MAKELSAN POWERPACK PLUS SERIES User manual

s
www.makelsan.com.tr
USER M ANU A L
UNINTERRUPTIBLE POWER SUPPLIES
ONLINE U P S
POWERPACK PLUS SERIES
1-2-3 kVA

Foreword
Manual instruction
Thanks for purchasing our UPS, it is safe and reliable, so few maintenance is required.
Read this manual carefully and completely. It includes instructions of safety installation
and operation. They will help your UPS obtain the longest life and service. This manual
accounts the internal working principle and the relative protection functions. This manual
also contains information about the usage of the equipment.
Please obey the instructions and all the warning stated in the manual or on the machine.
Don’t operate the machine before finishing reading the safety and operation instructions.
Note: Because of the continuous improvements, our products may differ somewhat from the
contents included in this manual. You can contact local office to get the information when
necessary.

Content
1.Safety instruction .......................................................................................................... 1
1.1 Safety instruction................................................................................................... 1
1.2 Symbols indication ................................................................................................ 1
2.Product Introduction...................................................................................................... 3
2.1 The appearance of the product ............................................................................. 3
2.2 The principle of the product................................................................................... 4
2.3 Model .................................................................................................................... 4
3.Installation..................................................................................................................... 5
3.1 Unpacking and inspection ..................................................................................... 5
3.2 Notes..................................................................................................................... 5
3.3 UPS input connection............................................................................................ 5
3.4 UPS output connection ......................................................................................... 6
3.5 Long backup external battery connection.............................................................. 6
4.Panel display, operation and running ............................................................................ 8
4.1 Faceplate display illumination ............................................................................... 8
4.2 Operation ............................................................................................................ 11
4.3 Parameter setting................................................................................................ 12
4.4 Parameters inquiring ........................................................................................... 20
4.5 Run mode ........................................................................................................... 22
5.Maintenance ............................................................................................................... 25
6.Troubleshooting and performance of product ............................................................. 26
6.1 LED indication and warning table........................................................................ 26
6.2 Troubleshooting .................................................................................................. 28
6.3 EMC standard/Safety standard ........................................................................... 29
6.4 Product Performance .......................................................................................... 29
6.5 Communication interface .................................................................................... 30

1
1. Safety instruction
Abstract
This chapter mainly introduce the safety marks and notes of 1KVA-3KVA series on-line
UPS. Read this chapter carefully before operating on the equipment.
1.1 Safety instruction
There is dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions and
relative laws, otherwise it will result in personnel injury or equipment damage. Safety
instructions in this manual act as a supplementary for the local safety instructions.
Our company will not assume the liability that caused by disobey of safety instructions.
Please note the following:
1. Don’t use the UPS when the actual load exceeds the rated load.
2. There are high-capacity batteries in the standard type UPS. You mustn’t open the
enclosure or it will lead to electric shock. If it needs internal maintenance or battery
replacement, please send it to the designated site.
3. Internal short-circuit of the UPS will cause electric shock or fire. So don’t place the
containers equipped with liquid on the top of the UPS so as not to cause danger of
electric shock and so on.
4. Don’t put the UPS in a place with high temperature or humidity as well as the
corrosive gas, much dust.
5. Keep good air circulation between in-vent on front panel and out-vent on back
panel.
6. Avoid direct sunlight or near heat-dispensed objects.
7. In case that the smoke appears on the UPS, please cut off the power as soon as
possible and contact the dealer service site.
1.2 Symbols indication
The safety symbols cited in this manual are shown in table 1-1, which are used to
inform readers of safety issues that should be obeyed when installation, operation and
maintenance.

2
Safety Symbol Indication
Attention
Static discharge sensitive
Electric shock
There are three levers of safety grade: Dangerous, Warning and Attention. The remark
is on the right side of the safety symbol, the detailed comments is behind, shown as
following:
Dangerous
Indicate risk of serious injury or death or seriously damage the equipment
Warning:
Indicate risk of serious injury or damage the equipment.
Attention:
Indicate risk of injury or damage the equipment.

3
2. Product Introduction
2.1 The appearance of the product
FIG.1 Front Panel view
FIG.2 1kVA Rear Panel view

4
FIG.3 2/3kVA Rear Panel view
2.2 The principle of the product
FIG.4 UPS Principle Diagram
1.Input filter: Complete filtering the input AC utility power to provide the clean power
for UPS.
2. AC/DC converter: Convert the filtered AC mains to DC and boost the DC for DC/AC
inverter.
3. DC/DC booster: When the UPS works in battery mode, the circuit boosts the DC for
DC/AC inverter.
4. DC/AC inverter: Convert the boosted DC to stable AC output.
5. Bypass: When overload or failure of inverting happen in the UPS, it transfers to
bypass mode to supply power to loads.
6. Charger: Standard unit provides 1A.
7. Battery: Sealed Lead Acid Battery.
8. Output filter: Complete filtering the output of the UPS to provide the clean power for
loads.
2.3 Model
UPS sort MODEL NO Remark
Standard
unit
1KVAS Internal 1A charger, 2 PCS 9AH batteries
1KVAH Internal 6A charger, 2 PCS batteries
2KVAS Internal 1A charger, 4 PCS 9AH batteries
2KVAH Internal 6A charger, 4 PCS batteries
3KVAS Internal 1A charger, 6 PCS 9AH batteries
3KVAH Internal 6 charger, 6 PCS batteries

5
3. Installation
3.1 Unpacking and inspection
1. Unpacking the UPS and check that whether it’s damaged during the
transportation. If damaged or some parts missing, don’t start the
machine and inform the carrier and franchiser.
2. Check the annex (please consult Appendix Table 1).
3. Check if the equipment is just what you wanted to purchase. You can affirm through
inspecting the model number on back panel of the equipment.
3.2 Notes
1. Please place the UPS in a clean, stable environment, avoid the vibration, dust, too
humidity, flammable gas and liquid, corrosive.
2. The ambient temperature around UPS should keep in a range of 0℃~40℃. If UPS
works above 40℃, it is required that the rated value of the largest load decreases
12%while the temperature increases every 5℃. The highest temperature cannot
be more than 50℃when UPS works.
3. UPS should be placed in a sufficiently ventilated place.
3.3 UPS input connection
Connect the UPS to the mains by input power cable which is equipped
with the UPS.

6
FIG.5 Input Connection
3.4 UPS output connection
FIG.6 Output connection
3.5 To install the optional EBP(s) for a UPS(Standard unit):

7
3.6 Long backup external battery connection
FIG.7 battery connection
Warning:
★Before installing battery, make sure that UPS and breaker are all turned off. Remove
all your metallic adornment such as finger ring, watch, and so on before connecting
battery.
★No anti-connection or short circuit between the battery anode and cathode forever.
Red cable connect with battery anode “+” and black cable connect with cathode “-”.
★Please use the screwdriver with insulating handle. Do not lay the tools or metallic
goods on the battery.
Notice:
★When using the external battery, It is best to use external battery cable which
matches with the equipment.
★When connecting load to UPS, first turn off load and then connect the power cable
and finally turn on load one-by-one.
★Inductance loads such as motor, fluorescent lamp, photocopier are strictly prohibited
connecting to UPS to avoid damage.
★Plug UPS on the special socket with over-current protection, the power socket that
used should be connected with ground wire.
★UPS is likely to have output voltage no matter whether the power input cable is
plugged in mains input socket. If you wish UPS have no output, first break off the
switch and then cancel the mains.
★When connect laser printer, select the capacity of UPS according to the UPS start
power because the startup power is higher.

8
4. Panel display, operation and running
The operation is simple, operators only need to read the manual and
follow the operation instructions listed in this manual without any special training.
4.1 Faceplate display illumination
4.1.1 Keys function
FIG.8 front panel buttons instruction
ON key (+ )
Press and hold this key for more than half a second to turn on the UPS.
OFF key (+ )
Press and hold this key for more than half a second to turn off the UPS.
TEST/MUTE key (+ )
Press and hold the key for more than 1 second in Line mode or economical mode:
UPS runs the self-test function.
Press and hold the key for more than 1 second in battery mode: UPS runs the mute
function.
INQUIRING key or
Non-function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Indicate the
items of the LCD item section orderly.

9
Press and hold this key for more than 2 seconds: Circularly and orderly display the
items every 2 seconds, when press and hold the key for some time again, it will turn to
output status.
Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Select the
set option.
Function setting key
Non-function setting mode:
Press and hold the key for more than 2 seconds: Function setting interface.
Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Affirm the
set option.
Press and hold the key for more than 2 seconds, exit from this function setting
interface.
4.1.2 The function of LED indicators
Warning red LED is on: UPS is fault. For example: Overload beyond the allowed time,
inverter fault, BUS fault, over temperature fault etc.
Bypass yellow LED is on: UPS is alarming. For example: Bypass mode supply power
and etc.
Battery yellow LED is on: UPS is alarming. For example: Battery mode supply power
and etc.
Inverter green LED is on: UPS is normally powered by mains or ECO mode or battery
mode.
After starting the UPS, the four LEDs will light and go out one-by-one. It circulates
several times until starting the UPS successful.

10
NOTE: As to the LED indication in different modes, please refer to the LED display
panel and warning table.
4.1.3 LCD display functions
The LCD displays as following Fig.
LCD display comprises numerical value section, capacity graphics section, fan-status
graphics section and charger-status graphics section.
Numerical value section-display the corresponding numerical value of inquiring
items(output, load, temperature, input, battery), for example, as the graphics shows
above, the output voltage is 230v, the output frequency is 50Hz.
Capacity graphics section-display the capacity of the battery and load. Every pane
represents 20%capacity. As graphics shown above, the load reaches 80%-100%( 5
panes), the capacity of the battery is 40%-60%(3 panes). When UPS is overload, the
icon will flash, when capacity of battery is too low or disconnected, the icon will also
flash.
Fan-status graphics section-display if the fan works normally. When the fan works
normally, it will show the dynamic fan blades rotating; when the fan works abnormally,
the icon will keep on flashing with the warning .
Charger-status graphics section-display the status of the charger. When charger
works normally, the corresponding icon will vary dynamically and orderly, just as
Graphics (1);
(1)

11
when charger works abnormally, the icon will flash in a whole, as Graphics(2):
(2 )
When UPS is in battery mode, the number of the icons of the charger-state section will
vary according to the changeable capacity of the battery (pane). For example, there
are five panes in Fig.A,(as the right picture of the Graphics(3) shows), so the
corresponding number of icons is five rows(as the left picture of the Graphics(3)
shows),, followed by this rule,
(3 )
4.2 Operation
4.2.1 Start up operation
Turn on the UPS in line mode
①Once mains power is plugged in, the UPS will charge the battery, at the moment,
LCD shows that the output voltage is 0, which means UPS has no output. If it is
expected to have output of bypass, you can set the bps “ON” by LCD setting menu.
②Press and hold the ON key for more than half a second to start the UPS, then it
will start the inverter.
③Once started, the UPS will perform a self-test function, LED will light and go out
circularly and orderly. When self-test finishes, it will come to line mode, the
corresponding LED lights, UPS is working in line mode.
Turn on the UPS by DC without mains power
①When mains power is disconnected, press and hold the ON key for more than half
a second to start UPS.
②The operation of UPS in the process of start is almost the same as that when
mains power is in. After finishing the self-test, the corresponding LED lights and UPS
is working in battery mode.

12
4.2.2 Turn off operation
Turn off the UPS in line mode
①Press and hold the OFF key for more than half a second to turn off the UPS and
inverter.
②After UPS shutting down, LED go out and there is no output. If output is needed,
you can set bps “ON” on LCD setting menu.
Turn off the UPS by DC without mains power
①Press and hold the OFF key for more than half a second to turn off the UPS.
②When turning off the UPS, it will do self-testing firstly. LED light and go out
circularly and orderly until there is no display on the panel.
4.2.3 UPS self-test/mute test operation.
①When UPS is in line mode, press and hold the self-test/mute key for more than 1
second, LEDs light and go out circularly and orderly. UPS comes to self-test mode and
tests its status. It will exit automatically after finishing testing, LED resume.
②When UPS is in battery mode, press and hold the self-test/mute key for more than
1 second, the buzzer stops beeping. If you press and hold the self-test/mute key for
one more second, it will restart to beep again.
4.3 Parameter setting
UPS has setting function. It can run the setting on any mode. After setting, it will
become effective at once when meets some standards. The set information can be
saved only when the battery connected and normally turning off the UPS.
The operation of setting is as following:
4.3.1 ECO mode setting(1)
①Enter the setting interface. Press and hold the function setting key for more
than 2 seconds, then come to setting interface, the letters “ECO” will flash
②Enter the ECO setting interface. Press and hold the function setting key for
more than half a second(less than 2 seconds), then come to setting interface of ECO,
at this time, the letters “ECO” will light for a long time. The “ON”(or OFF) below the
ECO will flash. Press and hold the inquiring key for more than half a second (less
than 2 seconds) to determine whether the ECO function is used or not. If used, the
corresponding word is “ON”, if not, the word is “OFF”. It can be determined by
yourself.

13
③Confirm the ECO selecting interface. After selecting ON or OFF, press and hold
the function setting key for more than half a second (less than 2 seconds). Now, the
ECO setting function is completed and the “ON” or “OFF” below the “ECO” will light
without flash.
④Set the ECO tolerance range. Short press the scroll key or for more than half a
second (shorter than 2 seconds)to select the voltage range in percentage.
+5%,+10%,+15%,+25%(default is +25%),then short press function setting key
for more than half a second (shorter than 2 seconds)to confirm the selection, then to
set the minus range
⑤To set the minus range in the same way.
⑥Exit from the setting interface. Press and hold function setting key for more
than 2 seconds, exit from the setting interface and turn to main interface.
4.3.2 Bypass mode setting(2)
①Enter the setting interface. Press and hold the function setting key for more than
2 seconds, then come to setting interface, Press and hold the function setting
key for more than half a second(less than 2 seconds), select the function setting,
choose the bypass output interface, at the moment, the letters “bPS” will flash
②Enter the Bypass output selecting interface. Press and hold the function setting
key for more than half a second(less than 2 seconds), then come to setting
interface of bPS, at this time, the letters “bPS” will light for a long time. The “ON”

14
below the bPS will flash. Press and hold the inquiring key for more than half a
second (less than 2 seconds) to determine whether the bPS function is used or not. If
used, the corresponding word is “ON”, if not, the word is “OFF”. It can be determined
by yourself.
③Confirm the Bypass output selecting interface. After selecting ON or OFF, press and
hold the function setting key for more than half a second (less than 2 seconds),
Now, the bPS setting function is completed and the “ON” or “OFF” below the “bPS” will
light without flash.
④Set the BPS tolerance range. Short press the scroll key or for more than half
a second (shorter than 2 seconds)to select the voltage range in percentage.
+5%,+10%,+15%,+25%(default is +25%),then short press function setting key
for more than half a second (shorter than 2 seconds)to confirm the selection,
then to set the minus range
⑤To set the minus range in the same way.
④Exit from the setting interface. Press and hold function setting key for more than
2 seconds, exit from the setting interface and return to main interface.
⑤After setting bPS as ON, when mains power plugged in without turning on the
UPS or no mains power plugged in, there is bypass output but no power down backup
function.
4.3.3 Output voltage setting(3)
①Enter the setting interface. Press and hold the function setting key for more
than 2 seconds, then come to setting interface, Press and hold the inquiring key for
more than half a second(less than 2 seconds), select the function setting, choose
output voltage setting interface, at the moment, the letters “OPU” will flash
②Enter the output voltage selecting interface. Press and hold the function setting
key for more than half a second(less than 2 seconds), then come to setting
interface of output voltage OPU, at this time, the letters “OPU” will light for a long time.

15
The numerical value below the OPU will flash. Press and hold the inquiring key for
more than half a second (less than 2 seconds), select the numerical value in
accordance with “OPU” function. The provided voltages are 208V,220V, 230V, 240V
you can choose anyone by yourself (The default is 220v).
③Confirm the output voltage selecting interface. After selecting numerical value,
press and hold the function setting key for more than half a second (less than 2
seconds). Now, the OPU setting function is completed and the numerical value below
the “OPU” will light without flash.
④Exit from the setting interface. Press and hold function setting key for more
than half a second (less than 2 seconds), exit from the setting interface and return to
main interface.
NOTE:When setting the output voltage, you’d better cut off the load of the UPS first.
4.3.4 Battery Pack (EBP) number and type setting(4)
①Enter the setting interface. Press and hold the function setting key for more than
2 seconds, then come to setting interface, Press and hold the scroll key for
more than half a second(less than 2 seconds), select the function setting, choose
battery setting interface, at the moment, the letters “bAt” will flash.
②Enter the battery setting interface. Press and hold the function setting key for
more than half a second(less than 2 seconds), then come to setting interface of
battery, the letters “bAt” will stop flashing. The numerical value below the “bAt” will
flash. Press and hold the scroll key for more than half a second (less than 2
seconds), select the numerical value in accordance with the real connected battery
packs.
③Confirm the battery packs setting interface。

16
After selecting numerical value, press and hold the function setting key for more
than half a second (less than 2 seconds). Now, the battery packs setting is confirmed
and the battery type value below will flash。
④set the battery type in the same way.
⑤Exit from the setting interface. Press and hold function setting key for more than
half a second (less than 2 seconds), exit from the setting interface and return to
main interface.
4.3.5 Load segment setting(5)
①
Enter the setting interface. Press and hold the function setting key for more
than 2 seconds, then come to setting interface, Press and hold the scroll key for
more than half a second(less than 2 seconds), select the function setting, choose
battery setting interface, at the moment, the letters “Seg 1” will flash.
②Enter the load segment setting interface. Press and hold the function setting
key for more than half a second(less than 2 seconds), then come to setting
interface of load segment, the letters “Seg 1” will stop flashing. The numerical value
below the “Seg 1” will flash. Press and hold the scroll key for more than half a
second (less than 2 seconds), select the battery voltage, 10.5v,11.0v,11.5v(default is
10.5v)。
③Confirm the power shedding shielding battery voltage setting. After selecting
numerical value, press and hold the function setting key for more than half a
second (less than 2 seconds). Now, the load shielding battery voltage setting is
confirmed.
④Exit from the setting interface. Press and hold function setting key for more than
half a second (less than 2 seconds), exit from the setting interface and return to main
interface.

17
4.3.6 Automatic Battery Test mode setting(6)
①Enter the setting interface. Press and hold the function setting key for more
than 2 seconds, then come to setting interface, Press and hold the inquiring key for
more than half a second(less than 2 seconds), select the function setting, choose
Automatic Battery Test setting interface, at the moment, the letters “Abt” will flash
②Enter the “Abt” setting interface. Press and hold the function setting key for
more than half a second(less than 2 seconds), then come to setting interface of “Abt”,
at this time, the letters “Abt” will light for a long time. The “ON”(or OFF) below the “Abt”
will flash. Press and hold the inquiring key for more than half a second (less than 2
seconds) to determine whether the “Abt” function is used or not. If used, the
corresponding word is “ON”, if not, the word is “OFF”. It can be determined by
yourself.
③Confirm the “Abt” selecting interface. After selecting ON or OFF, press and hold
the function setting key for more than half a second (less than 2 seconds). Now, the
“Abt” setting function is completed and the “ON” or “OFF” below the “Abt” will light
without flash.
④Exit from the setting interface. Press and hold function setting key for more than
half a second (less than 2 seconds), exit from the setting interface and return to main
interface.
If used, the corresponding word is “ON”,One month periodically check the battery
connections.
4.3.7 Warning Code Display mode setting(7)
①Enter the setting interface. Press and hold the function setting key for more
than 2 seconds, then come to setting interface, Press and hold the inquiring key for
more than half a second(less than 2 seconds), select the function setting, choose
Warning Code Display setting interface, at the moment, the letters “wc” will flash
②Enter the “wc” setting interface. Press and hold the function setting key for
more than half a second(less than 2 seconds), then come to setting interface of “wc”,
at this time, the letters “Abt” will light for a long time. The “ON”(or OFF) below the Abt
Other manuals for POWERPACK PLUS SERIES
1
This manual suits for next models
6
Table of contents
Other MAKELSAN UPS manuals

MAKELSAN
MAKELSAN Lion X 650 User manual

MAKELSAN
MAKELSAN 1K User manual

MAKELSAN
MAKELSAN Lion+ Series User manual

MAKELSAN
MAKELSAN POWERPACK PLUS SERIES User manual

MAKELSAN
MAKELSAN POWERPACK PRIME SERIES User manual

MAKELSAN
MAKELSAN LEVELUPS T3 SERIES User manual

MAKELSAN
MAKELSAN BOXER SERIES User manual

MAKELSAN
MAKELSAN PowerPack SE 1 kVA User manual

MAKELSAN
MAKELSAN SE SERIES User manual

MAKELSAN
MAKELSAN Lion 650VA User manual