / 3
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +60°C
(23 to 140°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
EURO Type
Terminals
ZERO
SPAN
Body
Specifications/
Connection Diagram
Zero Adj.
Span Adj.
INSTALLATION
Refer to “EXTERNAL DIMENSIONS.”
P/I TRANSDUCER MODEL TPV
TPV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-3220 Rev.6 P. 2 / 3
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
Ground the screw terminal at the bottom for RFI protection if necessary. When grounded, dielectric strength between output
signal line and ground is of 50V DC, though it is of 500V AC when not grounded.
■EXTERNAL DIMENSIONS unit: mm [inch]
18 [.70]
19 [.75]
25 [.98]
53 [2.08]
60 [2.36]
60 [2.36]
13
[.51]
75 [2.95]
PNEUMATIC
CONNECTION
Rc 1/4” or 1/4” NPT
PNEUMATIC
CONNECTION
Rc 1/4” or 1/4” NPT
EURO TYPE
TERMINALS
EURO TYPE
TERMINALS
2 – 4.4 [.17] dia.
MTG HOLE
NPT FITTING*1
NPT FITTING*1
approx.
27 [1.06]
M4 [.16] SCREW
M4 [.16] SCREW
1
2
3
4
•When mounting, no extra space is needed between units.
60 [2.36]
92.9
approx.
27 [1.06]
■DIN RAIL TYPE
■SURFACE MOUNT TYPE
19 [.75]
25 [.98]
100 [3.94]
60 [2.36]
4[.16]
17.9 [.70]
(3.3[.13])
DIN RAIL
35mm wide
*Fitting provided for 1/4” NPT connection.
*Fitting provided for 1/4” NPT connection.
1
2
3
4
■CONNECTION DIAGRAM
3
4
+
mA
MONITOR
+
–
+
–
LOAD
1
2
OUTPUT
24V DC
4 – 20mA DC
–
PNEUMATIC
INPUT
TPV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-3220 Rev.6 P. 3 / 3
WIRING INSTRUCTIONS
■EURO TYPE TERMINAL
Applicable wire size: 0.25 – 1.5 mm2
Stripped length: 7 mm
PIPING
The pneumatic inlet is female screwed of Rc 1/4” (1/4” NPT
optional with a fitting). Tightening torque is at the maxi-
mum of 12 N·m. Check that there is no air leak at the con-
nection after sealing it.
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check that there is no air leak at the pneumatic
connection.
3) Output: Check that the load is within the permissible
limit including wiring resistance.
Load Resistance (Ω) = Supply Voltage (V) – 12 (V)
0.02 (A)
(including leadwire resistance)
4) When you check the output signal, connect an ammeter
of which the internal resistance is of 10Ω max. to the
monitor terminals.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.