3
Installation requirements
Voltage: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120V / 60Hz / 1Ph
Circuit Amps: . . . . . . . . . . . . . . . . . . . . . . . . . . .Dedicated 15A circuit / Unit total is 5.2FLA
Syrup and Co2 Tubing Size: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/8 inch I.D. Minimum
Water Inlet Size: . . . . . . . . . . . . . . 1/2 in supply “T’d” to 2 - 3/8 inch I.D. Lines Minimum
Water Flow Rate: . . . .300 gallons per hour at a minimum flowing pressure of 30-35 psi.
Dimensions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 3/8”W x 31 ½”D x 37”H
Unit Support: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . table rated for ~1000 pounds
CO2 pressure to BIB Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75psi.
Finished Drink Flow Rate: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ~ 3.0 ounces / second
- set water flow rate first to 2.5 oz./sec followed by adjusting syrup flow rate
Ratio: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Refer to Product Manufacturer
Notes:
•If Hopper is to be manually filled with Ice, adequate space above the top of the unit
must be allowed.
•Hopper should NEVER be filled with Ice from a freezer as damage may occur. If
bagged ice is to be used it must be left out of the cooler for approximately 15-20
minutes, broken up and removed from the bag.