McQuay MQC164036CCK216B User manual

R410A 60Hz Universal Outdoor Series Technical Manual Outdoor Unit
I
16 SEER TOP-DISCHARGE UNIT
TECHNICAL MANUAL

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
II
Part 1. General Information.......................................................................................4
1. Model Names of Indoor/Outdoor Units .......................................................................5
2. External Appearance .....................................................................................................6
3. Features ..........................................................................................................................7
Part 2 Outdoor Unit....................................................................................................8
1. Specification ...................................................................................................................9
2.Dimensions....................................................................................................................13
3. Service Space..............................................................................................................14
4. Wiring Diagrams ..........................................................................................................15
5. Electric Characteristics ...............................................................................................17
6. Operation Limits...........................................................................................................17
7. Sound Levels................................................................................................................18
8. Exploded View .............................................................................................................19
9. Troubleshooting ...........................................................................................................20
Part 3 Indoor units ...................................................................................................36
1. Round-way cassette ............................................................................................37
1.1 Standard round-flow cassette........................................................................................................ 37
1.2. Specification ................................................................................................................................. 39
1.3. Dimension..................................................................................................................................... 41
2.Floor & Ceiling ......................................................................................................52
2.1 Features.........................................................................................................................52
2.2 Specifications................................................................................................................54
2.4 Service Space................................................................................................................57
2.5 Wiring Diagrams...........................................................................................................58
2.6 Electric Characteristics .................................................................................................58
Content

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
III
Part 4 Installation.....................................................................................................70
1. Precaution on Installation...........................................................................................71
2. Vacuum Dry and Leakage Checking ........................................................................73
3. Additional Refrigerant Charge ...................................................................................75
4. Insulation Work ............................................................................................................77
5.Test Operation...............................................................................................................79
6. Wiring diagram when connecting with 10 seer indoor unit....................................80

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
4
Part 1. General Information
2. Model Names of Indoor/Outdoor Units ........................................... 4
3. External Appearance ...................................................................... 5
4. Features ......................................................................................... 6
R410A 60Hz Universal Outdoor series

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
5
1. Model Names of Indoor/Outdoor Units
1.1 Indoor Units
Model name
Dimension(W×H×D)
(mm)
Power supply
SEER 16 Cooling Only
MQC164036CCK216B
840×285×840
208~230V-1Ph-60Hz
MQC164036CFC216B
1250×675×235
208~230V-1Ph-60Hz
MQC164060CCK216B
840×285×840
208~230V-1Ph-60Hz
MQC164060CFC216B
1670×750×235
208~230V-1Ph-60Hz
1.2 Outdoor Units
Model name
Dimension (W×H×D)
(mm)
Power supply
24V control
MCI16036CCU216A
740×633×740
208~230V-1Ph-60Hz
MCI16060CCU216A
740×835×740
208~230V-1Ph-60Hz

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
6
2. External Appearance
2.1 Indoor unit
Cassette
Floor-ceiling
2.2 Outdoor unit

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
7
Top-discharge
Note: Standard outdoor unit is using metal grill, and plastic grill can be customized.
3. Features
3.1 Capacity range : 36k/60k, cooling only type.
3.2 Well known brand inverter compressor: Mitsubishi & GMCC, reliable quality.
3.3 Can be matched with cassette\floor-ceiling and air-handler units.
3.4 Coils constructed with enhanced aluminum fins, golden fins/ blue dins are avaliable.
3.5 Integrated circuit with refrigerant cooling design
3.6 24V control, time delay relay, fan relay and transformer included.
3.7 R410A environment friendly refrigerant.
3.8 Flexible installation, ceiling suspended and floor standing .
3.9 New panel for cassette units,simple and voguish appearance suit for different.

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
8
Part 2 Outdoor Unit
1. Specification ................................................................................... 8
2. Dimensions................................................................................... 10
3. Service Space ...............................................................................11
4. Wiring Diagrams ........................................................................... 12
5. Electric Characteristics ................................................................. 14
6. Operation Limits ........................................................................... 14
7. Sound Levels................................................................................ 15
8. Exploded View.............................................................................. 16
9. Troubleshooting............................................................................ 17

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
9
1. Specification
Model name
Unit
MCI16036CCU216A
MCI16060CCU216A
Code
Outdoor code
821039000061
821039000060
Power supply
V/Ph/Hz
208~230-1-60
208~230-1-60
Cooling
Capacity
Btu/h
36000
60000
Capacity
W
10500(3500-10500)
16000(6200-16000)
Power Input
W
600-4000
600-5500
Current Input
A
2.5-19
2.5-30
Outdoor coil
Number of row
1
2
Fin spacing
mm
1.4
1.4
Fin material
Hydrophilic
aluminum foil
aluminum
Hydrophilic
aluminum foil
aluminum
Tube outside
diameter
mm
φ7
Ф7
Tube material
Inner grooved
Inner grooved
Coil length x height x
width
mm
2148×588×13.37
2136×798×26.76
Compressor
Brand
GMCC
Mitsubishi
Model
ATM240D57UFT
MNB40FEQMC
Type
Twin-rotary
Twin-rotary
Capacity
W/h
7190
12900
Input
W
1935
3960
Rated current(RLA)
A
8.85
14.8
Refrigerant oil
ml
670
1100
Outdoor fan motor
Brand
Lvzhi
SINJUN
Model
YDK-110-8P2
YDK-230-6P2
Output
W
110.00
230.00
Running current
A
0.9
/
Capacitor
μF
6μF/450V
12μF/450V
Speed
r/min
850
1100
Outdoor air flow
m3/h
4500
6000
Outdoor noise level
dB(A)
57
60
Outdoor dimension
Unit (WxHxD)
mm
740×740×635
740×740×835

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
10
Packing (WxHxD)
mm
760×760×660
760×760×875
Net/Gross weight
kg
66/70
80/85
Refrigerant
Type
R410A
R410A
Charge
kg
2.2
3.8
Refrigerant pipe
Liquid side/ Gas side
mm(inch)
3/8 / 3/4
3/8 / 3/4
Max. refrigerant pipe
length
m
25
30
Max. difference in
level
m
20
20
Operation temperature range
℃
16~32
16~32
Ambient temperature range
℃
16~50
16~50

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
11
Model
36K
60K
820023100002
820023100001
MQC164036CFC216B
MQC164060CFC216B
Indoor power supply
V/Ph/Hz
208~230/1/60
208~230/1/60
Cooling
Capacity
kW
10.5
16
Input
W
240
320
Rated current
A
1.0
1.5
Max. power input
W
4000
6800
Max. current input
A
19.0
35.0
Indoor fan motor
Model
YSK110-180LD-4P2
YSK110-85LD-4P2
Brand
XINJUN
KANGBAO
Power output
W
180
85*2
Capacitor
μF
5
5
Speed
r/min
1330/1230/1130
1560/1430/1300
Insulation class
B
B
Indoor coil
Number of rows
3
4
Tube pitch(a) x row pitch(b)
mm
25*21.65
22*19.05
Fin spacing
mm
1.7
1.4
Fin type
Hydrophilic
Hydrophilic
Tube outside dia. and type
mm
9.52
7.94
Inner grooved
Inner grooved
Coil length x height x width
mm
982/250/65
1360/252/70
Number of circuits
5
4
Indoor air flow(High speed)
m3/h
1800
2000
Indoor noise level
dB(A)
≤64
≤65
Indoor unit
Dimension(W×H×D)
mm
1250×675×235
1670×675×235
Packing(W×H×D)
mm
1380×765×325
1750×765×325
Gross/Net weight
kg
38/33
49/43
Max pressure
MPa
4.5
4.5
Refrigerant type
R410A
R410A
Refrigerant piping
Liquid side/Gas side
mm
Ф9.52/Ф15.88
Ф9.52/Ф15.88
Drainage pipe
mm
DN25
DN25
Standard controller
Wired control

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
12
Operation temp
°C
16-32
16~32

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
13
2.Dimensions
All dimensions are in mm. They are subject tochange without notice.
Certified dimensions will be provided upon request.
Model
Dimensions(mm)
Refrigerant Connection pipe
Size(mm)
A
B
C
Liquid(φ)
Vapor(φ)
LF
RF
36K
633
740
740
9.52
12.7
19.05
60K
835
740
740
9.52
12.7
19.05
NOTE: LF means cooling only model; RF means heat pump model.

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
14
3. Service Space

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
15
4. Wiring Diagrams

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
16

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
17
5. Electric Characteristics
Model
Outdoor Unit
Hz
Voltage
Min.
Max.
Outdoor
motor
output(kw)
MCI16036CCU216A
60
208~230V
198V
242V
0.21
MCI16060CCU216A
60
208~230V
198V
242V
0.36
6. Operation Limits
Operation mode
Outdoor temperature(℃)
Room temperature(℃)
Cooling operation
18~47
16~32
10 15 25 30 3520
15
20
25
30
35
40
45
Indoor temperature(℃WB)
Outdoor temperature(℃DB)
STD
Cooling

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
18
7. Sound Levels
1 m
(body height +1 )/2 m
Microphone
Model
Noise level dB(A)
MCI16036CCU216A
57
MCI16060CCU216A
60
Note: Sound level is measured at a point 1 m in front of the unit, at a height of (Unit body height +1)/2 m.

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
19
8. Exploded View
No.
Part Name
Qty
No.
Part Name
Qty
1
Cover net
1
11.3
Gas outlet pipes welded assy
1
2
Outdoor motor
1
11.3.1
Gas outlet pipe
1
3
Axial-flow fan
1
11.3.2
Gas concentration filter pipe
1
4
Top cover assy
1
12
Cooler cover
1
5
Support board
3
13
Electronic components
1
6
Refrigenrant cooling tubes assy
1
13.1
Terminal block
1
7
Top panel
1
13.2
Outdoor display board
1
8
Compressor
1
13.3
Outdoor integrated E-board
1
9
Chassis assy
1
13.4
Reactor
1
10
Bottom side panel
1
13.5
Inserted fan motor capacitor
1
11
Refrigerant flow tubes assy
1
13.6
E-parts installation board welded assy
1
11.1
High pressure valve welded assy
1
13.7
Main control board installation base
1

R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
20
11.1.1
High pressure valve connecting pipe
1
13.8
Communication board installation base
1
11.1.2
Square valve
1
13.9
Terminal block installation board
1
11.2
Low pressure valve welded assy
1
14
Reactor installation lid
1
11.2.1
Square valve
1
15
Condenser
1
11.2.2
Low pressure valve connecting pipe
1
16
Outdoor unit protecting net
1
9. Troubleshooting
The fault codes for outdoor unit as follows:
CODE
FAULT DESCRIPTION
E4
T4 Outdoor ambient temperature sensor error
E5
T5 Discharge temperature sensor error
E6
T3 Condenser temperature sensor error
E9
AC under voltage protection
E10
EEPROM error
E12
IPM modular sensor error
E13
HLP Pressure sensor error
E14
T3 or T5 sensor disconnect error
E15
High pressure switch error
H0
Communication error of main chip and IPM chip
H1
T3 sensor high temperature error(In cooling mode) (20 times P5 error within 180mins)
H2
High pressure switch error(20 times P1 error within 150 mins)
H3
High pressure abnormal in heating mode (20 times P13 error within 180 mins)
H4
IPM modular high temp error (20 times P8 within 120 mins)
H5
Low pressure error (20 times P2 within 100 mins)
This manual suits for next models
5
Table of contents
Other McQuay Fan manuals