When selecting any battery mode, you will be prompted to set the following values:
◦OverDischg SOC” > set "20%" (discharge limit in normal use).
◦“ForceCharge SOC” > set "10%" (emergency charge when the battery reaches this storage level).
◦“ForceChg Limit” > power at which the battery is to be charged during emergency charging (from the mains).
Generally 1600 W is selected so as not to trigger protections.
If, on the other hand, there is no battery installed at the moment, select: NO-BATTERY.
•METER SET:
▪METER SELECT: using the meter supplied with the inverter (EASTRON SDM120CT), you must select: EASTRON 1PH METER.
▪CT DIRECTION: if during installation, you have positioned the meter toroid incorrectly, i.e. with the date pointing to the loads
of the installation, select REVERSE. Otherwise, do not change this function.
•STORAGE MODE SELECT:
In this parameter, the working mode of the equipment is defined, and it must always have the following configuration:
▪FEED IN PRIORITY: OFF.
▪BACKUP: OFF.
▪OFF-GRID: OFF.
▪SELF-USE: ON.
◦CHARGING FROM GRID: (to be determined if you want the equipment to also charge the batteries within a specific
schedule with utility power). Generally, you will select: NOT ALLOW.
•EXPORT POWER SET:
▪ON/OFF: Select ON mode.
▪BACKFLOW POWER:
◦For landfill 0: +0000 W.
◦For sale of surplus: +9900 W.
▪FAIL SAFE: Select ON mode.
The equipment is ready to be used. In the event that the FAIL SAFE fault appears on the screen, check the installation (wiring) of the
energy meter (METER), as the polarity of the communication cable has most probably been reversed.
The configuration of the application for monitoring via WI-FI must be carried out with the mobile application, after acquiring the
STICK-WIFI (accessory) for this equipment.