Micno 3kW DC24V User manual

USER MANUAL
3.5KW/5.5KW
SOLARE INVERTER/CHARGER

Contents
ABOUT THIS MANUAL................................................................................................................................................................ 1
Purpose.............................................................................................................................................................................. 1
Scope ................................................................................................................................................................................. 1
SAFETY INSTRUCTIONS .............................................................................................................................................................. 1
INTRODUCTION ......................................................................................................................................................................... 2
Features ............................................................................................................................................................................. 2
Basic System Architecture ................................................................................................................................................. 2
Product Overview.............................................................................................................................................................. 3
INSTALLATION ............................................................................................................................................................................ 4
Unpacking and Inspection ................................................................................................................................................. 4
Preparation........................................................................................................................................................................ 4
Mounting the Unit............................................................................................................................................................. 4
Battery Connection............................................................................................................................................................ 5
AC Input/Output Connection............................................................................................................................................. 7
PV Connection ................................................................................................................................................................... 8
Final Assembly ................................................................................................................................................................. 10
Communication Connection............................................................................................................................................ 10
OPERATION.............................................................................................................................................................................. 11
Power ON/OFF................................................................................................................................................................. 11
Operation and Display Panel ........................................................................................................................................... 11
LCD Display ICONS ........................................................................................................................................................... 12
LCD Setting....................................................................................................................................................................... 14
Fault Reference Code....................................................................................................................................................... 19
Warning Indicator............................................................................................................................................................ 19
Operating Mode Description........................................................................................................................................... 20
Display Setting ................................................................................................................................................................. 22
SPECIFICATIONS ....................................................................................................................................................................... 23
Table 1 Line Mode Specifications .................................................................................................................................... 23
Table 2 Inverter Mode Specifications .............................................................................................................................. 24
Table 3 Charge Mode Specifications................................................................................................................................ 24
Table 4 General Specifications......................................................................................................................................... 25
Trouble shooting...................................................................................................................................................................... 26
Appendix: Approximate Back-up Time Table........................................................................................................................... 26

1
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual
carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
The following cases are not within the scope of warranty.
1. Out of warranty.
2. Series number was changed or lost.
3. Battery capacity was declined or external damaged.
4. Inverter was damaged caused by transport shift, remissness, etc external factor
5. Inverter was damaged caused by irresistible natural disasters.
6. Not in accordance with the electrical power supply conditions or operate environment caused damage.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual
for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit the batteries and all appropriate
sections of this manual.
2. CAUTION --To reduce risk of injury charge only deep-cycle lead acid type rechargeable batteries. Other types of
batteries may burst, causing personal injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect
re-assembly may result in a risk of electric shock or fire.
4. To reduce risk of electric shock, disconnect all wires before attempting any maintenance or cleaning. Turning off the unit
will not reduce this risk.
5. CAUTION --Only qualified personnel can install this device with battery.
6. NEVER charge a frozen battery.
7. For optimum operation of this inverter/charger; please follow required spec to select appropriate cable size. It is very
important to correctly operate this inverter/charger.
8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or
short circuit batteries or other electrical parts and could cause an explosion.
9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to
INSTALLATION section of this manual for the details.
10. Fuses (1 piece of 150A, 63VDC for 3kW~ 5kW) are provided as over-current protection for the battery supply.
11. GROUNDING INSTRUCTIONS- This inverter/charger should be connected to a permanent grounded wiring system. Be
sure to comply with local requirements and regulation to install this inverter.
12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following trouble
shooting table, please send this inverter/charger back to local dealer or service center for maintenance.

2
INTRODUCTION
This is a multi-function inverter/charger; combining functions of inverter; solar charger and battery charger to offer
uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and
easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage
based on different applications.
Features
Pure sine wave inverter
Configurable input voltage range for home appliances and personal computers via LCD setting
Configurable battery charging current based on applications via LCD setting
Configurable AC/Solar Charger priority via LCD setting
Compatible to mains voltage or generator power
Auto restart while AC is recovering
Overload/ Over temperature/ short circuit protection
Smart battery charger design for optimized battery performance
Cold start function
Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also include following devices to have a
complete running system:
Generator or Utility
PV modules (option)
Consult with your system integrator for other possible system architectures depending on your requirements.
Figure 1 Hybrid Power System

3
Product Overview
1. LCD display 2. Line indicator 3. INV indicator 4. Battery indicator
5. Fault indicator 6. Function button 7. RS232 port 8. USB port
9. AC input 10. AC output 11. PV input 12. Battery input
13. Input over current protection 14. Parallel communication port (only for models with parallel function)
15. Power on/off switch 16. Installation kit

4
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received
the following items inside of package:
The unit x 1
User manual x 1
Preparation
Before connecting all wires, please
Remove two screws as shown below.
Mounting the Unit
Consider the following points before selecting where to install:
1. Do not mount the inverter on flammable construction materials.
2. Mount on a solid surface.
3. Install this inverter at eye level in order to allow the LCD display
to be read at all times.
4. For proper air circulation to dissipate heat, allow a clearance of
approx. 200 mm to the side and approx. 300 mm above and below
the unit.
5. The ambient temperature should be between 0c and 55℃to
ensure optimal operation.
6. The recommended installation position is to be adhered to
the wall vertically.
7. Be sure to keep other objects and surfaces as shown in the
diagram to guarantee sufficient heat dissipation and to have
enough space for removing wires.

5
SUITABLE FOR MOUNTING ON CONCRETE OROTHER
NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing four screws.
Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or
disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications,
however, it is still requested to have over-current protection installed. Please refer to typical amperage in below table as
required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNINGI It's very important for system safety and efficient operation to use appropriate cable for battery connection.
To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Ring terminal:
Recommended battery cable and terminal size:
Model
Typical Amperage
Wire Size
Cable mm2
Ring Terminal
Torque Value
Dimensions
D (mm)
L (mm)
3kW DC24V
118A
1*2AWG
38
8.4
39.2
5Nm
3kW DC48V
71A
1*6AWG
14
8.4
39.2
5kW DC48V
118A
1*2AWG
38
8.4
39.2

6
Please follow below steps to implement battery connection:
1. Assemble battery ring terminal based on recommended battery cable and terminal size.
2. Connect all battery packs as units requires. It's suggested to connect at least 200Ah capacity battery for 3kW~5kW
model.
3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened
with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly connected and ring
terminals are tightly screwed to the battery terminals.

7
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal.
Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
CAUTION!!Before making the final DC connection or closing DC breaker/dis-connector; be sure positive (+)
must be connected to positive (+) and negative (-) must be connected to negative (-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC
input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected
from over current of AC input. The recommended spec of AC breaker is 32A for 3kW and 50A for 5kW.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do not invert input and output
connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection,
lb reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model
Gauge
Torque Value
3KW DC24V
12 AWG
1.2~ 1.6Nm
3KW DC48V
12 AWG
1.4~ 1.6Nm
5KW DC48V
10 AWG
1.4~ 1.6Nm
Please follow below steps to implement AC input/output connection:
1. Before making AC input/output connection, be sure to open DC protector or dis-connector first.
2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to
connect PE protective conductor @ ) first.
4. PEGround(Yellow -Green)
5. LLine(brown or black)
6. NNeutral(blue)

8
WARNING:
Be sure to that AC power source is disconnected before attempting to hard-wire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to
connect PE protective conductor @ )first.
PEGround(Yellow -Green)
LLine(brown or black)
NNeutral(blue)
5. Make sure the wires are securely connected.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility
short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it is required to have
enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will
cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air
conditioner if it is equipped with time-delay function before installation. Otherwise, this inverter/charger will trig
overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air
conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV
modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection.
To reduce risk of injury; please use the proper recommended cable size as below.
Model
Typical Amperage
Cable Size
Torque
3kW
60A
8AWG
2.0-2.4 Nm
5kW
80A
8AWG
2.0-2.4 Nm
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
3. Max. Power Voltage (Vmpp) of PV modules should be close to best Vmp of inverter or within Vmp range to get best
performance. If one PV module can not meet this requirement, it's necessary to have several PV modules in series

9
connection. Refer to below table.
Note:* Vmp: panel max power point voltage.
The PV charging efficiency is maximized while PV system voltage is close to Best Vmp.
Maximum PV module numbers in Series: Vmpp of PV module*X pcs = Best Vmp of Inverter or Vmp range
PV module numbers in Parallel: Max. charging current of inverter/Impp
Total PV module numbers=maximum PV module numbers in series*PV module numbers in parallel.
Solar Charging Mode
INVERTER MODEL
3KW DC24V
3KW DC48V
5KW DC48V
Rated Power
3000W
3000W
5000W
MPPT charger
solar charging current
60A
80A
80A
Max.PV Array Power
1500W
5500W
Max. PV Array Open Circuit Voltage
145Vdc
450Vdc
PV Array MPPT Voltage Range
30~115Vdc
120~430Vdc
Min. battery voltage for PV charge
30Vdc
120Vdc
AC INPUT charger
AC charging current
60A
80A
80A
Operating Voltage Range
90~280Vac
PV module configuration
Recommended module specification
Maximum Power (Pmaxl)
250W
Max. Power Voltage Vmpp(V)
30.9V
Max. Power Current Impp(A)
8.42A
Open Circuit Voltage Voc(V)
37.7V
Short Circuit Current Isc(A)
8.89A
Recommended PV module configuration
Model
Solar Input
Qty of Panels
Total Input Power
3000W DC24V
3 pcs in series and 2 set in parallel
6 pcs
1500W
3000W DC48V
5000W DC48V
6 pcs in series
6 pcs
1500W
8 pcs in series
8 pcs
2000W
12 pcs in series
12 pcs
3000W
13 pcs in series
13 pcs
3250W
8 pcs in series and 2 set in parallel
16 pcs
4000W
10 pcs in series and 2 set in parallel
20 pcs
5000W
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors
2. Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+)of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection cable
to negative pole (-) of PV input connector.

10
3. Make sure the wires are securely connected.
Final Assembly
After connecting all wires, please put bottom cover back by screwing two screws as shown below.
Communication Connection
Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and follow
on-screen instruction to install the monitoring software. For the detailed software operation, please check user manual of

11
software inside of CD.
WARNING: It is forbidden to use network cable as the communication cable to directly communicate with the PC port.
Otherwise, the internal components of the controller will be damaged.
WARNING: RJ45 interface is only suitable for the use of the company's supporting products or professional operation.
Below chart show RS45 pins definition.
Pin
Definition
1
RS-485-B
2
RS-485-A
3
GND
4
5
CANL
6
CANH
7
8
OPERATION
Power ON/OFF
When the inverter works in AC mode, output is powered on or off by the button.
If powering the inverter to battery mode, must first switch on the button.
Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators,
four function keys and a LCD display, indicating the operating status and input/output power information.
LED Indicator
LED Indicator
Messages
AC
Green
On
AC input is normal and working in AC Mode
Flash
AC input is normal, but not working in AC Mode
Off
AC input is abnormal.
INV
Yellow
On
Working in Battery Mode
Off
Not working in Battery Mode

12
BAT
Yellow
On
Battery is in float charge.
Flash
Battery is in constant voltage charge.
Off
Not in charge
FAULT
Red
On
Fault occurs.
Flash
Warning occurs.
Off
No fault or alarm
Function keys
Function Keys
Description
ESC
Return to previous level.
UP
Increase the setting value.
DOWN
Decrease the setting value.
ENTER
Enter setting mode and confirm the selection in setting mode go to next
selection.
LCD Display ICONS
Icon
Function Description
Input Source Information and Output Information
Indicates the AC information
Indicates the DC information
Indicate input voltage, input frequency, PV voltage, battery voltage and charger
current.
Indicate output voltage, output frequency, load in VA, load in Watt and
discharging current.
Configuration Program and Fault Information
Indicates the setting programs
Indicates the warning and fault codes.
Warning: flashing with warning code.
Fault: lighting with fault code.
Battery Information

13
Indicate battery level by 0-24%, 25%-49%, 50-74% and 75-100% in battery mode
and charging status in line mode
In AC mode, it will present battery charging status
Status
Battery voltage
LCD Display
Constant Current
mode/Constant Voltage mode
<2V/cell
4 bars will flash in turns
2V/cell~2.083V/cell
Bottom bar will be on and the other three
bars will flash in turns.
2.083v/cell~2.167v/cell
Bottom two bars will be on and the other
two bars will flash in turns.
>2.167V/cell
Bottom three bars will be on and the top
bar will flash.
Batteries are fully charged.
4 bars will be on.
In battery mode, it will present battery capacity
Load Percentage
Battery Voltage
LCD Display
Load >50%
<1.717V/cell
1.717V/cell~1.8V/cell
1.8V/cell~1.883V/cell
>1.883 V/cell
50%> Load>20%
<1.817V/cell
1.817V/cell~1.9V/cell
1.9 V/cell ~1.983V/cell
>1.983 V/cell
Load<20%
<1.867V/cell
1.867V/cell~i.95V/cell
1.95V/cell~2.033V/cell
>2.033 V/cell
Load Information
Indicates overload.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
0%~24%
25%~49%
50%~74%
75%~100%
Mode Operation Information

14
Indicates unit connects to the mains.
Indicates unit connects to the PV panel.
Indicates load is supplied by utility power.
Indicates the solar charger circuit is working.
Indicates the DC/AC inverter circuit is working.
Mute Operation
Indicates unit alarm is disabled.
LCD Setting
After pressing and holding "ENTER" button for 2 seconds, the unit will enter setting mode. Press "UP" or "DOWN"
button to select setting programs. And then, press "ENTER" or "ESC" button to confirm the selection and exit.
Setting Programs:
Program
Description
Select-able option
01
Output voltage
NOTE: When the
output voltage is set
to 208V, the output
needs to be derated
to 90%.
02
Output frequency
03
Output source
priority : To
configure load
power source
priority
Utility will provide power to the loads
as first priority.
Solar and battery energy will provide
power to the loads only when utility
power is not available.
Solar energy provides power to the
loads as first priority.
If solar energy is not sufficient to
power all connected loads, Utility
energy will supply power to the loads
at the same time.
Solar energy provides power to the
loads as first priority.
If solar energy is not sufficient to
power all connected loads, battery
energy will supply power to the loads
at the same time.

15
Utility provides power to the loads
only when battery voltage drops to
either low-level warning voltage or
the setting point in program 15.
04
AC input voltage
range
If selected, acceptable AC input
voltage range will be within
90-280VAC.
If selected, acceptable AC input
voltage range will be within
170-280VAC.
05
Charger source
priority :To configure
charger source
priority
Solar energy and utility will charge
battery at the same time.
Solar energy will be the only charger
source no matter utility is available or
not
Utility will charge battery as first
priority.
Solar energy charge battery only when
utility is not available.
Solar energy will charge battery as
first priority.
Utility will charge battery only when
solar energy is not available.
06
Maximum utility
charging current
3/5KVA:1-60A
Note: If setting value in program 07 is
smaller than that in program in 06,
the inverter will apply charging
current from program 07 for utility
charger.
07
Maximum charging
current: To configure
total charging
current for solar and
utility chargers
Max. charging current =utility
charging current + solar charging
current.
3KW 24VDC:
2/10/20/30/40/50/60/70/
80/90/100/110/120A can set.
3KW 48VDC/ 5KW 48VDC:2/10/
20/30/40/50/60/70/80A can set.
08
Auto return to
default display
screen
ON (default): If selected, no matter
how users switch display screen, it
will automatically return to default
display screen (Input voltage /output
voltage) after no button is pressed for
1 minute.
OFF : If selected, the display screen
will stay at latest screen user finally
switches.
09
Auto restart when
overload occurs
Restart disable (default)
Restart enable

16
10
Auto restart when
over temperature
occurs
Restart disable (default)
Restart enable
11
Beeps while primary
source is interrupted
Alarm on (default)
Alarm off
12
Low power power
saving
Power Saving OFF (default)
Power Saving ON
13
Overload bypass:
When enabled, the
unit will transfer to
line mode if overload
occurs in battery
mode.
Bypass disable (default)
Bypass enable
14
Buzzer mute setting
Buzzer on (default)
Buzzer off
15
Low DC cut-off
voltage:
•If battery power is
only power source
available, inverter
will shut down.
•If PV energy and
battery power are
available, inverter
will charge battery
without AC output.
If PV energy, battery
power and utility are
all available, inverter
will transfer to line
mode and provide
output power to
loads.
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 23.0V
Set Range : 22-26V
3KW 48VDC/5KW 48VDC
Default setting : 46.0V
Set Range : 44-52V
When the battery definition mode is AGM (lead-acid battery type), FLD
(water injection battery type) mode:the setting point in program 17.
3KW 24VDC
default setting : 23.0V
Set Range: 22-26V
3KW 48VDC/5KW 48VDC
Default setting : 46.0V
Set Range : 44-52V
When the battery definition mode is UB (lithium battery type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 23.8V
Set Range : 20-25V
3KW 48VDC/5KW 48VDC
Default setting : 47.6V
Set Range : 40-50V
16
Setting voltage point
back to battery
mode when
selecting nOPP" (OPP
" priority) in program
03.
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 26.0V
Set Range : 24-29V
3KW 48VDC/5KW 48VDC
Default setting : 54.0V
Set Range : 48-58V

17
When the battery definition mode is AGM (lead-acid battery type), FLD
(water injection battery type) mode:the setting point in program 17.
3KW 24VDC
Default setting : 26.0V
Set Range : 24-29V
3KW 48VDC/5KW 48VDC
Default setting : 52.0V
Set Range : 48-58V
When the battery definition mode is LIB (lithium battery type) mode: the
setting point in program 17.
3KW 24VDC
default setting : 27.2V
Set Range : 23-29V
3KW 48VDC/5KW 48VDC
Default setting : 54.4V
Set Range : 46-58V
17
Battery Type
Lead-acid batteries (default): "AGM"
Water-filled battery : ”FLD”
Lithium battery: "LIB”
Customer Setup Type : ''CUS"
18
Battery low voltage
alarm point
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 22.0V
Set Range : 21-27V
3KW48VDC/5KW48VDC
Default setting : 44.0V
Set Range : 42-54V
When the battery definition mode is LIB (lithium battery type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 23.8V
Set Range : 20.6-25V
3KW48VDC/5KW48VDC
Default setting : 47.6V
Set Range : 41.2-50V
19
Battery low voltage
shutdown point
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 21.0V
Set Range : 20-24V
3KW 48VDC/5KW 48VDC
Default setting : 42.0V
Set Range : 40-48V
When the battery definition mode is LIB (lithium battery type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 23.0V
Set Range : 20-24V
3KW 48VDC/5KW 48VDC
Default setting : 46.0V
Set Range : 40-48V

18
20
Battery Constant
Voltage
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 28.2V
Set Range : 28-29V
3KW48VDC/5KW48VDC
Default setting : 56.4V
Set Range : 48-60V
When the battery definition mode is LIB (lithium battery type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 28.2V
Set Range : 25-29V
3KW48VDC/5KW48VDC
Default setting : 56.4V
Set Range : 48-56V
21
Floating Charging
Voltage
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW24VDC
Default setting : 27.6V
Set Range : 26.6-27.8V
3KW48VDC/5KW48VDC
Default setting : 54.0V
Set Range : 48-60V
When the battery definition mode is LIB (lithium battery type) mode: the
setting point in program 17.
2KW24VDC/3KW24VDC
Default setting : 27.6V
Set Range : 24-28V
3KW48VDC/5KW48VDC
Default setting : 55.2V
Set Range : 50-58V
22
Line Low Voltage
The setting point in program 04 APP mode
default setting : 154V Set Range : 90-154V
The setting point in program 04
UPS mode default setting : 185V
Set Range : 170-200V
23
Line High Voltage
The setting point in program 04 APP mode
default setting :264V Set Range : 264-280V
The setting point in program 04
UPS mode default setting : 264V
Fixed value, cannot be changed.
24
Low Watt Discharge
Default setting : 8 Hours
Set Range : 1-8 Hours
When the battery voltage exceeds 13.2V
(single cell voltage) for more than 30s, this
discharge time will be reset.
In battery mode, after the
continuous discharge time
exceeds this set value, the
battery voltage shutdown point
will be modified to 11V (single
cell voltage) before reaching the
battery shutdown point. Alarm
for 1 minute and then shut
down.
25
Soft Relay Enable
OFF(default)
When set to OFF, the output switch will
not be closed until the inverter voltage
rises to the rated output.
ON
When set to ON, the inverter
output gradually increases from
0 to the target voltage value.
26
Set Default (Reset all
settings to default
Before setting, this interface is displayed as OFF, when it is set to ON, the
system will restore the default settings. After the setting is completed, this
This manual suits for next models
2
Table of contents
Other Micno Inverter manuals