3Specifications
Specifications TM200
Specifications are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.
Environment
Application field The instrument is intended for use
in medium-voltage substations and
industrial environments.
Altitude <2000 m (6500 ft) above
sea level.
Temperature
Operating 0°C to +50°C (32°F to +122°F)
Storage & transport -20°C to +70°C (-4°F to +158°F)
Humidity 5% – 95% RH, non-condensing
CE-marking
LVD 2006/95/EC
EMC 2004/108/EC
General
Power supply 5 V DC
via separate adapter
Input: 100 / 240 V AC, 50 /60 Hz
Output: 5.0 V DC, 2.40 A
Dimensions
Instrument, excl. handle 194 x 115 x 49 mm
(7.7” x 4.5” x 1.9”)
Instrument, incl. handle 252 x 132 x 49 mm
(9.9” x 5.2” x 1.9”)
Weight 1.0 kg (2.2 lbs)
2.8 kg (6.2 lbs) with accessories and
carrying case
Test lead set, with touch-
proof contacts
4 x 2 m (6.6 ft), 2.5 mm²
Measurement section
Range 0-999.999 s
Resolution 1 ms
Inaccuracy ±0.02% + 1 digit of displayed value
Timer inputs
Input voltage 250 V AC/DC (max)
Voltage mode
Parameter Min Max Unit
Threshold level, Positive at red terminal 820 V DC
Threshold level, Negative at red terminal -20 -8 V DC
Input current at threshold level
Positive at red terminal
0.7 2.0 mA DC
Input current at threshold level
Positive at black terminal
412 mA DC
Threshold level, low to high, 50 Hz 515 V ACRMS
Threshold level, high to low, 50 Hz 15 45 V ACRMS
Contact mode
Parameter Min Max Unit
Closed contact detection 0 1 kΩ
Open contact detection 4 - kΩ
Open circuit voltage 17 20 V DC
Short circuit current 813 mA DC
Input current at maximum input voltage, inrush
Parameter Max Unit
At 250 V DC, Positive at red terminal 8mA DC
At 250 V DC, Positive at black terminal 150 mA DC
At 250 V AC 80 mA DC
Input current at maximum input voltage, continuous
Parameter Max Unit
At 250 V DC, Positive at red terminal 8mA DC
At 250 V DC, Positive at black terminal 12 mA DC
At 250 V AC 15 mA DC
6TM200 ZP-BE02E BE0058JE
3 SPECIFICATIONS