Mindman MF01 Series User manual

Digital Flow Sensor
MF01 series
INSTRUCTION
MANUAL
201012

II
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Contents
Product features..................................................................................................................................................................... 1
Application..................................................................................................................................................................................3
Thermal mass ow sensor principles.................................................................................................................4
Order example..........................................................................................................................................................................4
Specications...........................................................................................................................................................................5
Output type .................................................................................................................................................................................7
Pressure loss characteristics.....................................................................................................................................8
Installation instructions................................................................................................................................................... 9
● Piping ..................................................................................................................................................................................................9
● Mounting bracket.................................................................................................................................................................................9
● Wiring diagrams ................................................................................................................................................................................10
● Dimensions........................................................................................................................................................................................ 11
● Mounting accessories........................................................................................................................................................................12
How to use.................................................................................................................................................................................13
● Names and functions of individual parts ...........................................................................................................................................13
● Internal structure ...............................................................................................................................................................................14
● Functions instructions........................................................................................................................................................................15
Functions setting mode .................................................................................................................................................................15
Measurement mode ......................................................................................................................................................................16
● Operation setting instructions............................................................................................................................................................17
[F-01] OUT1 setting selection .......................................................................................................................................................17
[F-02] OUT2 setting selection .......................................................................................................................................................18
[F-03] LCD display color selection ................................................................................................................................................19
[F-04] Response time selection.....................................................................................................................................................19
[F-05] Display refresh time selection............................................................................................................................................. 20
[F-06] Unit selection ......................................................................................................................................................................20
[F-07] Flow reference standard selection...................................................................................................................................... 20
[F-08] Display rotation ...................................................................................................................................................................20
[F-09] Accumulated value hold selection.......................................................................................................................................21
[F-10] Flow sensor display mode selection ...................................................................................................................................21
[F-91] Power-save mode selection................................................................................................................................................ 22
[F-92] External input selection.......................................................................................................................................................22
[F-93] Modbus RTU setting ...........................................................................................................................................................23
[F-94] Fine adjustment setting.......................................................................................................................................................24
[F-95] Forced output function ........................................................................................................................................................24
[F-99] Reset to the default setting .................................................................................................................................................25
Instantaneous ow zero adjustment function ................................................................................................................................25
Reset accumulated ow function ..................................................................................................................................................25
Peak value display ........................................................................................................................................................................25
Bottom value display .....................................................................................................................................................................26
Key lock / Unlock mode.................................................................................................................................................................26
Modbus RTU instruction...............................................................................................................................................26
Error code instruction.....................................................................................................................................................28
Caution for safety................................................................................................................................................................ 29

1
Flow
Indicator accuracy ± 3% F.S.
Repeatability ± 1% F.S.
Digital display Switch output Analog output Accumulated pulse output
Instantaneous ow value
Accumulated ow value
NPN output
PNP output
Voltage output 1~5V
Current output 4~20 mA 50 ms pulse output
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Product features
Cost Control
User-friendly
High Performance
Multiple output function
High Precision
DRY AIR, N2
RS-485 MODBUS
CONTROL
30.0
OUT1 OUT2
L/min

2
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Product features
Screen Invertible
Display can be vertically
inverted. To set and watch
monitor easily.
Accumulated ow rate
display at a glance
Accumulated ow rate display
Flow rate (L/min)
MF01-005
MF01-010
MF01-050
MF01-100
MF01-500
MF01-101
MF01-201
Wide range of ow rates
0 0.5 1 5 10 50 100 200
30.0
OUT1 OUT2
L/min
8205
L
01
00
Screen invertible

3
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Application
Application
01
Paint and coating ow monitoring
Air ow and pressure management of paint and
coating processes.
Application
02
Laser welding monitoring
Precision management of shielding gas,
ow rate and pressure.
30.0
L/min
30.0
L/min

4
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Application
Application
03
Suction operation
Detect the suction state of micro-
electronic parts by ow rate.
Application
05
Leakage detect
Container with gas and inspect
whether it leaks.
Application
04
Electronic part installation
Control the tension of gold wire for
bonding electronic parts.
Application
06
Air consumption
monitoring
Monitor air consumption of devices.

5
MF01 – 005 – 010 – R6
MP – A26
MODEL
OPTION PARTS
PORT SIZE OUTPUT SPEC.
FLOW RATE
RANGE
R6: ø6 mm, for ow rate range
005, 010, 050, 100, 500.
R8: ø8 mm, for ow rate range
101, 201.
F1C: Rc1/8", with internal threads,
for ow rate range
005, 010, 050, 100, 500
F4C: Rc1/4", with internal threads,
for ow rate range 101, 201
010: 2 NPN output +
Analog output 1 ~ 5 V
011: 2 NPN output +
Analog output 4 ~ 20 mA
02 : 2 NPN output + RS485
030: 2 PNP output +
Analog output 1 ~ 5 V
031: 2 PNP output +
Analog output 4 ~ 20 mA
04 : 2 PNP output + RS485
005: 500 (ml/min)
010: 1000 (ml/min)
050: 5 (l/min)
100: 10 (l/min)
500: 50 (l/min)
101: 100 (l/min)
201: 200 (l/min)
Thermal mass wo sensor principles
Order example
Mounting accessories
Symmetric
temperature prole
(a) No ow
In the absence of ow, the heat
from the heater spreads evenly
left and right, so the temperature
distribution is like (a).
(b) Small ow
When ow begins, the inlet side
is cooled by the ow, the outlet
side is warmed by the heat of the
inlet side of the heater, and the
temperature distribution is like (b).
(c) Large ow
When the ow increases, it
becomes a distribution like (C).
Since the temperature distribution
before and after the heater is
proportional to the ow rate, the
ow rate can be determined from
the ratio.
Temperature
Sensor 1
Temperature
Sensor 1
Temperature
Sensor 1
Temperature
Sensor 2
Temperature
Sensor 2
Temperature
Sensor 2
Heating
Element
Heating
Element
Heating
Element
Skewed
temperature prole
Small Flow
Skewed
temperature prole
Large Flow
MODEL
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Thermal mass ow sensor principles / Order example
A26: Mounting bracket (BT-26)
B4: Panel adapter (PA-G)
C4: Panel adapter + Front protective lid (PA-H)
A26 B4 C4

6
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Specications
Model 005 010 050 100 500 101 201
Fluid Dry air, N2, Non-corrosive / Non-ammable gas
Measured ow rate range 0 ~ 500 mL/min 0 ~ 1000 mL/min 0 ~ 5 L/min 0 ~ 10 L/min 0 ~ 50 L/min 0 ~ 100 L/min 0 ~ 200 L/min
Flow direction Unidirection
Display
Display 4 digital (Flow) × 8 digital (Accumulated ow), 7 segment LCD display ( Red / Green / Orange )
Instant ow
rate
Display range 0 ~ 525 mL/min 0 ~ 1050 mL/min 0 ~ 5.25 L/min 0 ~ 10.50 L/min 0 ~ 52.5 L/min 0 ~ 105.0 L/min 0 ~ 210 L/min
Min. setting
scale
LPM 1 mL/min 0.01 L/min 0.1 L/min 1 L/min
CFM *1 0.01 ft3/min 0.1 ft3/min 1 ft3/min
Accumulated
Flow
Display range 99999999 mL 999999.99 L 9999999.9 L 99999999 L
Min. Setting Scale *1 1 mL 0.01 L 0.1 L 1 L
0.01 ft30.1 ft31 ft3
Accuracy
Guaranteed range 2 ~ 100 % F.S.
Indicator accuracy ± 3 % F.S. ± 1 digit *2
Analog output accuracy ± 5 % F.S. *2
Repeatability ± 1 % F.S. ± 1 digit *3
Linearity ± 3 % F.S. *3
Temp. characteristic ± 2 % F.S. ( 15 ~ 35 °C ) ; ± 5 % F.S. ( 0 ~ 15°C, 35~ 50°C ) ( compare with *3 )
Pressure characteristic ± 5 % F.S. ± 1 digit *4
Switch output
Switch output
2 NPN : open collector 2 outputs
Max. Load Current : 125 mA
Max. Supply Voltage : 28 V DC
Voltage Drop : ≤ 1.5 V
2 PNP : open collector 2 outputs
Max. Load Current : 125 mA
Max. Supply Voltage : 24 V DC
Voltage Drop : ≤ 1.5 V
Response time 800 ms ( 50 ms, 80 ms, 120 ms, 200 ms, 400 ms, 1500 ms selectable )
Output mode Hysteresis Mode, Window Comparator Mode, Accumulated Output, Accumulated Pulse Output
Hysteresis Adjustable
Output short circuit proterction Yes
Accumulated pulse output *1 5 mL/Pulse 10 mL/Pulse 0.05 L/Pulse 0.1 L/Pulse 0.5 L/Pulse 1 L/Pulse 2 L/Pulse
0.02 ft3/Pulse 0.04 ft3/Pulse 0.2 ft3/Pulse 0.4 ft3/Pulse 2 ft3/Pulse 4 ft3/Pulse 7 ft3/Pulse
Analog
output
Voltage output Voltage output range : 1 ~ 5 V ; Output impedance : 1 KΩ
Current output Current output range : 4 ~ 20 mA ; Load impedance : ≤ 300 Ω
Response time ≤ 100 ms
External input Non-voltage input, < 0.4 V, ≥ 30 ms
Communication interface RS-485 *5
Power supply voltage 12 ~ 24 V DC ± 10 %, Ripple ( P-P ) ≤ 10 %
Current consumption ≤ 50 mA
Environment
Working pressure range -0.09 ~ 0.8 MPa
Withstand pressure 1 MPa
Enclosure IP40
Working Fluid Temp. 0 ~ 50°C ( No condensation or freezing )
Ambient Temp. Range Operation : 0 ~ 50°C ; Storage : -10 ~ 60°C ( No condensation or freezing )
Ambient Humidity Range Operation / Storage : 35 ~ 85 % R.H. ( No condensation )
Insulation Resistance ≥ 50 MΩ ( 500 V DC, between case and lead wire )
Withstand Voltage 1000 V AC in 1-min ( between case and lead wire )
Vibration Total amplitude 1.5 mm or 10 G, 10 Hz ~ 55 Hz ~ 10 Hz scan for 1 minute, 2 hours each direction of X, Y and Z
Shock 100 m/s² ( 10 G ), 3 times each in direction of X, Y and Z
EMC IEC 61000-6-2, IEC 61000-6-4
Lead wire ø4 Oil-resistance cable (PVC) - 26 AWG ( 0.15 mm2 ) - 6 cores
Port
Size
R6, F1C
R8, F4C
Weight (with 2 meter lead wire) Approx. 109.3 g ( ø6 port ) ; Approx. 112.7 g ( ø8 port ); Approx. 118 g (Rc1/4 port); Approx. 128.5 g (Rc1/8 port)
*1. CFM ( ft3/min*10-2 ) and ft3*10-2.
*2. Condition: Inlet pressure: 300 kPa , Outlet pressure: 1 atmospheric pressure, 25 °C.
*3. Condition: Outlet pressure: 1 atmospheric pressure, 25 °C.
*4. -0.09 ~ 0.8 MPa, Outlet pressure: 1 atmospheric pressure, 25 °C.
*5. This function only available for Output Specication -02 and -04.
Specications

7
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Output type
Normal open mode
● Hysteresis Mode
FH-1
(FH-2)
FH-1
(FH-2)
FH-1
(FH-2)
FH-1
(FH-2)
FL-1
(FL-2)
FL-1
(FL-2)
AdH1
AdL1
AdH2
AdL2
AdH1
AdL1
AdH2
AdL2
FL-1
(FL-2)
FL-1
(FL-2)
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
0 L 0 L Time
HysHys
50ms
HysHys
Time
OFF
OFF
FlowFlowFlow
FlowFlowFlow
● Window Comparator Mode
● Accumulated Output Mode ● Accumulated Output Mode
● Accumulated Pulse Output Mode
● Window Comparator Mode
● Hysteresis Mode
Normal close mode
NOTE
*1. In case hysteresis is set at less than or equal to 2 digits, switch output may chatter if input
detected uctuates near the set point.
*2. When using window comparator mode, the difference between two set points must be greater
than the xed hysteresis, otherwise will cause the switch output to malfunction.
Flow Range 500mL 1000mL 5L 10L 50L 100L 200L
Pulse Output Rate 5mL 10mL 0.05L 0.1L 0.5L 1L 2L
Time

8
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Pressure loss characteristics
Pressure loss (kPa)
Flow rate (mL/min)
100 200 300 400 500
0.006
0.005
0.004
0.003
0.002
0.001
0
0.1 MPa
0.2
0.3
0.35
0.4
0.5
Pressure loss (kPa)
Flow rate (mL/min)
200 400 600 800 1000
0.018
0.015
0.012
0.009
0.006
0.003
0
0.1 MPa
0.2
0.3 / 0.35 / 0.4
0.5
Pressure loss (kPa)
Flow rate (L/min)
1 2 3 4 5
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
0.1 MPa
0.2
0.3
0.35
0.4
0.5
Pressure loss (kPa)
Flow rate (L/min)
10 20 30 40 50
5
4
3
2
1
0
0.1 MPa
0.2
0.3
0.35
0.4
0.5
Pressure loss (kPa)
Flow rate (L/min)
50 100 150 200
20
16
12
8
4
0
0.3 MPa
0.35
0.4
0.5
Pressure loss (kPa)
Flow rate (L/min)
2 4 6 8 10
0.25
0.20
0.15
0.10
0.05
0
0.1 MPa
0.2
0.3
0.35
0.4
0.5
Pressure loss (kPa)
Flow rate (L/min)
20 40 60 80 100
12
10
8
6
4
2
0
0.2 MPa
0.3
0.35
0.4
0.5
MF01-005 MF01-010
MF01-050
MF01-500
MF01-500
MF01-100
MF01-101

9
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Installation instructions
Installation instructions
●Piping
Install the pipe by following the arrow indication that shows
the air ow direction on the product.
Use straight piping 8cm or longer to connect the Piping Port
(Inlet side).
If straight piping is not installed, the accuracy may vary by ±
2% F.S..
* Straight Piping: The pipe is without bending and the cross
sectional areas of the pipe keeps the same.
Blow the air to ush out the foreign matters, dust and etc.
before installing the pipe.
Uncleaned air may cause malfunction or damage to the
product.
Piping for the One-Touch Fitting, insert the tube rmly into the
tting and make sure it cannot be pulled out.
Also using the proper tube cutter is recommended to ensure
square edge tube.
●Mounting Bracket / Optional Parts
The LCD display may be difcult to see at certain angles.
The sensor can be installed horizontally or vertically, but
the ow rates
may change because of the installation way of the product
or piping.
The tightening torque for screws should be under 0.5 ±0.1
N.m.
* The tightening torque for bracket mounting screws should
be under 0.5 ± 0.1 N.m.
Flow direction
straight piping
8cm or longer
Piping Port
(Inlet side)
Piping Port
(Outlet side)
Horizontal mounting (by Through-Hole)
Bracket mounting
Mounting screw
Mounting screw
Mounting screw
P type
3×6L

10
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Wiring diagrams
●Wiring diagrams
NPN Output, Analog Output and External Input
● NPN Output / Analog Voltage Output / External Input
● NPN Output / Analog Current Output / External Input
● NPN Output, RS-485 Modbus
PNP Output, Analog Output and External Input
● PNP Output / Analog Voltage Output / External Input
● PNP Output / Analog Current Output / External Input
● PNP Output, RS-485 Modbus
Brown (Power supply +)
1kΩ
Yellow (External input)
Load
Main Circuit
Load
Black (Output 1)
White (Output 2)
Blue (Power supply –)
Orange
(Analog output)
1kΩ
Brown (Power supply +)
Yellow (External input)
Load
Main Circuit
Load
Black (Output 1)
White (Output 2)
Blue (Power supply –)
Orange
(Analog output)
Brown (Power supply +)
Yellow (External input)
Main Circuit
Load
Load
Load
Black (Output 1)
White (Output 2)
Blue (Power supply –)
Orange
(Analog output)
Brown (Power supply +)
Main Circuit
Load
Load
Orange
RS-485 (B+)
Yellow RS-485 (A-)
Black (Output 1)
White (Output 2)
Blue (Power supply –)
Brown (Power supply +)
Main Circuit
Load
Load
Orange
RS-485 (B+)
Yellow RS-485 (A-)
Black (Output 1)
White (Output 2)
Blue (Power supply –)
Brown (Power supply +)
Yellow
(External input)
Main Circuit
Load
Load
Load
Black (Output 1)
White (Output 2)
Blue (Power supply –)
Orange (Analog output)
Pin. no. Line color Content Content (RS-485 Modbus)
1Brown Power supply (DC 12 to 24V DC) Power supply (DC 12 to 24V DC)
2Orange Analog voltage output: 1 ~ 5V
Analog current output: 4 ~ 20mA RS-485 (B+)
3Yellow External input RS-485 (A-)
4Black Output 1 (Max. load current: 125mA) Output 1 (Max. load current: 125mA)
5White Output 2 (Max. load current: 125mA) Output 2 (Max. load current: 125mA)
6Blue 0V (GND) 0V (GND)
1
2
3
4
5
6
NOTE
Procedure to wiring RS485 products : To prevent product damage due to short circuit,
MUST do RS485 line conneciton BEFORE power line connection.

11
8
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Dimensions
Internal Thread
Rc1/4”, Rc1/8”
Quick tting ø6, ø8
2×ø2.5×5.5 depth
2×ø2.5×5.5 depth
36.7
36.7
9.5
9.5
18
28
28
18
55
55
24
24
3
38
50.250.2 1717
5252
A
B
Code
Tube I.D. A (mm)
ø8 92.2
ø6 83
Code
Thread B (mm)
Rc1/8" 76.2
Rc1/4" 76.2
Port size
F1C (Rc1/8")
F4C (Rc1/4")
Port size
R6 (ø6)
R8 (ø8)

12
33.6
26
2-ø3.5
4×3.5
4×6
18
8
30
28
5
67.3
27 6.2 27 49.5
32.6
22
3.3
65
21.8
25.3
5.9
258.5
59.8
40
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 Mounting accessories
Mounting bracket
Panel type
MP-A26 (BT-26)
Front protective lid + Panel adapter MP-C4 (PA-H)
Panel thickness 1~4.5
Front protective lid Panel adapter Panel adapter Panel adapter
Panel cut dimensions
Panel adapter MP-B4 (PA-G)
22.5±0.3
34 or over
60.5±0.3
4×R3 or less
Mounting screw
P type 3×6

13
Button
Button
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 How to use –Names and functions of individual parts
●Names and Functions of Individual Parts
3 color LCD Display
Connector
Lead Wire
Connector
Piping Port (Inlet side) Body
Through-Hole
Use to mount the product
on a plate directly.
Piping Port (Outlet side)
Button
Use for mode selection,
ON/OFF switching and
set value adjustment.
Setting Button
Use for selection each mode
and set value conrmation.
4-Digit LCD Flow Display
8-Digit LCD Accumulated Flow Display
Output 1 Indicator
Setting Button
Modbus Symbol
Symbol ashing when MODBUS
data is transmitted.
Flow Unit Display Section
Flow Unit Display Section
Output 2 Indicator
Flow Direction Symbol
How to use
Panel description
Body description

14
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 How to use –Internal structure
1
1
7
7
8
8
9
9
11
13
2
2
3
3
4
4
5
5
6
6
No. Part name (Material)
1Case (PC + ABS)
2Electronic circuit board
3Sensor (SiC)
4Liquid crystal cover (PC)
5Liquid crystal
6Button (Silicone)
7Port lter (Stainless steel)
10
12
Port size
F1C (Rc1/8")
F4C (Rc1/4")
Port size
R6 (ø6)
R8 (ø8)
No. Part name (Material)
8Resin body (PBT)
9O-ring (Viton)
10 O-ring (NBR)
11 One-touch Fitting
12 O-ring (Viton)
13 Internal thread (SUS303)

15
Function
code Item Default setting Explanation
F-01
oUt1 OUT1 setting oUt1
Set Output 1 ow value to
switch ON/OFF.
FLoy OUT1 output mode KY5
oUt1 OUT1 output type no
FL-1 OUT1 set value input
50 % of maximum measured ow rate
005 : 250 mL/min, 010 : 500 mL/min
050 : 2.50 L/min, 100 : 5.00 L/min
500 : 25.0 L/min, 101 : 50.0 L/min
201 : 100 L/min
FK-1 OUT1 set value input
60 % of maximum measured ow rate
005 : 300 mL/min, 010 : 600 mL/min
050 : 3.00 L/min, 100 : 6.00 L/min
500 : 30.0 L/min, 101 : 60.0 L/min
201 : 120 L/min
F-02
oUt2 OUT2 setting oUt2
Set Output 2 ow value to
switch ON/OFF.
FLoy OUT2 output mode KY5
oUt2 OUT2 output type no
FL-2 OUT2 set value input
50 % of maximum measured ow rate
005 : 250 mL/min, 010 : 500 mL/min
050 : 2.50 L/min, 100 : 5.00 L/min
500 : 25.0 L/min, 101 : 50.0 L/min
201 : 100 L/min
FK-2 OUT2 set value input
60 % of maximum measured ow rate
005 : 300 mL/min, 010 : 600 mL/min
050 : 3.00 L/min, 100 : 6.00 L/min
500 : 30.0 L/min, 101 : 60.0 L/min
201 : 120 L/min
F-03
CLor LCD display setting CLor
Select back light color and
display mode.
d15p LCD display corresponding to output oUt1
coL LCD display color selection 5oG
F-04
rE5P Response time selection rE5P Select the response time in
50ms,
80ms, 120ms, 200ms, 400ms
or 1500ms for analog output.
FLoy Response time selection 800 (ms)
F-05
UPdR Display refresh time selection UPdR Display refresh cycle can be
set in 200 ms, 500 ms or 1000
ms.
UPdR Display refresh time of ow sensor
selection 500 (ms)
F-06
Un1t Unit selection Un1t
Select the UNIT of ow sensor.
FLoy Flow unit selection LPA
F-07
rEFE Flow reference standard selection rEFE Select the ow value is shown
under standard (ANR) or
normal condition ( NOR ).
rEFE Flow reference standard selection Anr
Function setting mode
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 How to use –Functions instructions

16
Function setting mode
Measurement Mode
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 How to use –Functions instructions
Function
code Item Default setting Explanation
F-08 rotR Display rotation rotR
Set Display Rotation.
rotR Output selection oFF
F-09 EEPr Accumulated value hold selection EEPr To save the last accumulated ow
value every 2 or 5 minutes.
EEPr Accumulated value hold selection oFF
F-10 d1s Flow sensor display mode selection d1s Select to display Instantaneous
Flow or Accumulated Flow Mode.
dsp Flow sensor display mode selection 1nS
F-91 ECo Power-Save mode selection ECo Select if turn on powersave
mode to reduce power consumption.
ECo Power-Save mode selection no
F-92 1nP External input selection 1nP Select for Accumulated ow rate
zero clear, Auto-Shift or Auto-Shift
zero.
1nP External input selection r_r
F-93
AbUS Modbus RTU setting AbUS
Set ID number, baud rate and
transmission format.
1d ID number setting 1
rAt Baud rate setting 96 (9600 Bd)
For Transmission format setting n81
trR Communications protocol setting rtU
F-94 F1nE Fine adjustment setting F1nE The displayed value can be
adjusted slightly.
F1nE Fine adjustment setting oFF
F-95
FoUt Forced output function FoUt
To turn the analog ON / OFF
forcibly.
oUt1 Forced output function oFF
oUt2 Forced output function oFF
F-99 rESt Reset to the default setting rESt
Return to the factory default setting.
rSt Reset to the default setting oFF
Item Explanation
Flow display Display instantaneous flow rate.
Accumulated flow rate display Display accumulated flow rate.
Instantaneous Flow rate zero setting The displayed instantaneous flow rate value can be adjusted to "0".
Accumulated flow rate zero clear The accumulated flow rate can be set to "0".
Peak value display The maximum pressure or instantaneous flow can be detected when the power is supplied
for a period.
Bottom value display The minimum pressure or instantaneous flow can be detected when the power is supplied
for a period.
Key lock/unlock mode To prevent errors occurring due to unintentional changes of the set values.

17
●Operation setting instructions
At Measurement Mode, press button for more than 3 sec.
to display [F-01]. Press or button to select other setting
functions.
Press for 3 sec. at Function Setting Mode to return to
Measurement Mode.
●[F-01 ]OUT1 Setting Selection
Press or button at Function Setting Mode to display
[ F-01 ] [ oUt1 ].
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 How to use –Operation setting instructions
F-01
oUt1 oUt2 rESt
F-02
00
F-99
Flashing
alternately
F-01
oUt1
Flashing
alternately
Flashing
alternately
Flow Sensor
Selected Mode
Fixed Hysteresis
Mode
Selected Output
NO mode NC mode
Selected Mode
Set Value
Set Value
Selected Mode
Hysteresis
Mode
Window
Comparator
Mode
Accumulated
Output Mode
Accumulated
Pulse Output
Mode
Measurement Mode
Enter in each function setting
Press button for
more than 3 sec.
Press button
Press button
Press button
Press button
Press button to return to
Function Selection Mode
Press button
Flashing
alternately
Flashing
alternately
Flashing
alternately
Flashing
alternately
Flashing
alternately
Function Selection Mode
Output Mode Setting
Set Value Setting
Fixed Hysteresis Setting
Output Type Setting
Select output mode
Press or button to
select output mode of OUT1.
4 output modes included.
OUT1 set value setting
Press or button to
adjust the set value.
Fixed hysteresis setting
Press or button to
adjust xed hysteresis
value.
Hysteresis Mode [ HYS ]: [ FL-1 ], [ FH-1 ]
Window Comparator Mode [ y1n ]: [ FL-1 ], [ FH-1 ]
Accumlated Output Mode [ ADD ]: [ AdL1 ], [ AdH1 ]
OUT1 type setting
Press or button
to select OUT1 type.
* NOTE: The Accumulated Pulse Output Mode can only be set in
OUT1, and OUT2 does not have this setting.
* NOTE: Type setting will not display when Accumulated Pulse
Output Mode is set.
FLoy
FL-1
FH-1
oUt1
FLoy FLoy FLoy FLoy
HYS
25.0
30.0
no
no nC
HYS
oUt1 oUt1
Flashing
alternately
Flashing
alternately
Flashing
alternately
Flashing
alternately
Flashing
alternately
Flashing
alternately
Y1n Add PL5
* NOTE: Set value setting will not display when Accumulated Pulse
Output is set.
* NOTE: Fixed hysteresis setting will not display when Hysteresis
Mode, Accumulated Output Mode and Accumulated Pulse Output
Mode is set.

18
●[F-02 ]OUT2 Setting Selection
Press or button at Function Setting Mode to display
[ F-02 ] [ oUt2 ].
DIGITAL FLOW SENSOR ( INSTRUCTION MANUAL )
MF01 How to use –Operation setting instructions
F-02
oUt2
Flashing
alternately
Flow Sensor Selected Mode
Fixed Hysteresis
Mode
Selected Output
NO mode NC mode
Selected Mode Set Value
Set Value
Selected Mode
Press button Press button
Press button
Press button
Flashing
alternately
Flashing
alternately
Flashing
alternately
Flashing
alternately
Press button to return to
Function Selection Mode
Output Mode Setting Set Value Setting
Fixed Hysteresis Setting
Output Type Setting
Select output mode
Press or button to
select output mode of OUT2.
3 output modes included.
OUT2 set value setting
Press or button to
adjust the set value.
Fixed hysteresis setting
Press or button to
adjust xed hysteresis
value.
Hysteresis Mode [ HYS ]: [ FL-2 ], [ FH-2 ]
Window Comparator Mode [ y1n ]: [ FL-2 ], [ FH-2 ]
Accumlated Output Mode [ ADD ]: [ AdL2 ], [ AdH2 ]
OUT1 type setting
Press or button
to select OUT2 type.
* NOTE: The Accumulated Pulse Output Mode can only be set in
OUT1, and OUT2 does not have this setting.
FLoy FL-2
FH-2
oUt2
HYS 25.0
30.0
no
no nC
oUt2 oUt2
Flashing
alternately
Flashing
alternately
Hysteresis
Mode
Window
Comparator
Mode
Accumulated
Output Mode
FLoy FLoy FLoy
HYS
Flashing
alternately
Flashing
alternately
Flashing
alternately
Y1n Add
* NOTE: Fixed hysteresis setting will not display when Hysteresis
Mode, Accumulated Output Mode and Accumulated Pulse Output
Mode is set.
This manual suits for next models
7
Table of contents
Other Mindman Accessories manuals