MIRI AD2006+ Instruction manual

EXPANSION MODULES
QUICKSTART MANUAL
(August 2020)
PLEASE ENSURE THAT YOU HAVE THE CORRECT POWER SUPPLY VOLTAGE BEFORE POWERING UP THE MODULE.
The product warranty does not cover installation error.

Miri Technologies, 2 Fellowship Road, Gnangara, Western Australia 6077 | Tel: +61 89 409 8998 | www.miri.com.au
Contents
1. Specifications ...........................................................................................................................................1
M-16LN Input Module........................................................................................................................1
M-16HN Input Module.......................................................................................................................1
M8-AD Analog Input Module.............................................................................................................2
M-16TR Relay Module........................................................................................................................3
M4-DA Analog Output Module .........................................................................................................3
2. Wiring Detail.............................................................................................................................................4
3. DIP Switch Settings .................................................................................................................................5
DIP Switch Operation.........................................................................................................................5
Set the Baud Rate ..............................................................................................................................5
Set the Status Defaults .....................................................................................................................5
Select the Protocol.............................................................................................................................5
Configure the Polling ID.....................................................................................................................5

Page 1 of 5
Miri Technologies, 2 Fellowship Road, Gnangara, Western Australia 6077 | Tel: +61 89 409 8998 | www.miri.com.au
1. Specifications
Each module is DIN rail mounting so as to negate the
need for additional DIN rail mounting terminals.
Overall dimensions - 160L x 60W x 50H
M-16LN Input Module
10-35 Volts AC/DC
Inputs per Module 16 Optically Isolated
Input Voltage Range 10-35 Volts AC or DC
Input Impedance 4k7 Ohms
Commons per Module 2 Separate groups of 8
Isolation 3.5kV
Supply Voltage 10-30VDC
Module Power Drain No Inputs Driven - 200mW
All Inputs Driven - 1.2W
M-16HN Input Module
70-130 Volts AC/DC
Inputs per Module 16 Optically Isolated
Input Voltage Range 70-130 Volts AC or DC
Input Impedance 27k Ohms
Commons per Module 2 Separate groups of 8
Isolation 3.5kV
Supply Voltage 10-30VDC
Module Power Drain No Inputs Driven –200 mW
All Inputs Driven - 1.2 W

Page 2 of 5
Miri Technologies, 2 Fellowship Road, Gnangara, Western Australia 6077 | Tel: +61 89 409 8998 | www.miri.com.au
M8-AD Analog Input Module
4-20mA, 1-5V, 0-20mA, 0-5V
Inputs per Module 8 Channels –Common
Ground
Input Current Range 0-20mA or 4-20mA
Input Voltage Range 0-5V or 1-5V
Input Impedance 250 ohms (current mode)
Resolution 12 bits
Accuracy 0.1%
Linearity 0.1%
Supply Voltage 10-30VDC
Module Power Drain Idle 200mW
Range Selection
The analog input range options are selected via
jumpers J9 and J10, there are 3 possible options,
shown in the table below.
Note: The range selected will apply to all analog input
channels.
The factory default setting is 4-20mA / 1-5V.
Current / Voltage Selection
The analog input channels are configured by means
of J1 through J8, which correspond to the analog
channel numbers. They can be configured for any mix
of current or voltage inputs, but will all be scaled
according to the setting of jumpers J9 and J10.
Jumper settings for each channel (1 to 8)
Jumper: Channel is set to current.
No Jumper: Channel is set to voltage.
Default factory setting is jumpers (1 to 8) installed
such that all channels are configured as current
inputs.

Page 3 of 5
Miri Technologies, 2 Fellowship Road, Gnangara, Western Australia 6077 | Tel: +61 89 409 8998 | www.miri.com.au
M-16TR Relay Module
2 Amps
Outputs per Module 16 Relays
Output Current Capability 2A @ 30VDC or
240VAC
Commons per Module 2 Separate Groups of
8
Total Output Capability 10 A per Common
Isolation 3.5 kV
Supply Voltage 10-30 VDC
Module Power Drain No Outputs Driven –
200 mW
All Outputs Driven –
2 W
M4-DA Analog Output Module
4-20 mA
Outputs per Module 4 Channels -
Common Ground
Output Current Range 4-20mA
Load Impedance 250 Ohms @ 12V
500 Ohms @ 24V
Resolution 16 bits
Accuracy 0.1%
Linearity 0.1%
Supply Voltage 10-30VDC
Module Power Drain Idle 200mW

Page 4 of 5
Miri Technologies, 2 Fellowship Road, Gnangara, Western Australia 6077 | Tel: +61 89 409 8998 | www.miri.com.au
2. Wiring Detail
The expansion modules are driven from the RS485
port on the AD2006+ module, or via an M232-485
converter if using the RS232 port of an AD2000
module.
Any combination of up to 32 expansion modules can
be driven from one AD2006+ module.
Standard RS485 parameters apply to the expansion
module bus and thus the modules do not have to be
located in close proximity to the AD2006+ but can be
can be up to 1.5km from the AD2006+ telemetry
module.
An option to run Modbus on the RS485 bus is
provided. This means that the expansion modules
can be operated in conjunction with third party
Modbus devices on a multi-drop RS485 bus.
Note: The protocol selection in MiriMap must match
the DIP switch settings on the expansion modules.
The other settings selected in software are typically:
•Interface - Expansion Modules
•Polling –Continuous
•RTS during Tx must be checked
•Baud rate - 38.4k (default)
When using an AD2000 RS232 port, you will require
an M232-485 converter connected as shown below.

Page 5 of 5
Miri Technologies, 2 Fellowship Road, Gnangara, Western Australia 6077 | Tel: +61 89 409 8998 | www.miri.com.au
3. DIP Switch Settings
The DIP Switches located at the top of each
expansion module configure the module settings.
The function of each switch is shown below.
DIP Switch Operation
Set the Baud Rate
Note: Power cycle required for change to take effect.
Set the Status Defaults
In the event of loss of communications, the digital and
analog outputs will either default to a “HOLD
LAST” or “CLEAR ALL” status according to the switch
settings below.
Select the Protocol
DEFAULT/MIRI - The default setting is Miri protocol
which would normally be used when driving only
expansion modules via RS485.
MODBUS - Modbus protocol is usually used where
other third party Modbus devices are also connected
to the RS485 Multi-Drop Network. Please note that
this can only be done at 9600 or 38400 baud, so the
third party MODBUS devices must be capable of one
of these baud rates.
Configure the Polling ID
In an RS485 Multi-Drop network, whether the
protocol is Miri or MODBUS, each Expansion Module
will need a unique ID. The DIP Switch settings above
let you do this.
Table of contents
Other MIRI Control Unit manuals
Popular Control Unit manuals by other brands

BFT
BFT ALTAIR manual

DINA
DINA DNSL-ZM Original instruction manual

VAT
VAT 590 Series Installation, operating, & maintenance instructions

Mitsubishi Electric
Mitsubishi Electric NZ2GF2B-60TCTT4 user manual

Tews Technologies
Tews Technologies TIP866-TM-20 user manual

Burkert
Burkert 0290 operating instructions