Maxeon Sunpower Setup guide

Safety and Installation Instructions
for Europe, Asia, Australia, Latin America and Africa
This document applies to Maxeon PV Modules
Languages:
English
French
German
Italian
Spanish
Polish
Indonesian
Contents of this manual are subject to change without notice.
In case of inconsistencies or conflicts between the English version and any other versions of this manual (or
document), the English version shall prevail and take control in all respects.
For the latest Europe, Asia, Australia, Latin America and Africa please refer to
www.sunpower.maxeon.com/int/PVInstallGuideIEC
Maxeon Solar Technologies, Ltd.
www.sunpower.maxeon.com
Document 001-15497 Rev Z
P/N 100657
P/N 520728
REVISION: Z
EnglishFrenchGermanItalianIndonesian Spanish
Polish

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Safety and Installation Instructions
(English - IEC version)
1.0 Introduction
This manual provides safety and installation instructions for IEC
certified Maxeon photovoltaic modules carrying the TUV logo on the
product label (Figure 1).
Figure 1
1.1 Disclaimer of Liability
The installation techniques, handling and use of this product are
beyond company control. Therefore, Maxeon does not assume
responsibility for loss, damage or expense resulting from improper
installation, handling or use.
1.2 Conformity to International Electrotechnical Commission (IEC)
standards
This product meets or exceeds the requirements set forth by IEC
61215 Edition 3-2016 for PV Modules, as well as IEC 61730 Edition 1
and 2 series for Class II applications. The IEC Standard covers flat-plate
PV modules intended for installation on buildings and those intended
to be freestanding. This product is not intended for use where
artificially concentrated sunlight is applied to the module.
This manual shall be used in combination with industry recognized
best practices. Modules should be installed by certified professionals
only.
1.3 Limited Warranty
Module limited warranties are described in the Maxeon warranty
document obtainable at www.sunpower.maxeon.com. Please read
this document for more information.
Warranties do not apply to any of the following;
PV Modules subjected to: (i) misuse, abuse, neglect or accident;
(ii) alteration or improper installation (improper installation
includes, without limitation, installation or array that does not
comply with all Maxeon installation instructions and operations
and maintenance instructions of any type (as may be amended
and updated from time to time at Maxeon’s sole discretion), and
all national, state, and local laws, codes, ordinances, and
regulations); (iii) repair or modification by someone other than
an approved service technician of Maxeon; (iv) conditions
exceeding the voltage, wind, snow load specifications; and any
other operational specification; (v) power failure surges,
lightning, flood, or fire; (vi) damage from persons, biological
activity, or industrial chemical exposure; (vii) glass breakage from
impact or other events outside Maxeon’s control.
2.0 Safety Precautions
Before installing this device, read all safety instructions in this manual.
•Cover all modules in the PV array with an opaque cloth or material
before making or breaking electrical connections.
•Do not disconnect any modules when its inverter is feeding in to
the grid. Switch off the inverter before disconnecting, reinstalling
or making any action with the modules.
•For connectors, which are accessible to untrained people, it is
imperative to use the locking connectors and safety clips, if
applicable, in order to defend against untrained personnel
disconnecting the modules once they have been installed.
•All installations must be performed in compliance with all
applicable regional and local codes.
•There are no user serviceable parts within the module. Do not
attempt to repair any part of the module.
•Installation should be performed only by qualified personnel.
•Remove all metallic jewelry prior to installing this product to
reduce the chance of accidental exposure to live circuits.
•Use insulated tools to reduce your risk of electric shock.
•Do not stand on, walk, drop, and scratch or allow objects to fall on
the glass surface of the modules.
•Damaged modules (broken glass, torn back sheet, broken j-boxes,
broken connectors, etc) can be electrical hazards as well as
laceration hazards. Contact with damaged module surfaces or
module frame can cause electric shock. Damaged modules should
be immediately disconnected from the electric system. The
module should be removed from array as soon as possible and
contact the supplier for disposal instructions.
•Unconnected connectors must always be protected from pollution
(e.g dust, humidity, foreign particles, etc), prior to installation. Do
not leave unconnected (unprotected) connectors exposed to the
environment. A clean assembly environment is therefore essential
to avoid performance degradation.
•Do not allow the connectors to come in contact with chemicals
such as greases, oils and organic solvents which may cause stress
cracking.
•Do not install or handle the modules when they are wet or during
periods of high wind.
•Do not block drain holes or allow water to pool in or near module
frames
•Contact your module supplier if maintenance is necessary.
•Save these instructions!
3.0 Electrical Characteristics
The module electrical ratings are measured under Standard Test
Conditions (STC) of 1 kW/m² irradiance with AM 1.5 spectrum and a
cell temperature of 25 °C. Maxeon modules have specific electrical
characteristics as shown on the datasheets.
A photovoltaic module may produce more current and/or voltage
than reported at STC. Sunny, cool weather and reflection from snow
or water can increase current and power output. Therefore, the values
of Isc and Voc marked on the module should be multiplied by a factor
of 1.25 when determining component voltage ratings, conductor
ampacities, fuse sizes, and size of controls connected to PV output. An
This document includes references to Maxeon X-series (SPR-
Xyy-xxx), P-Series (SPR-Py-xxx-UPP, SPR-Py-xxx-COM-M-BF, SPR-
Py-xxx-COM-S-BF, SPR-Py-xxx-BLK, SPR-Py-xxx-COM-XS), SPR-
MAX3-xxx, SPR-MAX5-xxx, SPR-MAX6-xxx PV Modules.
Do not mix X, MAX3, MAX6, P3 ,P5 and P6 in one System.
All module series does not require functional grounding and are
compatible with transformer-less inverters (ref. section 4.1)
Important! Please read this instruction sheet in its entirety
before installing, wiring, or using this product in any way.
Failure to comply with these instructions will invalidate the
Maxeon Limited Warranty for PV Modules.
Danger! Module interconnects pass direct current (DC) and are
sources of voltage when the module is under load and when it is
exposed to light. Direct current can arc across gaps and may
cause injury or death if improper connection or disconnection is
made, or if contact is made with module components that are
damaged. Do not connect or disconnect modules when current
from the modules or an external source is present.

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
additional 1.25 multiplier may be required by certain local codes for
sizing fuses and conductors. Maxeon recommends the use of open-
circuit voltage temperature coefficients listed on the datasheets when
determining Maximum System Voltage.
4.0 Electrical Connections
Modules may be connected in series and/or parallel to achieve the
desired electrical output as long as certain conditions are met. Please
use only the same type of modules in a combined source circuit.
Even if allowed by local regulation, Plug and Socket connectors mated
together in a PV system must be of the same type (model, rating) from
the same manufacturer i.e. a plug connector from one manufacturer
and a socket connector from another manufacturer, or vice versa,
shall not be used to make a connection. Maxeon recommends that all
wiring be double insulated with a minimum rating of 85° C (185° F). All
wiring should use flexible copper (Cu) conductors. The minimum size
should be determined by the applicable codes. We recommend a size
not less than 4mm2. The insulation type should be appropriate for the
type of installation method used and must meet SCII (Safety Class II)
and IEC 61730 requirements. To minimize the risk from indirect
lightning strikes (Voltage surges), the system should be designed to
avoid loops in the wiring.
Maxeon recommends a conservative minimum bending radius (R) 5x
cable diameter must be maintained and must not be bent on the
direct exit of the connector or junction box. Avoid exposure of
electrical connections to direct sunlight and do not place the
connector in a location where water could easily accumulate.
Installers must refer to connector manufacturer’s instruction for
further installation and connection requirements.
Connectors are factory assembled with intentional gaps between the
cable nut and the body of the connector. Do not retighten module
connector nuts as this may lead to stress cracking of the connector
assembly and will void the warranty.
4.1 System & Equipment Grounding
Please refer to the applicable regional and local codes on grounding
PV arrays and mounting frames for specific requirements (e.g.
lightning protection).
Module Types
SPR X , P series modules and our Maxeon and Performance Product Line are
compatible with Transformer Less (TL) inverters, when used as an
ungrounded PV source.
No frame grounding requirements (including functional frame grounding),
but may be subjected to local regulation.
Functional system grounding of a polarity (positive or negative) is optional
and may be subject to local requirements.
X Series:
SPR-Xyy-xxx-COM
P Series/ Performance Product Line:
SPR-P3-xxx SPR-P3-xxx-BLK SPR-P5-xxx-UPP SPR-P6-xxx-COM-M-BF
SPR-P6-xxx-COM-S-BF SPR-P6-xxx-BLK SPR-P6-xxx-COM-XS
Maxeon Product Line:
SPR-MAX3-xxx SPR-MAX3-xxx-BLK SPR-MAX3-xxx-BLK-RSPR-MAX3-
xxx-RSPR-MAX3-xxx-COM SPR-MAX6-xxx SPR-MAX6-xxx-BLK, SPR-
MAX6-xxx-COM
Note: If you are installing an older Module Type than above
mentioned, please refer to different/previous applicable Safety and
Installation Manual.
If you are doing a frame grounding connection, avoid the direct
contact between Aluminum and Copper using an intermediate metal
like stainless steel or tin.
4.2 Series Connection
The modules may be wired in series to produce the desired voltage
output. Do not exceed the maximum system voltage specified in
module datasheet.
4.3 Parallel Connection
The modules may be combined in parallel to produce the desired
current output. Series string must be fused prior to combining with
other strings if the resulting maximum reverse current exceeds the
fuse rating as shown in the datasheets. Bypass diodes are factory
installed in the modules. Please refer to the applicable regional and
local codes for additional fusing requirements and limitations on the
maximum number of modules in parallel.
5.0 Module Mounting
The Maxeon Limited Warranty for PV Modules is contingent upon
modules being mounted in accordance with the requirements
described in this section.
5.1 Site Considerations
Maxeon modules should be mounted in locations that meet the
following requirements:
Operating Temperature: All Maxeon modules must be mounted in
environments within the following maximum and minimum operating
temperatures:
Maximum Operating Temperature +85 °C (+185 °F)
Minimum Operating Temperature -40 °C (-40 °F)
Care should be taken to provide adequate ventilation behind the
modules, especially in hot environments.
Shading: Modules should be installed so that permanent shading of
cells is avoided and partial shading that may occur during certain
times of the day or year is minimized. Permanent shading is defined
as shade that is cast over the same position (of constant area) of the
solar module throughout the generation hours of the day.
Shading may induce in certain cases strong energy production
reduction, even in case of small shading and should be avoid as much
as possible, specially at mid-day when the production is maximum.
Design Strength: Maxeon modules are designed to meet a positive or
negative (upward and downward, e.g. wind) withstanding test
pressure load and a negative (or downward, e.g. static load or snow
load) withstanding test pressure load, as per IEC 61215, when
mounted in the configurations specified in Section 5.2 and Tables 1.2
or 1.3 below.
When mounting modules in snow prone or high wind environments,
special care should be taken to mount the modules in a manner that
provides sufficient design strength while meeting local code
requirements.
Additional authorized Operating Environments:
Modules can be mounted in the following aggressive environment
according to the test limits mentioned below (On Request)
Salt mist corrosion testing: IEC 61701 Severity 6*
Ammonia Corrosion Resistance: IEC 62716 Concentration: 6,667ppm*
*Pending for SPR-MAX3-xxx-R SPR-MAX3-xxx-BLK-R
Excluded Operating Environments:
Certain operating environments are not recommended for specific
Maxeon modules and are excluded from the Maxeon Limited
Warranty for these modules.
English

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
No Maxeon module should be mounted at a site where it may be
subject to direct contact with salt water, or other aggressive
environment.
Modules should not be installed near flammable liquids, gases, or
locations with hazardous materials; or moving vehicules of any type.
Performance Series Mounting Orientation
Performance Series (P-Series) modules are designed to be installed in
landscape orientation. In landscape orientation, P-series modules
maintain higher power under row to row shading and edge soiling.
5.2 Mounting Configurations
Mounting system must provide a flat plane for the modules to be
mounted on and must not cause any twist or stress to be placed on
the Module, even in case of thermal expension.
Modules may be mounted at any angle from horizontal to vertical.
Select the appropriate orientation to maximize sunlight exposure.
Maxeon recommends for a good performance of the system
(reduction of soiling effect/water pooling) a minimum of 5˚tilt angle.
The cleaning frequency must be increased for modules installed with
a very low angle.
Commercial modules (128 cells) frames have permanently attached
stacking pins located a 20mm zone on the long side frame at 388-408
mm. Mounting system hardware used with commercial modules must
account for the presence of these stacking pins (see Appendix).
Specific information on module dimensions and the location of
mounting and grounding holes is provided in Appendix.
In order to prevent water from entering the junction box, which could
present a safety hazard, modules should not be mounted such that
the front/top glass faces downward (e.g., on a tracking structure that
positions the module with the junction box facing skyward during
sleep mode).
We also want to remind that the watertightness is not ensured by the
modules but by the mounting system and that drainage should be well
designed for Modules.
Clearance between the module frames and structure or ground is
required to prevent wiring damage and allows air to circulate behind
the module. The recommended assembling clearance between
modules installed on any mounting system is a minimum of 50 mm
distance.
When installed on a roof, the module shall be mounted according to
the local and regional building and fire safety regulations. In case the
module is installed in a roof integrated PV-System (BIPV), it shall be
mounted over a watertight and fire-resistant underlayment rated for
such application
Modules mounting systems should only be installed on building that
have been formally considered for structural integrity, and confirmed
to be capable of handling the additional weighted load of the Modules
and mounting systems, by a certified building specialist or engineer.
Mounting system supplier shall manage the galvanic corrosion which
can occur between the aluminium frame of the Modules and
mounting system or grounding hardware if such devices is comprised
of dissimilar metals.
The module is only certified for use when its factory frame is fully
intact. Do not remove or alter the module frame. Creating additional
mounting holes or removing the stacking pins may damage the
module and reduce the strength of the frame, therefore are not
allowed. Using mounting Clamps or clips with additional grounding
bolts or grounding metal sheets could be in compliance with this
Safety and Installation Instructions manual subject to conditions of
Section 4.1
Modules may be mounted using the following methods only:
1) Frame Holes: Secure the module to the structure using the
factory mounting holes. Four M6 or M8 stainless steel bolts,
with nuts, washers, and lock washers are recommended per
module. Bolts to be fasten according to racking supplier
recommendations. Refer to Appendix for the module
dimensions and mounting hole locations.
2) Pressure Clamps or Clips: Mount the module with the opposite
clips on the longer and/or shorter side of the frame of the
module. The clips allowed location should be according to Table
1.1. Installers should ensure the clamps are of sufficient
strength to allow for the maximum design pressure of the
module. Clips and clamps are not provided by Maxeon. Clamps
must apply force collinear with the ‘wall’ of the module frame
and not only to the top flange. Clamps shall not apply excessive
force to the top frame, warp the top flange, or contact the glass-
these practices void the module warranty and risk glass
breakage. Figure 1a
illustrates locations for top
frame clamp force. Avoid
clamping within 50mm of
module corners to reduce
risk of frame corner
deflection and glass
breakage. When clamping
to the module frame,
torque should never exceed 15 N.m to reduce chances of frame
deformation, if the clamp datasheets show a specific torque
value which is lower than 15 Nm the installer should follow the
torque value which ever is more stringent. A calibrated torque
wrench must be used. Mounting systems should be evaluated
for compatibility before installing specially when the system is
not using Clamps or clips. Please contact Maxeon for the
approval of the use of non-standard pressure clamps or clips
where torque values are higher than otherwise stated.
Minimum clamp width allowance is ≥35mm, and for corner
clamping the minimum clamp width is: ≥50mm. Clamps should
not be in contact with the front glass and clamps should not
deform the frame.
Maxeon does not recommend nor endorse the application on
the modules of clamps which, as part of their grounding or
earthing function, have teeth or claw features (see Figure 2)
which may, individually or cumulatively, cause the module
breakage due to (and without limitation):
i) the grounding features touching the front glass which is
incorporated into the module due to the position of such
grounding feature,
ii) the shape, the position or the number of the grounding
features deforming the module top frame, or
iii) the clamp being over-torqued during the installation.
Force must not deform
top frame flange or
glass may break
Force has
to be
applied in
line with
frame
wall
Figure 1a: Clamp Force Locations

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Maxeon shall not be
liable for any damages or
losses whatsoever arising
from the use by the
Installer of any such
clamps on its modules,
and disclaims all
warranties, express or
implied, applicable to
those modules should
they be damaged in any way by such clamps. Therefore, the use
of the above mentioned clamps by the Installer is at the
Installer's sole risks.
3) End Mount: End mounting is the capture mounting of the
length of the module’s shorter frames with clamps on each
shorter sides of the frame. Three different configurations are
possible: 1) with two mounting rails under the complete length
of each shorter side of the Modules, (See Table 1.2), 2) with two
mounting rails parallel to the long side of the Modules (See
Table 1.2) and 3) without any mounting rail (See Table 1.2). The
end-mounting rails and clips or clamps (identified as A(1&2&3&4)
in Table 1.1) must be of sufficient strength to allow for
maximum designed test pressure of the module. Verify this
capacity with the mounting system of vendor before
installation.
4) Hybrid Mount: Combination with clamps or clips located on
longer or shorter sides of Modules are also possible, see Table
1.2 for allowed configurations. In any case, four clampings
points are needed.
5) Maxeon specified or Maxeon supplied mounting systems.
Modules mounted with strict adherence to Maxeon
documentation, using hardware systems supplied by or
specified by Maxeon.
Figure 2 and Table 1.1 below demonstrate the mounting locations and
Tables 1.2 and 1.3 give allowed load ratings (designed test value) for
Maxeon modules.
Figure 2: Mounting Zone locations for Maxeon modules
For P3-COM, MAX3 96, 104, 112 cells and MAX6 66 cells:
For 128 cells, P-Series and MAX5/MAX6 Commercial:
Table 1.1: Approved module clamping/direct fixation zones
Module Configuration Mounting zone distance from
corner in (mm)1Frame
holes
E
Module size
Frame
type
A B C
(1&2&3&4) (1&2&3&4) (1&2&3&4) (1&2&3&4)
96 cells, 104
cells (MAX3),
112 cells and
and P3 RES+
G3
(Black)
Silver &
G4.1 &
G4.2 &
G4.3
50-350
150-380
50-150
As per
Drawing in
the Table 2
112 AC ready G5.2 50-350 272-453 50-272
128 cells G4 &
G4.1 50-350 408-880 50-375
P3-COM G4.2 &
G4.3 50-350 408-833 50-375
MAX6 (66 cells) G5.2 50-350 265-514 50-265
MAX6 COM
(72 cells)
G4.2 &
G5.6 50-350 296-536 50-296
D - There is a 20mm zone at 388-408mm from the corner where mounting is not
allowed due to the module stacking pin feature. Applicable to 128 and 96 cell
commercial only.
1) No part of the module clamp may extend beyond this area.
Figure 3: Mounting Configurations
Configurations 1 and 2 show mounting with rail support, 3 and 4
show mounting without rail support. In “With Rail Support” the rails
becomes conventional or rails transverse while “Without Rail
Support” becomes end mounted in long or short side. In the case
when the glass deflects it would not deflect in the rails for additional
support.
Figure 2

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Table 1.2: Mounting Zone Design Load Ratings for Racking system
without rail support underneath the module. Refer to configuration
3 and 4 in Fig.3
Module
Configuration
Wind (up & down) / Snow (down)
(units in Pa) (***)
Module
size
Frame
type
End
Mount
A
(1&2&3&4)
Frame
Holes
E
(1&2&3&4)
B
(1&2&3&4)
C(1&2&3&4)
or B + C
(B1&3 +C2&4 or B2&4 +C1&3)
Or A + B
(A1&3 +B2&4 or A2&4 +B1&3)
Or A + C
(A1&3 +C2&4 or A2&4 +C1&3)
96 cells
G3
Black &
Silver
2400/
2400(*)
2400/
5400
2400/
5400
2400/2400
104 cells
(MAX3)
and 112-
cells
(MAX3)
G4.2 1800/
1800
112 AC
Ready G5.2 1800/
1800
3600/
3600
2400/
2400 1800/1800
P3 RES+ G4.3 1300/
1600
1600/
2400
1600/
2400
1300/
1600
128 cells G4 &
G4.1
Not
applicable
(**)
2400/
5400
3600/
3600 2400/2400
P3-COM G4.2 &
G4.3
1600/
1600
1600/
2400
1600/
2400 1600/1600
MAX6 (66
cells) G5.2 1600/
1600
3600/
3600
3600/
3600 1600/1600
MAX6-
COM
(72 cells)
G5.6
1067/
1200
3600/
3600
3600/
3600 1600/1600
(*): 5400Pa is allowed with clamps and mounting rails along the longer side of the frame
(**): 2400/2400Pa are allowed with clamps and mounting rails along the longer side of
the frame
For Rooftop application 1200/1200Pa is allowed with only clamps
(***) Safety factor of 1.5 included
Table 1.3: Mounting Zone Load Ratings for Racking system with rail
support. Refer to Configuration 1 and 2 in Fig.3
Module Configuration
Wind (up & down) /
Snow (down)
(units in Pa) (***)
Module size Frame type B (1&2&3&4) C (1&2&3&4)
96 cells and P3 BLK G3 (Black &Silver) &
G4.1 & G4.2 2400 / 5400
2400 / 2400
104 cells (MAX3) and
112-cells (MAX3) G4.2 3600/5400
112 AC Ready G5.2 2800/3600 1800/1800
P3 RES+ G4.3 1600/3600 1600/3600
128 cells G4 & G4.1 3600 / 5400 2400/ 3600
P3-COM G4.2 & G4.3 2000/2400 1600/2400
MAX6 (66 cells) G5.2 3600/6000 2800/2800
MAX6 COM
(72 cells) G5.6 3000/5400 2400/2400
Table 1.4: Mounting Zone Load Ratings for Performance Modules
Applicable
Products2
Mounting
Zone
Distance
from
corner
(mm)
Wind (up &
down) /
Snow(down)
(units in Pa)3
Mounting
Method
P3 UPP
(2066 x 1160
x35mm
A 183-283
1600/2400
Clamp
B 466-566
1600/36004
C 783-833
1600/1600
D 260-320
1600/1600
E 465-565
1600/2400
Frame
Holes2
383 (1300) 1600/1600
Bolt
504 (1058) 1600/3600
683 (700) 1600/1600
833 (400)
P5 UPP &
P6 COM-
M
(2384 x 1092 x
35mm)
A 50-546
800/1600
Clamp6
B 546-692
1600/36004
C 692-1042
1333/3600
D 0-323
933/933 Clamp7
E 546-692
1600/3600 Clamp8
F 546-692
1600/2000 Clamp9
G 0-323
933/933 Clamp10
Frame
Holes2
492 (1400) 1600/3600
Bolt5
642 (1100) 1600/3600
992 (400) 1160/1160
P6 RES
BLK &
COM-XS
(1808 x 1086 x
30mm) &
(1808 x 1092 x
30mm)
A 50-402
1333/1333
Clamp6
B 402-502
1600/3600
B2 217-617
1333/1800
C 502-754
1200/1333
D 221-321
1066/1066 Clamp7
E 402-502
1200/1800 Clamp8
F 50-100
1300/1300 Clamp9
G 0-221
1066/1066 Clamp10
P6 COM-S
(2185 x 1092 x
35mm)
A 50-496
1066/1200
Clamp6
B 496-596
1600/3600
C 596-942
1066/1600
D 223-323
933/1600 Clamp7
E 496-596
1200/1867 Clamp8
F 50-100
1066/1200 Clamp9
G 0-100 666/800 Clamp10
100-323 1066/1066
Frame
Holes2
1100(392) 1600/3600 Bolt
1400(542) 1600/3600
2 Refer to Table 2 for different mounting hole locations
3 Safety Factor 1.5 included
4 IEC validated
5 Minimum washer size of 24mm in diameter is required.
6 Long Side Mounting, Rails Perpendicular to Mounting Frame
7 Short Side Mounting, Rails Parallel to Mounting Frame
8 Long Side Mounting, Rails Parallel to Mounting Frame
9 Long Side Mounting, Point Supported (Bottom Flange Mounting)
10 Corner Mounting (Short Side), minimum of 50mm clamp is required.
Figure 4: Mounting Zone Locations for Performance modules
For P3, P5 UPP and P6 (COM-M, COM-S, RES BLK, COM-XS)

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
5.3 Ground Mount Applications for Bifacial modules
Various environmental and installation parameters affect bifacial
gain. Albedo is a measure of the amount of light reflected from the
ground surface. A higher albedo factor will increase irradiance on the
backside and result in higher bifacial gain of the module. The surface
conditions, month of the year, time of day, GHI and DNI both influence
the amount of incident rearside irradiance.
Maxeon recommends to check with solar module mounting hardware
supplier in order to determine the Structure Shading factor of your
particular installation. The Structure Shading Factor varies with
racking system design, irradiance, albedo and height of module
installation above ground and has an overall impact on the rear side
irradiance mismatch.
The Rearside mismatch losses are proportional to the albedo, height
of the modules above ground and structure shading factor. The
irradiance non-uniformity on the rearside results in mismatch
generally as the albedo increases and installation height of the
modules are lower to the ground.
5.4 Rooftop Applications for Bifacial modules
Bifacial modules use direct, reflected or diffuse sunlight at the
rearside to generate additional power. Therefore, it is recommended
to use bifacial modules installed on flat roof applications.
In order to maximize the bifacial gain at the rooftop applications the
following parameters listed below should be considered:
•Surface Albedo
•Roof Integrity
•Module Tilt Angle
•Module Elevation
•Structural Backside Shading
The bifacial modules can be mounted both landscape or portrait
orientation as shown in Appendix section.
When installing a bifacial module on a roof, check applicable building
codes and ensure that the roof construction and the structural load
calculations of the building are suitable.
Bifacial gain tends to be most effective with a higher tilt angle.
As the tilt angle and the module elevation from the underlying surface
increases, more reflected light and diffuse light can be captured by the
module. The mounting rails shall be designed to limit the rear side
shading as much as possible. Obstacles between modules and the
ground should be avoided as much as possible in order to increase the
bifacial gain.
5.5 Bifacial Electrical Considerations
The overall electrical bifacial gain is determined by the combination of
surface albedo, irradiance, module tilt angle, shading losses from the
rearside, rearside mismatch and module elevation above ground.
Please refer to the Maxeon datasheet for the electrical outputs with
respect to the overall bifacial gain. Please utilise a suitable
performance software package to simulate the overall bifacial gain.
5.6 Handling of Modules during Installation
Do not place modules face forward in direct contact with abrasive
surfaces like roofs, driveways, wooden pallets, railings, stucco walls,
etc…
The module front surface glass is sensitive to oils and abrasive
surfaces, which may lead to scratches and irregular soiling.
During storage, modules need to be protected from rain or any kinds
of liquids. Required storage temperature is between 10°C to 40°C in a
dry environment (humidity between 30 to 80%). Do not store modules
outdoor to avoid moisture and wet conditions.
Modules that feature antireflective coated glass are prone to visible
finger print marks if touched on the front glass surface. Maxeon
recommends handing modules with anti-reflective glass with gloves
(no leather gloves) or limiting touching of the front surface. Any finger
print marks resulting from installation will naturally disappear over
time or can be reduced by following the washing guidelines in Section
6.0 below. Any module coverage (colored plastic tarps or similar)
during installation can lead to permanent front glass discoloration and
is not recommended. The use of vacuum lifting pads can cause
permanent marks on the front glass. Never lift or move the module
using the cables or the junction box under any-circumstances.
Shading incidence need to be avoided during PV system operation.
The system is not supposed to be energized until the mounting
scaffolding, fences or railing have been removed from the roof.
Systems should be disconnected in any cases of maintenance which
can cause shading (e.g. chimney sweeping, any roof maintenance,
antenna/dish installations, etc).
6.0 Maintenance
Maxeon recommends visual inspection on a regular basis of all
modules for safe electrical connections, sound mechanical
connection, and free from corrosion. This visual inspection should be
performed by trained personnel. The standard frequency is once a
year according to environmental conditions, periodic cleaning of
modules is recommended but is not required. Periodic cleaning has
resulted in improved performance levels, especially in regions with
low levels of annual precipitation (less than 46,3cm (18,25 inches)).
Consult your dealer or supplier about recommended cleaning
schedules for your area.
To clean a module, wash with potable, non-heated, water. Normal
water pressure is more than adequate, but pressurized water up to
100 bar (min.50 cm distance) may be used. Maxeon recommends
using a large hosepipe and not to perform cleaning at high outside
temperatures. Fingerprints, stains, or accumulations of dirt on the
front surface may be removed as follows: first rinse off area and let
soak for a short period of time (5 mins). Re-wet and use a soft sponge
or seamless cloth to wipe glass surface in a circular motion.
Fingerprints typically can be removed with a soft cloth or sponge and
water after wetting. Do not use harsh cleaning materials such as
scouring powder, steel wool, scrapers, blades, or other sharp
instruments to clean the glass surface of the module. Use of such
materials or cleaning without consultation will invalidate the product
warranty. As dry cleaning is also risky for Anti-Reflective (AR) coated
module surface, spinning brush is not recommended for module
cleaning.

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Recommended Cable Management
*The image above is for illustration purposes only
Portrait Stringing
Leapfrog Stringing (Portrait)
Maxeon Product Line:
Landscape Stringing
Performance Product Line:
Portrait Stringing
Landscape Stringing
Leapfrog Stringing (Portrait)

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Table 2: Module Frame Details
Platform Module mounting and ground hole detail Frame Profile
RESIDENTIAL G3 FRAME ONLY
Residential
Modules
96 CELL MODULE FRAME DETAIL SIDE FRAME PROFILE
END FRAME PROFILE
FOR COMMERCIAL (SILVER FRAME) MODULES ONLY, INCLUDES STACKING PINS
Commercial
Modules
96 CELL COMMERCIAL MODULE 128 CELL COMMERCIAL MODULE SIDE FRAME PROFILE
With Stacking Pins
END FRAME PROFILE
32 mm
46.08 mm
10.30 mm
18.50 mm
2.20 mm
22 mm
46.08 mm
10.50 mm
1.27 mm
4X Ø 4.8 mm
Drain Holes
12X Ø 6.6 mm
Mounting Holes
6X Ø 4.2 mm
Ground Holes
4X Ø 6.10 mm
Stackings Pins
3.2 mm
398 mm
46 mm
(Back View)
(Front View)
Stacking Pins
4X Ø6.10 mm
300 mm
20X Ø6.8 mm
Mounting Holes
4X Ø4.2 mm
Ground Holes
4X Ø4.8 mm
Drain Holes
398 mm
3,2 mm 46 mm
(Front View)
(Back View)
1046 mm
1002 mm
2067 mm
1200 mm
1423 mm
539 mm
32 mm
46.08 mm
3.18 mm 10.30 mm
18.50 mm
2.20 mm
22 mm
46.08 mm
10.50 mm
1.27 mm
Method 1:
Frame Hole
Locations
Method 1:
Frame Hole
Locations
Measurement Tolerances are +/-3 mm for the Length and Width of the Module.

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Platform Module mounting and ground hole detail
FOR P3 MODULES
Residential/
Commercial
Modules
P3 BLK (GEN 4.3) P3 COM (GEN 4.2)
SIDE FRAME PROFILE END FRAME PROFILE SIDE FRAME PROFILE END FRAME PROFILE
FOR P3 GEN 4.3 FRAME MODULES
Commercial
Modules
P3 UPP P3 COM
SIDE FRAME PROFILE END FRAME PROFILE SIDE FRAME PROFILE END FRAME PROFILE
998 mm
954 mm
1690 mm
1300 mm
1100 mm
4X Ø4.2mm
Ground Holes
Mounting Holes
8X Ø6.8mm
400 mm
539 mm
1058 mm
1423 mm
954 mm
2066 mm
998 mm
40
4X Ø4.2mm
Ground Holes
Mounting Holes
12X Ø6.7mm
Mounting Holes
4X Ø6.8mm
4X 5.0mm (W)
x 15.0mm (L)
SLOT
1200 mm
1606 mm
32mm
35 mm
24 mm
35 mm
32mm
40 mm
24 mm
40 mm
1160 mm
2066 mm
MODEL:SPR-P19-410-COM
RatedPower(Pmax)
1
(+5/ 0
%) 410 W
Voltage(Vmp) 43.9
V
Current(Imp) 9.35
A
Open-CircuitVoltage(Voc) 53.1
V
Short-CircuitCurrent(Isc) 9.94
A
MaximumSeriesFuse 15
A
1
StandardTestConditions:1000W/m
2
,AM1.5,25°C
Suitableforungro unded, positive,ornegativegroundedDCsystems
FieldWiring:Cuwiringonly, min. 12 AWG/4 mm
2
,insulatedfor90°C min.
WARNING
SEVEREELECTRICALHAZARD
•Solarmodulehasfull voltage even in very low light.
•Installationshouldonlybe done by a qualified technician.
527040
www.sunpower.com
Patentedasshownatwww.sunpower.com/patents
SafetyClassII
FireRating:ClassC
Max.SystemVoltage:1500VDC
400 mm
700 mm
1058 mm
1300 mm
4X Ø4.2 mm
Ground
Holes
8X 10mm(L) x 7mm(W)
R3.5mm
Mounting Holes
8X 14mm(L) x 9mm(W)
R4.5mm
SLOTS
35mm
400 mm
539 mm
1058 mm
1423 mm
954 mm
2066 mm
998 mm
35
4X Ø4.2 mm
Ground
Holes
Mounting Holes
4X Ø6.7 mm
Mounting Holes
12X Ø6.8 mm
4X 5.0 mm (W)
x 15.0 mm (L)
SLOTS
1200 mm
1606 mm
35 mm
35 mm
35 mm
35 mm
32mm
35 mm
24 mm
35 mm

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Platform Module mounting and ground hole detail Frame Profile
FOR P5 UPP & P6 BIFACIAL GEN 4.3
Commercial
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
FOR P3 RES+ (GEN 4.3)
Commercial
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
FOR MAX3 (104-CELL) GEN 4.2 MODULES
Commercial
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
1092 mm
1043 mm
400 mm
1100 mm
1400 mm
2384 mm
4X Ø4.2mm
Ground Holes
8X 14mm (L) x 9mm (W)
R4.5mm
SLOTS
4X 10mm (L) x 7mm (W)
R3.5mm
Mounting Holes
35 mm
35 mm
35 mm
35 mm
16 mm
4x Ø 4.2 mm
Ground Holes
8x Ø 6.8 mm
Mounting Holes
1690 mm
1500 mm
1300 mm
1100 mm
1046 mm
1002 mm
35mm
32 mm
35mm
24 mm
4x Ø 4.2 mm
Ground Holes
8x Ø 6.8 mm
Mounting Holes
1690 mm
1500 mm
1300 mm
1100 mm
1046 mm
1002 mm
32mm
40 mm
24 mm
40 mm

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Platform Module mounting and ground hole detail Frame Profile
FOR 112c GEN 4.2 FRAME MODULES
SIDE FRAME PROFILE
END FRAME PROFILE
FOR MAX6 66-CELL GEN 5.2 FRAME MODULES
Residential/
Commercial
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
FOR MAX6 72-CELL GEN 5.6 FRAME MODULES
Residential
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
4x Ø 4.22 mm
Grounding Holes
8x Ø 6.80 mm
Mounting Holes
1812 mm
1656 mm
1300 mm
1100 mm
1046 mm
1002 mm
32mm
40 mm
24 mm
40 mm
1872 mm
1032 mm
Ground Holes
40mm
Quarter Mount Holes
1100 mm
32 mm
40mm
24 mm
40mm
35 mm
400 mm
1200 mm
1423 mm
1653 mm
1983 mm
2047 mm
1039 mm
995 mm
4X Ø 4.60mm
Ø 7.40mm X 90º
MLSD Holes
16X Ø 6.80 mm
Mounting Holes
4X Ø 4.22 mm
Ground Holes
60 mm
96.50 mm
32 mm
35 mm
32 mm
35 mm
Measurement Tolerances are +/-3 mm for the Length and Width of the Module.

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Platform Module mounting and ground hole detail Frame Profile
FOR P6 COM-S BIFACIAL GEN 4.3
Commercial
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
FOR P6 RES BLACK & COM-XS GEN 4.4
Commercial
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
FOR P6 COM-XS GEN 4.4 (1092mm)
Commercial
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
35 mm
1092 mm
2185 mm
1100 mm
1400 mm
1051 mm
4X Ø4.2
Grounding Holes
8X 9mm (W) x 14mm (L), R4.5
Mounting Holes
35 mm
30 mm
35 mm
16 mm
30 mm
1086 mm
1808 mm
1100 mm
1038 mm
4X Ø4.2
Grounding Holes
4X 9mm (W) x 14mm (L), R4.5
Mounting Holes
30 mm
33 mm
30 mm
24 mm
30 mm
1092 mm
1808 mm
1100 mm
1044 mm
2X Ø4.2
Grounding Holes
4X 9mm (W) x 14mm (L), R4.5
Mounting Holes
30 mm
33 mm
30 mm
24 mm
Measurement Tolerances are +/-3 mm for the Length and Width of the Module.

MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions - Document 001-15497 Rev.Z
©February 2023 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice.
Platform Module mounting and ground hole detail Frame Profile
FOR 112c AC READY GEN 5.2 FRAME MODULES
Residential
Modules
SIDE FRAME PROFILE
END FRAME PROFILE
1046 mm
1002 mm
1100 mm
1300 mm
1656 mm
1812 mm
B
A- Ground Holes (4X Ø4.2mm)
B- Mounting Holes (8X Ø6.8mm)
A
40 mm
32 mm
40 mm
24 mm
Measurement Tolerances are +/-3 mm for the Length and Width of the Module.
Other manuals for Sunpower
2
This manual suits for next models
3
Table of contents
Other Maxeon Solar Panel manuals