MDT AMI series User manual

MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
1
6/2014
Technical Manual
MDTSwitchActuators
withcurrentmeasurement
AMI/AMSR2.x
(2
nd
HardwareRevision)

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
2
1Content
1Content.................................................................................................................................................2
2Overview.............................................................................................................................................4
2.1Overviewdevices...........................................................................................................................4
2.2Exemplarycircuitdiagrams...........................................................................................................5
2.3Structure&Handling.....................................................................................................................6
2.4Functions.......................................................................................................................................7
2.4.1Overviewfunctions.................................................................................................................7
2.5.SettingsattheETS‐Software........................................................................................................8
2.6.Startingup....................................................................................................................................8
3Communicationobjects........................................................................................................................9
3.1Communicationobjectsperchannel.............................................................................................9
3.2Centralcommunicationobject....................................................................................................10
3.3CommunicationObjectscurrentmeasurement..........................................................................11
3.4Defaultsettingsofthecommunicationobjects..........................................................................12
4ReferenceETS‐Parameter..................................................................................................................13
4.1GeneralSettings..........................................................................................................................13
4.2Channelselection........................................................................................................................14
4.3Identicalparameter.....................................................................................................................15
4.3.1Relayoperatingmode..........................................................................................................15
4.3.2Centralfunction....................................................................................................................16
4.3.3Behavioratblock/unblock....................................................................................................16
4.3.4Behavioratbuspowerup/down..........................................................................................18
4.3.5Manualcontrolandcyclicsendofthecurrentstate...........................................................19
4.4Switchingoutput.........................................................................................................................20
4.4.1Overview...............................................................................................................................20
4.4.2On/Offdelay
.........................................................................................................................22
4.4.3Logicalfunctions...................................................................................................................23
4.4.4Scenefunction......................................................................................................................25
4.5Staircase......................................................................................................................................30
4.5.1Overview...............................................................................................................................30
4.5.2Staircasetime.......................................................................................................................32
4.5.3PrewarningundWarning.....................................................................................................33
4.5.4Manualswitchoff.................................................................................................................34
4.5.5Extendstaircasetime...........................................................................................................34

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
3
4.6Currentmeasurement.................................................................................................................35
4.6.1Generalsettings....................................................................................................................35
4.6.2Powermeterfunction..........................................................................................................37
4.6.3Totalcurrentmeasurement.................................................................................................38
4.6.4Totalpowermeterfunction.................................................................................................39
4.6.5Monitoringexceedance/deviationofload...........................................................................40
4.6.6Faultcurrent/Loadfailure...................................................................................................42
4.7Operatinghours...........................................................................................................................43
4.7.1Operatinghourscounter......................................................................................................43
4.7.2Reversecounter...................................................................................................................44
5Index...................................................................................................................................................46
5.1Registerofillustrations................................................................................................................46
5.2Listoftables.................................................................................................................................47
6Attachment.........................................................................................................................................48
6.1Statutoryrequirements...............................................................................................................48
6.2Routinedisposal..........................................................................................................................48
6.3Assemblage..................................................................................................................................48
6.4Groupstate..................................................................................................................................49
6.5Datasheet....................................................................................................................................50

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
4
2Overview
2.1Overviewdevices
Themanualreferstothefollowingdevices,whichareinourassortmentofswitchactuators.Actually
wecanofferyouthefollowingswitchactuators(OrderCoderespectivelyprintedinboldtype,
HardwarerevisonR2.x):
AMS‐0416.01Switchingactuator4‐fold,4TE,230VAC,16A,C‐Load100µF,standarddesign
o4TEREG,230VAC,16A,C‐Load100uF,withcurrentmeasurement
AMS‐0816.01Switchingactuator8‐fold,8TE,230VAC,16A,C‐Load100µF,standarddesign
o8TEREG,230VAC,16A,C‐Load100uF,withcurrentmeasurement
AMS‐1216.01Switchingactuator12‐fold,4TE,230VAC,16A,C‐Load100µF,standarddesign
o12TEREG,230VAC,16A,C‐Load100uF,withcurrentmeasurement
AMI‐0416.01Switchingactuator4‐fold,4TE,230VAC,16A,C‐Load200µF,industrialdesign
o4TEREG,230VAC,16A,C‐Load200uF,withcurrentmeasurement
AMI‐0816.01Switchingactuator8‐fold,8TE,230VAC,16A,C‐Load200µF,industrialdesign
o8TEREG,230VAC,16A,C‐Load200uF,withcurrentmeasurement
AMI‐1216.01Switchingactuator12‐fold,8TE,230VAC,16A,C‐Load200µF,industrialdesign
o12TEREG,230VAC,16A,C‐Load200uF,withcurrentmeasurement

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
5
2.2Exemplarycircuitdiagrams
Figure1:ExemplarycircuitdiagramAMS‐0816.01
Figure2:ExemplarycircuitdiagramAMI‐1216.01

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
6
2.3Structure&Handling
Theswitchactuators(here:AKI1216.01)containofonestatusLEDperchannel.ThisLEDindicates
thestateofthedependingoutput.Furthermoreeveryoutputcanbeswitchedmanual,independent
ofthecurrentparameterization.ThelinesAKSandAKIhavebuttonsforeverychannel.Incontrast
thelineoftheAKKhasonlyfourbuttons,independenttothenumberofchannels.Twobuttonsare
forchoosingthechannel,wherebythechosenchannelisindicatedbyaflashingstatusLED.The
buttonsupanddownareforswitchingthechannelonandoff.Theprogrammingbuttonactivates
theprogrammingfunction.AnactivatedprogramingfunctionisindicatedbyalitprogrammingLED.
Figure3:Overviewhardwaremoduleswitchactuator(e.g.AMI‐1216.01)
ThelinesAMSandAMIhavebistablerelays.Atthebistablerelaysthecurrentswitchingstatealso
staysincaseofabreakdownofthe230Vauxiliaryvoltageandatanupdateoftheparameterization.

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
7
2.4Functions
Allofthechannelshaveidenticalfunctions(havealookatthefunctionaloverview).Thenumbersof
channelsdependstothehardwaredesign,whichcanhave2,4,8,12or16channels.The
identificationisstandardlyinconsecutivealphabeticorder.
Thereare3differentstatesforeverychannelpossible:
notactive
Thechannelhasnofunction.Sotherearenocommunicationobjectsforthischannelshown.
Switch
Ifthechannelischosenasswitch,therewillbedifferentparameterizationoptionsfor
configuringtheswitchingprocess.
Staircase
Now,thechannelcanbecomeastaircaselightfunction.Thisfunctioncausesanautomatic
switchoffofthechannelafteranadjustedtime.
2.4.1Overviewfunctions
GroupoffunctionsFunctions
Resetbehaviorbehavioratbuspowerbreakdown
behavioratbuspowerup
startuptimeout
Relaymodenormallyclosed/normallyopened
Switchfunctionsswitching
centralswitchingfunction
Timefunctionson‐delay
off‐delay
Staircaselightfunctionstimeforstaircase
pre‐warning(withadjustablewarningandpre‐
warningtime)
manualoff
retriggerableon/off
Superiorfunctionsblockingfunction
logicfunctions(AND/OR)
Scenesscenefunctionforupto8scenesperchannel
Statusfunctionsfeedbackfunction
cyclicsendable“operating‐state”telegram
groupstateofallchannels
Currentmeasurementsinglecurrentmeasurementofeachchannel
warninganderrormessagesadjustable
totalcurrentmeasurementofthewholedevice
Electricmeterfunctionscountingofthecurrentconsumptionofevery
channel
countingofthecurrentconsumptionofthe
wholeactuator
Operatinghourscounterforwardcounteroftheoperatinghours
backcountertonextservicetime
Table1:Overviewfunctions

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
8
2.5.SettingsattheETS‐Software
Selectionattheproductdatabase:
Manufacturer:MDTTechnologies
Productfamily:Actuator
Producttype:SwitchActuators
MediumType:TwistedPair(TP)
Productname:addictedtotheusedtype,e.g.:AMI‐0816.01switchactuator8‐fold,8TE,16A
Ordernumber:addictedtotheusedtype,e.g.:AKI‐0816.01
2.6.Startingup
Afterwiring,theallocationofthephysicaladdressandtheparameterizationofeverychannelfollow:
(1) Connecttheinterfacewiththebus,e.g.MDTUSBinterface
(2) Switchingthepowersupply
(3) Setbuspowerup
(4) Presstheprogrammingbuttonatthedevice(redprogrammingLEDlights)
(5) LoadingofthephysicaladdressoutoftheETS‐Softwarebyusingtheinterface(redLEDgoes
out,aswellthisprocesswascompletedsuccessful)
(6) Loadingoftheapplication,withrequestedparameterization
(7) Ifthedeviceisenabledyoucantesttherequestedfunctions(alsopossiblebyusingtheETS‐
Software)

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
9
3Communicationobjects
3.1Communicationobjectsperchannel
Thecommunicationobjectsperchannelaredisplayed,whentheyareactivatedtroughthe
parameterization.Thereare8numbersreservedforeverychannel,evenifnotallofthemareneed.
Sothefirstchannelhasthenumbersfrom0to7,thesecondfrom8to15andsoon.The
communicationobjectsareneedfortheconnectiontothegroupaddressesandtoprogramyour
project.
ThefollowingillustrationshowsthecommunicationobjectsforthechannelsAandB.ChannelAis
selectedasswitch.Logicfunctions,blockingobjectandscenesareactivated.ChannelBisselectedas
staircase.Onlytheblockingfunctionisactivated:
Figure4:Communicationobjectsperchannel(ChannelA–switch;ChannelB–staircase)
Thefollowingcommunicationobjectscanbeshownforachannelselectedasswitch:
Nr.FunctionUsageDatatype
0Switchon/offswitchesthechannelon/offDPT1.001In,Write
2BlockblocksthechannelDPT1.001In,Write
4ScenecallsactivatedscenesDPT18.001In,Write
5StatusfeedbackfunctionDPT1.001Out,Read
6Logic1onlyshownatactivatedlogicfunctionDPT1.001In,Write
7Logic2onlyshownatactivatedlogicfunctionDPT1.001In,Write
+18nextchannel
Table2:Communicationobjects“switch”

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
10
Thefollowingcommunicationobjectscanbeshownforachannelselectedasstaircase:
Nr.FunctionUsageDatatype
1Staircaseswitchesthestaircasefunctionon/offDPT1.001In,Write
2BlockblocksthechannelDPT1.001In,Write
5StatusfeedbackfunctionDPT1.001Out,Read
+18nextchannel
Table3:Communicationobjects“staircase”
3.2Centralcommunicationobject
Thecentralfunctionsarealwaysshownalsoiftheyarenotusedinanyofthechannels.The
communicationobjectsforthecentralfunctionsareatthebottomofthecommunicationobjects.
Theyhavealwaysthefirstnumberafterthecommunicationobjectsforthechannels.
Everychannelcanbeparameterizedwhetheritshallbeeffectedofthecentralfunctionsornot.
Thefollowingcommunicationobjectexistsonlyonceandisforchannels:
Nr.FunctionUsageDatatype
Switchon/offcentralswitchingfunctionDPT1.001In,Write
OperatingsendscycliciftheactuatoranswersatthebusDPT1.001Out,Send
GroupStatesendsthestateofallchannelsDPT4.001Out,Send
ManualControlblocksthemanualcontrolDPT1.001In,Write
Table4:Centralcommunicationobject

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
11
3.3CommunicationObjectscurrentmeasurement
Thefollowingcommunicationobjectsareavailableforthecurrentmeasurementandcountingofthe
operatinghours:
Nr.FunctionUsageDatatype
8Responseoperating
hours
reportscountedoperatinghoursDPT7.007Out,Read
8TimetothenextservicereportstimetothenextserviceDPT7.007Out,Read
9ResetoperatinghoursresetscounterfortheoperatinghoursDPT1.001In,Write
9ResetserviceresetsthecounterfortheservicetimeDPT1.001In,Write
10 ServicerequiredreportsrequiredmaintenanceDPT1.001Out,Read
11Currentvaluereportstheactualcurrent
consumptionofthechannel
DPT7.012/
DPT9.021/
DPT14.019/
DPT9.024
Out,Read
12ExceedanceofloadreportsanexceededloadDPT1.001Out,Read
13LowerdeviationofloadreportsanunderrangedloadDPT1.001Out,Read
14FaultcurrentreportsafaultcurrentDPT1.001Out,Read
14LoadfaultyreportsafaultoftheloadDPT1.001Out,Read
14Faultcurrent/Loadfaultyreportsafaultcurrentandafaultof
theloadDPT1.001Out,Read
15Resetpowermeterresetsthecalculatedenergyofthe
channelDPT1.001In,Write
16Activeenergysendsthecalculatedenergyofthe
channel
DPT13.010/
DPT13.013
Out,Read
+18nextchannel
75/147Totalactiveenergysendsthesumofthecalculated
energy
DPT13.010/
DPT13.013
Out,Read
76/148Valueoftotalcurrentreportsthetotalcurrentofall
activatedchannels
DPT9.021/
DPT14.019/
DPT9.024
Out,Read
77/149Exceedanceoftotal
current
reportsanexceededloadofall
activatedchannelsDPT1.001Out,Read
Table5:Communicationobjectscurrentmeasurement
Thesizesaswellasthetypeoftheshownobjectsdependstotheadjustedparameterization,havea
lookattherelevantexplanationsatsection4.
Thereareobjectsforthecurrentmeasurementofthesinglechannelsaswellasforthetotalcurrent
measurementoftheactuator.Itcanbeadjustedwhetherachannelshallbeincludedtothetotal
currentmeasurementornot.

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
12
3.4Defaultsettingsofthecommunicationobjects
Thefollowingchartshowsthedefaultsettingsofthecommunicationobjects:
Defaultsettin
g
s
Nr.NameObjectFunction Length PriorityCRW T U
0ChannelAswitchon/off 1Bit LowX X
1ChannelAStaircase1Bit LowX X
2ChannelABlock1Bit LowX X
4ChannelAScene1Byte LowX X
5ChannelAStatus1Bit LowXXX
6ChannelALogic11Bit LowX X
7ChannelALogic21Bit LowX X
8ChannelAResponseoperatinghours 2Byte LowXXX
8ChannelATimetothenextservice 2Byte LowXXX
9ChannelAResetoperatinghours 1Bit LowX X
9ChannelAResetservice 1Bit LowX X
10ChannelAServicerequired 1Bit LowXXX
11ChannelACurrentvalue 2Byte LowXXX
11ChannelAExceedanceofload 4Byte LowXXX
12ChannelALowerdeviationofload 1Bit LowXXX
13ChannelAFaultcurrent 1Bit LowXXX
14ChannelALoadfaulty 1Bit LowXXX
14ChannelAFaultcurrent/Loadfaulty 1Bit LowXXX
14ChannelAResetservice 1Bit LowXXX
15ChannelAResetpowermeter 1Bit LowX X
16ChannelAActiveenergy 4Byte LowXXX
+8nextchannel
72/144CentralfunctionOperating 1Bit LowXXX
73/145CentralfunctionGroupstate 4Byte LowXXX
74/146CentralfunctionManualcontrol 1Bit LowX X
75/147CentralfunctionTotalactiveenergy 4Byte LowXXX
76/148CentralfunctionValueoftotalcurrent LowXXX
77/149CentralfunctionExceedanceoftotalcurrent 1Bit LowXXX
78/150Centralfunctionswitchon/off 1Bit LowX X
Table6:Communicationobjects–defaultsettings
Youcanseethedefaultvaluesforthecommunicationobjectsfromtheupperchart.Accordingto
requirementsthepriorityoftheparticularcommunicationobjectsaswellastheflagscanbe
adjustedbytheuser.Theflagsallocatesthefunctionoftheobjectsintheprogrammingthereby
standsCforcommunication,RforRead,Wforwrite,TfortransmitandUforupdate.

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
13
4ReferenceETS‐Parameter
4.1GeneralSettings
Thefollowingparameterexistsonlyonceandaffectstoallchannels:
Figure5:Generalsettings
Theparameterstartuptimeoutadjuststhetimebetweenanuploadandthefunctionalstartofthe
device.Theusedhardwarereactsonlyafterexpirationoftheadjustedtime.Allinputcommands
beforethestartuptimeoutexpire.Furthermorean“Operating”telegramandatelegramforthe
groupstatecanbeactivated.The“Operating”telegramsendscyclicwhethertheactuatoranswersat
thebusornot,sothedebuggingofgreaterobjectsbecomemucheasier.Thegroupstatesendsthe
stateofallchannelsas4Bytetelegram,whichcanbeusedforvisualizations.
Thefollowingchartshowsthedynamicrangeofthisparameter:
ETS‐textDynamicrange
[defaultvalue]
comment
Startuptimeout1‐60s
[1s]
Timebetweenanuploadandthe
functionalstartofthedevice
Cyclicsendof“Operating”‐
Telegram
nosend,10min,30min,1h,
3h,6h,12h,24h
activatesthecyclicsendingofthe
“Operating”telegramifthe
actuatoranswersatthebus
Sendgroupstatenotactive,onrequest,on
changes,onchangesandcyclic
5min/19min/30min/1h/2h/
4h
sendsthestatesofallchannelsas
4Bytetelegram
Totalcurrentactive
notactive
activatesthetotalcurrent
measurement,havealookat
chapter4.6.2totalcurrent
Table7:Generalsettings
Thefollowingchartshowstherelevantcommunicationobjects:
NumberNameLength Usage
Operating1Bitsendscyclic,iftheactuatorisatthebus
Groupstate4Bytesendsthestateofallchannels
Table8:Communicationobjectsgeneralfunctions

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
14
4.2Channelselection
Thefollowingillustrationshowsthemenuforselectingthechannels:
Figure6:Channelselection
Thereare3possiblestatesforeverychannel,whichcanbeadjustedatthemenu“channel
preselection”.Thefollowingparameterizationaccordstothechosenstateofachannel.Butifyou
chosseachannelas“notactive”,therewillbenofurtherparameterizationoptionsavailable.
Thechartshowsthesettingoptionsforevereychannel:
ETS‐textDynamicrange
[defaultvalue]
comment
ChannelA‐[O]notactive
Switch
Staircase
Operatingmodeofthe
channels
Table9:Channelselection

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
15
4.3Identicalparameter
Thefollowingparameters,whicharedescribedattheheadings4.3.x,areaswellavailableat
channelsselectedasswitchasatchannelsselectedasstaircase.
4.3.1Relayoperatingmode
Thefollowingillustrationshowsthesettingoptionsforthisparameter:
Figure7:Operatingmode
Thefollowingchartshowsthedynamicrangeforthisparameter:
ETS‐textDynamicrange
[defaultvalue]
comment
Modenormallyopened
normallyclosed
Relayoperatingmodeofthe
channel
Table10:Operatingmode
Thefollowingdiagramshowsthebehavioroftherelayoperatingmodenormallyclosedandnormally
opened.TheinputforthechannelsisaKNX‐telegram,whichsendsalternating0‐signalsand1‐signals:

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
16
4.3.2Centralfunction
ThefollowingillustrationshowsthesettingoptionsattheETS‐Software:
Figure8:Centralfunction
Thefollowingchartshowsthedynamicrangeforthisparameter:
ETS‐textDynamicrange
[defaultvalue]
comment
Centralfunctionnotactive
active
switchesthecentralfunction
on/offforthischannel
Table11:Centralfunction
Thecentralfunctioncanbeswitchedon/offforeverychannel.Forswitchingonthisfunction,you
havetochoosetheoption“active”.Bycallingthecentralcommunicationobject,allchannelswithan
activatedcentralfunctionareswitchedonwiththeircurrentparameterization.Soswitch‐ondelays
orstaircasefunctionsarestillkept.
Thecentralfunctioncanmakeprogrammingmuchmoreeasierandyourprojectcanbecomemore
clear.
Thefollowingchartshowstheassociatedcommunicationobject:
NumberNameLength Usage
Centralfunction1Bitcentralswitchingofthechannels
numberdependstothenumberofchannels
Table12:Communicationobjectcentralfunction
4.3.3Behavioratblock/unblock
ThefollowingillustrationshowsthesettingoptionsattheETS‐Software:
Figure9:Blockingfunction
Thefollowingchartshowsthedynamicrangeforthisparameter:
ETS‐textDynamicrange
[defaultvalue]
comment
Behaviorwhenlocked
Behaviorwhenunlocked
On
Off
nochange
Behaviortoa
blocking/unblockingprocess
Table13:Behavioratblock/unblock

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
17
Theblockingfunctiongetsactive,whenthecorrespondingcommunicationobjectbecomesalogical
“1”.Bysendingalogical“0”,theblockingfunctioncanbedeactivatedagain.
Theparameter“Behaviorwhenlocked”definesanactionfortheoutputatactivatingtheblocking
process.Therearethesettingon,offandnochangeavailable.Thesamesettingsarealsoavailable
forthe“Behaviorwhenunlocked”.Thisactioniscalledwhentheblockingfunctionisdeactivated
again.
Thefollowingchartshowsthecorrespondingcommunicationobject:
NumberNameLength Usage
2Block1Bitblocksthechannel
Table14:Communicationobjectblockingfunction
Thefollowingdiagramdescribestheblockingprocess.Forthe“Behaviorwhenlocked”,theactionon
wasparameterizedandforthe“Behaviorwhenunlocked”theactionoffwasparameterized:
TheKNXtelegramshowswhichvaluesaresendtotheblockingobject.Bysendingalogical“1”,the
blockingfunctionisactivatedandthechannelisswitchedon.Theblockingfunctionisdeactivated
againbysendingalogical“0”.Sothechannelisswitchedoff.

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
18
4.3.4Behavioratbuspowerup/down
ThefollowingillustrationshowsthesettingoptionsattheETS‐Software:
Figure10:Behavioratbuspowerup/down
Thefollowingchartshowsthedynamicrangeforthisparameter:
ETS‐textDynamicrange
[defaultvalue]
comment
Behavioratbuspowerup/
Behavioratbuspowerdown
On
Off
nochange
Adjustment,howthechannel
shallreactincaseofabus
powerbreakdown/return
Table15:Behavioratbuspowerup/down
Everychannelcanoccupyacertainstateaswellincaseofabuspowerbreakdownasincaseofabus
powerreturn.Thechannelcanbeswitchedofforon,butalsostayinitscurrentstatebychoosing
theparameter“nochange”.
Toavoidproblemsincaseofabuspowerbreakdown,youshouldadjustthisparametervery
conscientious.Becausethereisnocontrollingpossibleaslongasthebuspowerisdown.

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
19
4.3.5Manualcontrolandcyclicsendofthecurrentstate
Thefollowingillustrationshowstheavailablesettingsforthemanualcontrolandthecyclicsending:
Figure11:Manualcontrolandcyclicsend
Thefollowingchartshowsthedynamicrangeforthisparameter:
ETS‐textDynamicrange
[defaultvalue]
comment
Manualcontrolactive
notactive
activateviaobject
(Value1=notactive)
activatesordeactivatesthe
manualcontrol,also
switchableviathecentral
object„manualcontrol“
Sendcyclicthecurrentstate
value
nosendcyclic
5min
10min
20min
30min
1h
2h
4h
activatesthecyclicsendofthe
currentvalue
Ifactivated,thecurrentstate
willbesendcyclicatthe
adjustedtimestepsviathe
objectChannelX:state
Table16:Manualcontrolandcyclicsend
Themanualcontrolcanbeactivatedordeactivatedpermanentforeachchannel,bythesettings
“active”or“notactive”.Additionalthemanualcontrolcanbeblockedorenabledviathecentral
object“manualcontrol”.Thereisonlyonecentralobjectforeverychannel.Thisobjectblocksthe
manualcontrol,byalogical“1”,ateverychannelwiththesetting“activateviaobject”.
Thesetting“Sendcyclicthecurrentstatevalue”activatesthecyclicsendofthestateofthechannel
viaitsstatusobject.
Thefollowingchartshowstherelevantcommunicationobjects:
NumberNameLength Usage
5State1BitStatusobjectforthecorrespondingchannel
Manualcontrol1Bitblocksthemanualcontrolinthechannelswith
activatedfunction
Table17:Communicationobjectsmanualcontrolandcyclicsend

TechnicalManualSwitchActuatorsAMI/AMS
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
20
4.4Switchingoutput
Thefollowingparameters,whicharedescribedattheheadings4.4.x,areonlyavailableatchannels
selectedasswitch.
4.4.1Overview
Bychoosingachannelasswitch,asubmenu,calledChannelASwitching,appearsforthischannelat
theleftdropdownmenu.
Thesubmenuisshownatthefollowingillustration:
Figure12:Switchingoutput
This manual suits for next models
7
Table of contents
Other MDT Controllers manuals
Popular Controllers manuals by other brands

Pinnacle Systems, Inc.
Pinnacle Systems, Inc. NSD-TR-01 Installation and operation manual

Zennio
Zennio ZN1DI-RGBX4 quick start guide

Weir
Weir Hopkinsons Fig 9052 Standard Operating & Maintenance Instructions

Philips
Philips NOA0025 manual

Huawei
Huawei SmartACU2000B quick guide

LOVATO ELECTRIC
LOVATO ELECTRIC ATL 601 installation manual