Automated Logic InterOP8500 Owner's manual

Automated Logic Corporation •1150 Roberts Blvd. •Kennesaw, GA 30144 • 770/429-3000 •770/429-3001 Fax •
www.automatedlogic.com • Copyright 2001 Automated Logic Corporation. All rights reserved. Automated Logic, the
Automated Logic logo, SuperVision, Eikon, Alert, and InterOp are registered trademarks of Automated Logic
Corporation. WebCTRL is a trademark of Automated Logic Corporation. BACnet®is a registered trademark of ASHRAE.
All other brand and product names are trademarked by their respective companies.
Technical Instructions
InterOP8500
Introduction 2
Specifications 3
Mounting 4
Connecting Expander Modules 4
Addressing 4
Power Wiring 5
Using the ALC Power Supply 6
Using the Johnson Power Supply 7
Network Communications 7
Communicating with the Workstation 8
Input/Output 9
Analog Inputs 9
Unswitched and Switched Inputs 10
Calculating Offset and Gain 12
Binary I/O Power Jumper 12
Binary Inputs 13
Binary Outputs 13
Point Identifiers 15
Point Identifiers in WebCTRL 15
Channel Numbers in SuperVision 15
Transferring Memory 17
Transferring Memory in WebCTRL 17
Transferring Memory in SuperVision 18
Troubleshooting 18
Formatting the Module 18
LEDs 18
Protection 19
Production Date 19
Sample GFB 20

Revised 7/10/01 • InterOP8500 2 © 2001 Automated Logic Corporation
Introduction
The InterOP8500 mounts directly to a Johnson
Controls panel, replacing the Johnson FIC-1n1
control board and the PCR-102. The
InterOP8500 uses the same mounting
brackets and can be powered by the existing
power supply (using a special adaptor cable).
However, in order to retain the UL listing, the
RPA-105 and the LPS-105 must be replaced by
the PWRSUP8500.
In addition, the InterOP8500 uses the Johnson
field termination board (FTB-102) for binary
I/O and analog input. Please note that slave
FICs must be replaced by separate, stand-
alone InterOP8500 modules.
The InterOP8500’s edge connector plugs
directly into the field termination board’s
socket. Once connected, the InterOp8500
accesses the binary and analog I/O, as well
as an isolated 12VDC power supply for its
binary outputs. The InterOP8500 board
contains the microprocessor, a connection
port for the network connection, and a port
for I/O expansion. The InterOP8500 has 8
binary inputs, 15 analog inputs (which can be
set to either RTD or voltage mode), and 16
digital outputs.
The Access Port allows communication with
WebCTRL or SuperVision. The InterOP8500's
keypad port provides the interface for serial
communications with a BACview1or
BACview2keypad display. Refer to the
BACview1or BACview2 Hardware Technical
Instructions for more information on small
and large keypad display.
NOTE
NOTENOTE
NOTE A 24VAC power supply is required for
a keypad.
Figure 1. InterOP8500 layout and dimensions
CMnet
Terminal
Power
Switch
Power
Terminals
Baud Rate
Switch
Dual Rotary
Address
Analog Inputs
Binary I/O
11 1/4"
28.58 cm
85/8"
21.9 cm
5/8"
1.59 cm
3/8"
.95 cm
2/8"
.64 cm
47/8"
12.38 cm
1"
2.5 cm
Binary Output
HOA Switches
Binary I/O
Power Jumper
Format
Button
10's 1's
Access
Port
Comm Mode
Jumper
Expander Port InterOp8500
Keypad Port Keypad
Power
Binary Outputs

Revised 7/10/01 • InterOP8500 3 © 2001 Automated Logic Corporation
The table below outlines the limitations and
requirements depending on whether you are
using WebCTRL or SuperVision to
communicate with your InterOP8500.
For more information, see the appropriate
module driver document on the Automated
Logic website at www.automatedlogic.com.
Specifications
Power 5VDC, 175mA (external), 275 mA
(internal).
12VDC, 25mA.
12VDC, 175mA (external power), 25 mA
(internal power) supplied through the
card-edge connector.
24VAC, 300mA for use with the large
keypad/display.
Inputs 8 binary inputs, 15 analog inputs
(configurable for 1k ohm nickel RTD or 1
to 5V).
Input Resolution 12 bit A/D.
Digital Outputs 16 digital outputs,
12VDC, 300mA fused output.
Communication For WebCTRL, 156 kbps
BACnet-over-ARCNET and 9600 bps or
38.4 kbps EIA-485 BACnet MS/TP.
For SuperVision, 156 kbps BACnet-over-
ARCNET, 9600 bps or 38.4 kbps Legacy
CMnet. Access Port:9600 bps or 38.4 kbps
EIA-485.
WebCTRL SuperVision
Module Driver DRV_InterO
P8500
85M
Number of Function
Blocks*
100 59
Number of BACnet
Objects*
2000 1000
* depending on available memory
Figure 2. Network Architecture
Johnson Field
Termination Board
Johnson
Field Device
Johnson
Field Device
Johnson
Field Device
Johnson I/O Device
s
Johnson
Field Device
InterOp8500
CMnet (ARC156)
U-Cards
UNI/32
U-Line: 9600 bps or 38400 bps
TNPB
MX-Line
LGRM-E
MX-Line
S-Line
For WebCTRL, BACnet/IP.
For SuperVision, BACnet/Ethernet.

Revised 7/10/01 • InterOP8500 4 © 2001 Automated Logic Corporation
Environmental Operating Range 0-
130 °F (-17.8 to 54.4 °C), 10 to 90%
relative humidity, non-condensing.
Status Indication Visual (LED) status of
CMnet communication, running, errors,
and power.
Memory 1MB Flash memory, 2MB non-
volatile battery-backed RAM (which
stores data even during power failures).
128 bytes of EEPROM.
Real Time Clock A battery-backed real
time clock that keeps track of time in the
event of a power failure.
Protection Surge and transient protection
circuitry.Optically isolated
communications.
Bat t e ry Seven-year lithium BR2330 battery
provides a minimum of 10,000 hours of
data retention during power outages.
Mounting
CAUTION
CAUTIONCAUTION
CAUTION Changes or modifications to this
unit not expressly approved by the party
responsible for compliance could void the
user's authority to operate the equipment.
1. Remove all power to the Johnson Controls
panel.
2. Open the face of the Johnson Controls
panel. The panel may contain up to three
Johnson Controls boards which face the
front of the panel and a side-mounted
board.The facing boards are stacked
above one another and are located
adjacent to the field termination board.
Remove the facing boards and any cables
(called "RPA wires") connected to them.
3. The InterOP8500 mounts directly to the
field termination board using either the
PWRSUP8500 or the existing power
supply (RPA-105 and LPS-105) as shown
in Figure 3 on page 5 and Figure 5 on page
6. Connect the InterOP8500 edge
connectors to the field termination
board's socket. Lock the InterOP8500 in
place with the plastic retainers provided
in the panel.
4. Place the brushed aluminum ALC label on
the door of the panel.
Connecting Expander Modules
Up to five expansion Mx modules can be
connected to an InterOP8500. The stack can
be arranged in a single column using the
optional expansion cable.
NOTE
NOTENOTE
NOTE Use only one expansion cable per
stack.
Addressing
Before setting or changing the address, make
sure the InterOP8500’s power is off. The
InterOP8500 only reads the address when the
module is turned on. After changing the
address, you must transfer memory to the
module. Refer to “Transferring Memory” on
page 17.
The InterOP8500 has two rotary switches for
addressing:
• For WebCTRL systems, use the switches
to assign the device’s MAC (medium
access control) address on the BACnet-
over-ARCNET network segment. The
rotary switches define the MAC address
portion of the device’s BACnet address
which is composed of the network
address and the MAC address.
• For SuperVision systems, use the
switches to assign the device’s module
number.
One switch corresponds to the tens digit and
the other corresponds to the ones digit. For
example, if the module’s address is three, set
the tens switch to zero and the ones switch to
three, as shown in Figure 4 on page 5.

Revised 7/10/01 • InterOP8500 5 © 2001 Automated Logic Corporation
Power Wiring
The InterOP8500 module is designed to
accept power directly from either the
PWRSUP8500 or the existing Johnson power
supply (LPS-105 and RPA-105). In order to
retain the UL listing of your system, a field
inspection is required if using a Johnson
power supply or the RPA-105 and the LPS-105
must be replaced by the PWRSUP8500 or.
Refer to “Using the ALC Power Supply” on
page 6 for wiring with the PWRSUP8500, or to
“Using the Johnson Power Supply” on page 7
for wiring with an existing Johnson power
supply.
Whenever possible, make sure the module's
power and communications connections are
working properly before connecting any
inputs and outputs. Care should be taken to
isolate power wiring from all other wiring
inside the enclosure. The high and low
voltage wiring must be kept as far apart from
each other as is possible to avoid noise
interference.
NOTE
NOTENOTE
NOTE To protect analog signals from stray
noise and to minimize EMI, use shielded
cable on all signal wires and low voltage
power wires.
When entering, exiting, or interconnecting
with the enclosure, it is better to use several
small openings than one large one. The 12V
binary outputs are powered by a separate
source supplied through the field termination
board.
CAUTION
CAUTIONCAUTION
CAUTION The InterOP8500 module is a
Class 2 device (less than 30VAC.) Take
appropriate isolation measures when
mounting an InterOp8500 module where
non-Class 2 devices or wiring are present.
Figure 3. InterOp8500/PWRSUP8500 mounted in Johnson Controls panel
PWRSUP8500
(side-mounted)
InterOp-8500
Johnson Controls
Panel
Edge Connectors
Johnson Field
TerminationBoard
(FTB-102)
Plastic Retainers
to External
Power Supply
InterOp-8500
Power Connector
Power Cable
Figure 4. Setting the CMnet address
10's 1's

Revised 7/10/01 • InterOP8500 6 © 2001 Automated Logic Corporation
Using the ALC Power Supply
The PWRSUP8500 power supply replaces both
the Johnson Controls LPS-105 and Johnson
RPA-105. The PWRSUP8500 is designed to fit
into the previous power supply's mounting
bracket and power the InterOP8500. The
PWRSUP8500 does not require any adaptor
cables. It connects directly to the
InterOp8500's power connector.
CAUTION
CAUTIONCAUTION
CAUTION The PWRSUP8500 module is a
120VAC device. Take appropriate isolation
measures when mounting a PWRSUP8500.
1. Turn the power switches off on the
InterOP8500 and the Johnson Controls
panel.
2. Unplug the LPS-105 from the power outlet
(see Figure 5).
3. Remove the power cable from the
InterOP8500 power connector.
4. Take out the mounting screw from the
face of the LPS-105 and remove the LPS-
105 from the Johnson Controls panel.
5. Take out the mounting screw from the
back of the RPA-105 and remove the RPA-
105 from the Johnson Controls panel.
6. Place the PWRSUP8500 in the same
brackets that the RPA-105 was in. Make
sure the edges of the PWRSUP8500 are in
the slots.
7. Replace the mounting screw in the back
of the PWRSUP8500 (see Figure 3 on page
5).
8. Connect the power cable of the
PWRSUP8500 to the InterOP8500 power
connector and plug the PWRSUP8500 into
the power outlet.
9. After verifying that you have +5V on the
red and +12V on the blue, referenced to
the Gnd (black), turn the InterOp8500
power switch on.
Figure 5. InterOp8500/RPA-105 and LPS-105 mounted in Johnson Controls panel
ON
OFF
Johnson Controls
Panel
Johnson Field
Termination Board
(FTB-102)
InterOp-8500
RPA-105
(side-mounted)
Plastic Retainers
Power Adapter
Cable
Grounding Wire
(green)
Edge Connectors
LPS-105
Panel Power
Switch
J23
J20
to External
Power Supply

Revised 7/10/01 • InterOP8500 7 © 2001 Automated Logic Corporation
Using the Johnson Power Supply
1. Verify that the InterOP8500 is addressed
correctly.
2. Turn the Johnson Controls panel power
switch off.
3. Turn the InterOP8500 power switch off
(see Figure 1 on page 2).
4. Use the Power Adaptor Cable shown in
Figure 6 to connect power from the
Johnson power supply to the InterOP8500.
There is only one way for the connectors
on the cable to properly connect to the
indicated J terminals - do not force the
connectors on the wrong terminal.
5. Connect a grounding wire from the
chassis of the panel to the earth ground
terminal of the InterOp8500. See Figure 5
on page 6 for wiring.
6. Turn the InterOP8500 power switch on.
7. Turn the panel power switch on.
8. Make sure that the Communications
Power, Logic Power +5V, and Power +12V
LEDs are lit (located at the top edge of the
InterOp8500 board). See “LEDs” on
page 18.
Network Communications
The InterOP8500 module supports several
communications options through its CMnet
port.
On a SuperVision system, the InterOP8500
module can connect to a BACnet-over-
ARCNET network segment at 156 kbps, or to
a legacy CMnet at 9600 bps or 38.4 kbps.
When communicating at 156 kbps, the
network segment uses a unique
implementation of the industry standard
BACnet-over-ARCNET protocol called
ARC156. For a summary of the differences
between ARCNET and ARC156, please refer to
ARC156 CMnet Wiring Technical Instructions.
Use the appropriate wire for network
communications. When using an ARC156
network, use an A3ARC156 wire available
from:
Magnum Cable Corporation
Cleveland, OH 44110-0500
(800) 421-0820
Use a dedicated 22AWG to 18AWG twisted
pair wire for legacy CMnet (EIA-485) wiring.
For more information about CMnet wiring,
refer to the Technical Handbook or to ARC156
CMnet Wiring Technical Instructions.
1. Be sure the module’s power is off before
wiring it to the network.
2. Check the network communication wiring
for shorts and grounds.
3. Connect the appropriate communications
wires to the module’s screw terminals as
shown in Figure 7 on page 8. Be sure to
follow the same polarity as the rest of the
network.
4. Make sure the module is configured for
the correct baud rate. All modules on the
Figure 6. Power Cable
J23
J20
J3

Revised 7/10/01 • InterOP8500 8 © 2001 Automated Logic Corporation
network segment must use the same baud
rate.
On an ARC156 network segment (156
kbps), set the Comm Mode jumper to
ARC156 (see Figure 8 for the switch’s
location). The baud rate selection does
not matter in this case.
If you are using a legacy CMnet (9600 bps
or 38.4 kbps), set the Comm Mode jumper
to CMnet, and use the baud rate DIP
switch to determine the baud rate (see
Figure 9 and Figure 10).
NOTE
NOTENOTE
NOTE Setting the Comm Mode jumper
to CMnet disables the industry standard
BACnet-over-ARCNET (ARC156) protocol
for the network segment and enables the
proprietary ALC CMnet protocol.
You can verify that the InterOP8500 is
communicating on the network segment by
making sure the transmit and receive LEDs
are active.
Communicating with the
Wo r k s tat i o n
When using SuperVision, you can connect a
workstation or portable computer directly to
the InterOP8500 module using an APT and the
module’s Access Port (see Figure 11). This
type of connection can be used to
troubleshoot the module or transfer memory.
If you are using an ARC156 network segment,
you can receive colors while connected to a
module’s Access Port if a gateway module is
on the network segment. You cannot receive
alarms through the Access Port, however.
The baud rate of the Access port is
determined by the first switch on the eight-
position DIP switch (see Figure 7). If you need
to change the switch’s position, turn the
InterOP8500 module off first. Once you have
adjusted the switch, turn the module back on.
Figure 7. Wiring the Terminals
Figure 8. Using an ARC156 Network Segment
Figure 9. Setting the Mode Select for CMnet
Comm Mode port
Access port
ARC156
network segment
CMnet
CMnet ARC156
Comm Mode
CMnet ARC156
Comm Mode
Figure 10. Setting the baud rate DIP switch
Figure 11. Using the Access Port
O
N
1 2 3 4
Switch Number
38.4K baud
9600 baud
APT
ModeSelect
TTL 485
ACCESS
PORT
EIA-232
Port
Mode Select
Switch
Access
Port
InterOp-8500

Revised 7/10/01 • InterOP8500 9 © 2001 Automated Logic Corporation
1. Connect the computer’s serial port to the
EIA-232 port of the APT using a standard
straight-through serial cable.
2. Set the APT’s Mode Select switch.
• On an ARC156 network segment, use
the TTL setting.
• On a legacy CMnet, use the 485 setting.
3. Connect the Access port of the APT to the
Access port of the module.
4. In SuperVision, define the connection type
using Table 1.
Input/Output
The InterOP8500 is equipped with 8 binary
inputs, 15 analog inputs, and 16 binary
outputs. Any of the analog inputs can be used
as digital inputs. Table 2 summarizes the
requirements for conductors between the
Johnson Controls field devices and the
termination board.
All wiring to remote devices must be kept
separate from power wiring in the area.
Exposed drain wire at the termination board
should be kept as short as possible, not
exceeding two inches (5 centimeters). All field
devices should be terminated using a
correctly sized wire nut or, when terminals
are provided, a solderless crimp-type
connection should be made.
Analog Inputs
The InterOP8500 provides access to 15 analog
inputs through the Johnson Controls field
termination board. Use the formulas in the
“Calculating Offset and Gain” on page 12
section to read signals from these inputs.
There are four field terminals for each AI
point 1 through 7, and five for each AI point 8
through 15 (see Figure 12 on page 10). The
function of these terminals is as follows:
Termination Row 1 This terminal is for
analog inputs and is connected to a
multiplexer.
Termination Row 2 This terminal is
connected to a regulated +2.5VDC supply.
Table 1. Connection Types
SuperVision
Version
Type of
CMnet
Gateway
Present?
Use Connection
Type
3.0 any n/a Access Port
2.6 ARC156 yes Direct Connect
2.6 ARC156 no Direct Network
2.6 legacy n/a Direct Network
Table 2. Cable Selection Guide
Field
Device
I/O
Type
Conduct
or Size
(AWG)
Number
Required
Maximum
Cable
Length
(ft/m)
AQ-4101
BO 18 2 200/61
A1 18 3 250/76
EPT-101
BO 18 2 200/61
A1 18 3 250/76
H-6210 A1 18 2 250/76
N-9510 BO 18 2 200/61
PC-6100 A1 18 2 250/76
PET-101 A1 18 2 250/76
RTB-101
BO 18 2 200/61
BI 18 2 1000/305
PQ-1001 A1 18 2 250/76
TE-Series A1 18 2 250/76
V-9010 BO 18 2 200/61
V-9012 POS/
INC
18 2 200/61
Power
Supply
—18 2 —

Revised 7/10/01 • InterOP8500 10 © 2001 Automated Logic Corporation
Termination Row 3 This terminal is the
unswitched input signal common.
Termination Row 4 This terminal is not
used.
Termination Row 5 This terminal is the
switched input signal common and is
available only on AI points 8 through 15.
Unswitched and Switched Inputs
Unswitched inputs, the most common type of
input, reference the sensor to the module's
ground, the same ground referenced by all
other unswitched input sensors. This type of
input is for devices that are "floating,"
meaning that they are not ground referenced
anywhere. Examples would be RTD inputs or
dry contacts.
Switched inputs are selected one at a time,
and the circuit board's ground is then
referenced to the module's "Switched
Ground" lead. This feature allows modules
that are not floating, and that may have a
small amount of ground shift, to give stable
readings on their AIs. Examples would be 0-
5VDC or 0-2.5VDC devices.
NOTE
NOTENOTE
NOTE The channel number is not affected
by the input's condition (switched or
unswitched).
Table 3. Acceptable Analog Input Signals
Analog Input
Type Power Jumper? Switched?
RTD -
thermistor
Internal Yes Unswitched
0-5VDC -
linear
Internal No Switched or
Unswitched
0-2.5VDC -
linear
Internal No Switched or
Unswitched
4-20mA -
linear
(Offset/Gain
setup as
1-5VDC)
External (plus
parallel 250
ohm resistor)
No Unswitched
Figure 12. I/O Terminals for the Field Termination Board
Binary Inputs
Binary Common
Unused
+-
12 VDC
Input from external
+12VDC Power Supply
1
2
3
4
5
67
89
10 11 12 13 14 15
1
1
1
11
1
2
2
2
2
2
2
3
3
3
3
3
4
4
4
4
4
35
5
5
5
6
6
67
7
8
8
Analog Inputs
+2.5 VDC
Unused
Switched
Common
Unused
Binary Outputs
Binary Common
Analog Inputs
+2.5 VDC
Analog Common
(Unswitched)
Unused
BI #
BO # AI #
Analog Common
(Unswitched)

Revised 7/10/01 • InterOP8500 11 © 2001 Automated Logic Corporation
1. Turn the Johnson panel power switch off.
2. Determine the type of signal received by
the field termination board. Consult the
Johnson Controls manuals if necessary.
The InterOP8500 must be configured to
receive the same type of input as the
previously removed Johnson boards.
3. Set the InterOp8500 jumpers as follows:
• For RTD mode insert a jumper for the
individual input. The jumpers are
located along the lower right side of the
InterOP8500 board (see Figure 13).
NOTE
NOTENOTE
NOTE If using a solid-state current
switch on a digital input, the resistance
must drop low enough for the module to
recognize it.
• For voltage and potentiometer mode,
remove the jumpers. (Current mode can
be configured by adding an external
sense resistor. For 4-20mA use a 250
ohm resistor Figure 14). Turn the
InterOP8500's power switch on.
Figure 13. Analog Input Jumpers
Unswitched Inputs
Jumper in Place =
RTD Mode
Switched Inputs
Jumper Removed =
Voltage Mode
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Grip
Here
Figure 14. Analog Input Wiring for 4-20 mA Signal
InterOp8500
As specified by the
sensor manufacturer.
Sensor
120 VAC XX VAC
ungrounded
Isolated
DC Power
Supply 4-20mA
Transducer 250 ohm
resistor Connect to Analog Input
Connect to Analog Common (unswitched)
Field Termination
Board

Revised 7/10/01 • InterOP8500 12 © 2001 Automated Logic Corporation
4. For each input, enter the point identifiers.
• In WebCTRL, enter the point number
and the point type on the Properties
page. For linear inputs, set the
minimum value and maximum value to
scale the point to engineering units.
• In SuperVision, enter the channel
number, offset, and gain using the
Configure Points or Point Help feature.
Valid channel numbers are listed in
“Channel Numbers in SuperVision” on
page 15.
5. To verify each input’s operation, have
each sensor create a known value and
compare it to the condition reported on
the FB’s Properties page in WebCTRL or
Status page in SuperVision.
Calculating Offset and Gain
You may need to calculate the offset and gain
for analog inputs to ensure the correct value
is read by the InterOP8500. You can also use
the custom translation table on the module
driver Parameter page to read nonlinear
signals from these inputs. Refer to the
“Channel Numbers in SuperVision” on
page 15 for details.
Use this formula to calculate the gain for an
analog input point:
Use this formula to calculate the offset for an
analog input point:
For example, consider a 1 to 4.5V humidity
sensor with a relative humidity of 20 to 90%.
The voltage span is 3.5 volts (4.5V - 1V). The
user unit span is 70% (90% - 20%). Calculate
the gain and offset for a humidity sensor like
this:
Here is an example of a 0 to 2.5V V-9012
feedback sensor with a range of 0 to 100%
relative humidity. The voltage span is 2.5V
(2.5V - 0) and the user unit span is 100%
(100% - 0%). Calculate the gain and offset for
a V-9012 feedback sensor like this:
Binary I/O Power Jumper
The InterOP8500 provides a jumper (see
Figure 1 on page 2 for location) for selecting
between internal and external power for
Binary I/O points. The InterOP8500 provides
isolation for externally powered devices and
no isolation for internally powered devices. If
binary outputs are present, they must be
externally powered and the jumper must be
set to the External position (see Figure 15 on
page 13). If no binary outputs are present,
GAIN = user unit 256 voltage span
5 volts
*
256 minimum voltage
OFFSET = GAIN
5 volts
**
*5 volts
*
256 1 volt
OFFSET = 0.392
*
= 0.392 51.2
= 19.07
GAIN = 70% 256 3.5 volts
5 volts
*
= 70% 178.5
= 0.392
*
= 0.392 0
256 0 volts
5 volts
*
OFFSET = 0.78
*
= 0
GAIN = 100% 5 volts
256 2.5 volts
*
= 100% 127.5
= 0.78

Revised 7/10/01 • InterOP8500 13 © 2001 Automated Logic Corporation
then binary inputs can be internally powered
(no isolation) or externally powered
(isolated). Note the orientation of the
jumpers.
Binary Inputs
The InterOP8500 provides 8 binary inputs
with direct connection to the Johnson field
termination board. The inputs are for signals
in the range of -38VDC up to +38VDC. A
digital input microblock indicates On for any
voltage between -38.0VDC and 0.9VDC; it
indicates Off for any voltage between 2.5VDC
and 38.0VDC. These inputs are capable of
counting up to 1,000 pulses per second for
use in pulse-counting configurations. Each
binary input can sense either a set of non-
energized contacts, or a two-state DC voltage
level.
The field termination board contains three
terminals for each binary input point (see
Figure 12 on page 10):
Termination Row 1 This terminal is
connected to an input buffer (each input
has a separate buffer).
Termination Row 2 This terminal is the
input signal common.
Termination Row 3 Do not use terminal 3
unless you need to connect an earth
ground.
The common terminals for the binary inputs
are joined to the common terminals for the
binary outputs. All common terminals are
joined to the isolated 12VDC supply's
negative terminal through the field
termination board. This binary ground is
isolated and independent of the logic and
analog supply ground coming from the RPA-
105.
NOTE
NOTENOTE
NOTE All eight binary input terminals are
electrically connected on the field termination
board. To prevent ground loops, electrically
isolate the sources of the binary input signals
from each other.
Binary Outputs
The InterOP8500 provides 16 binary outputs
with a direct connection to the field
termination board. The 16 binary outputs
have suppression. The binary output power
requirement is 13.2VDC, which should be
supplied by an external Class 2 power supply.
The output of this external power supply is
connected to a pair of field terminals located
on the field termination board (see Figure 12
on page 10 for location). The maximum load
through each binary output is 200mA.
The field termination board has terminal
capacity for between 8 and 16 points
depending upon the types of output signals
provided. Each of the eight BO points located
on the termination board consists of six field
terminals. Each of these six field terminals
can provide either one or two independently
controlled binary output points. The function
of these terminals is as follows:
Termination Rows 1-2 These terminals
are independently connected to either
+12VDC or isolated common (depending on
application).
Termination Rows 3-4 These terminals
are connected to isolated common. They are
used with terminals 1 and 2 for fixed-polarity
signals.
Termination Rows 5-6 These terminals
are unused.
NOTE
NOTENOTE
NOTE Terminals 1, 2, 3, and 4 must not be
grounded. Voltages from field devices must
Figure 15. Binary I/O Power Jumper
External Power
(isolated)
Grip
Here
Internal Power
(no isolation)

Revised 7/10/01 • InterOP8500 14 © 2001 Automated Logic Corporation
not be fed back into the binary output
terminals.
Three types of output signals are available:
momentary, position, and maintained. The
momentary signal is used to control a
maintained or momentary relay
configuration. The position signal is intended
to control an actuator with a position
transducer or other interface device. The
maintained signal is intended to control a
two-position device by delivering a
maintained 0 or 12VDC signal.
Manual Operation
The HOA switches (SW3 through SW18),
located as shown in Figure 1 on page 2, allow
each binary output to be in placed in Auto,
On, or Off mode (as shown in Figure 16).
To verify each output’s operation, lock the
output to a known condition using the
Function Block’s Properties page in WebCTRL
or Parameter page in SuperVision. Be sure the
equipment operates as specified.
Each digital output can be placed in Manual
or Auto mode by setting the HOA switches
(see Figure 1 on page 2 for the switches’
location). Table 4 shows the status of the
digital output based on the output’s
configuration and the HOA switch position.
You can monitor the status of the HOA
switches through WebCTRL or InterOP8500.
In WebCTRL, assign each switch a digital
input in the FB using the point number and
the HOA Status Feedback point type. In
SuperVision, assign each switch a digital
input in the FB using channel numbers 81
through 80. Channel 81 corresponds to HOA
switch number one, channel 82 corresponds
to HOA switch two, and so on. Switches 10
through 15 use channel numbers 8A through
8F, and switch 16 uses channel number 80.
An off status means the HOA switch is in Auto
mode. An on status means the HOA switch is
in Manual mode.
Figure 16. InterOp8500 HOA switches
LED8 LED9 LED10 LED22 LED23
AUTO
OFF
ON
AUTO
OFF
ON
SW3 SW4 SW5 SW17 SW18
Table 4. HOA Switch Positions
Output
Configuration On Off Auto
Normally open
output
DO
contacts
closed
DO
contacts
open
determined
by FB
programming
Normally closed
output
DO
contacts
open
DO
contacts
closed
determined
by FB
programming
Results on
Properties page
in WebCTRL* or
Status page in
SuperVision**
ON ON OFF
* use point type of HOA Status Feedback and point
number
** use channel numbers 81 - 80

Revised 7/10/01 • InterOP8500 15 © 2001 Automated Logic Corporation
Point Identifiers
A point can be identified in WebCTRL by its
point number and point type; in SuperVision,
a point is identified by its channel number. On
both systems, expander number zero
represents I/O points on the InterOP8500.
Point Identifiers in WebCTRL
Enter the point identifiers in Eikon for
WebCTRL before the FB is made or on the
point’s Properties page in WebCTRL. Set the
type, number, and any other required
parameters for each point on the
InterOP8500.
1. Select a physical point type from the Point
Type field.
NOTE
NOTENOTE
NOTE To determine the physical point
type of an analog input, see Table 3 on
page 10.
2. If the physical point type is linear, enter
the appropriate minimum and maximum
present values on the microblock’s dialog
box.
For example, on a 0-5VDC sensor, enter 0
as the minimum and 5 as the maximum.
3. Enter the number of the input or output in
the Input or Output Number field.
NOTE
NOTENOTE
NOTE Points are numbered starting with
1 for each point type. For example, HOA
Status output numbers would start at 1
and could go up to 16; likewise, RTD input
numbers would start at 1 and could go up
to 15.
4. Enter an expander number if needed.
Channel Numbers in SuperVision
The following table shows the valid channel
numbers for each point on the InterOP8500.
The offset and gain values used depend on
the type of sensor or actuator attached to the
I/O point. You can select the channel number,
offset, and gain using SuperVision’s Point
Help feature or Configure Points utility.
Alternatively, you can preconfigure the points
by manually entering the channel number,
offset, and gain in Eikon using the values
shown in the following tables.
Table 5. Digital Output Channel Numbers
Point Signal Type Channel
Number
DO 1 Digital
HOA Status† 11
81
DO 2 Digital
HOA Status† 12
82
DO 3 Digital
HOA Status† 13
83
DO 4 Digital
HOA Status† 14
84
DO 5 Digital
HOA Status† 15
85
DO 6 Digital
HOA Status† 16
86
DO 7 Digital
HOA Status† 17
87
DO 8 Digital
HOA Status† 18
88
DO 9 Digital
HOA Status† 19
89
DO 10 Digital
HOA Status† 1A
8A
DO 11 Digital
HOA Status† 1B
8B
DO 12 Digital
HOA Status† 1C
8C
DO 13 Digital
HOA Status† 1D
8D
DO 14 Digital
HOA Status† 1E
8E
DO 15 Digital
HOA Status† 1F
8F
DO 16 Digital
HOA Status† 10
80
† Use digital input microblocks to
monitor the status of HOA Switches.

Revised 7/10/01 • InterOP8500 16 © 2001 Automated Logic Corporation
Table 6. Input Channel Numbers
Point Signal Type Channel
Number †Range Offset Gain
UI 1
RTD 51 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 31 4 to 20mA
0 to 5V §§
Digital 71
UI 2
RTD 52 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 32 4 to 20mA
0 to 5V §§
Digital 72
UI 3
RTD 53 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 33 4 to 20mA
0 to 5V §§
Digital 73
UI 4
RTD 54 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 34 4 to 20mA
0 to 5V §§
Digital 74
UI 5
RTD 55 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 35 4 to 20mA
0 to 5V §§
Digital 75
UI 6
RTD 56 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 36 4 to 20mA
0 to 5V §§
Digital 76
UI 7 RTD 57 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 37 4 to 20mA
0 to 5V §§
Digital 77
UI 8
RTD 58 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 38 4 to 20mA
0 to 5V §§
Digital 78
UI 9
RTD 59 -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 39 4 to 20mA
0 to 5V §§
UI 10
RTD 5A -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 3A 4 to 20mA
0 to 5V §§
UI 11
RTD 5B -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 3B 4 to 20mA
0 to 5V §§
UI 12
RTD 5C -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 3C 4 to 20mA
0 to 5V §§
UI 13
RTD 5D -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 3D 4 to 20mA
0 to 5V §§
UI 14
RTD 5E -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 3E 4 to 20mA
0 to 5V §§
UI 15
RTD 5F -50° to 250° F
-46° to 121° C 0.00
0.00 15.25‡
mA or Volts 3F 4 to 20mA
0 to 5V §§
† Celsius values can only be displayed in SuperVision when the Function
Block is made in Eikon v2.0 or later with the Metric option enabled. Refer to
the Eikon User’s Guide for more information.
§ Use the Point Configuration or Point Help feature available in SuperVision
v2.0 or later.
‡ Any adjustments needed to calibrate the RTD are done as offset adjustments
in the microblock.
Table 7. Maintained Binary Output
Channel Numbers across sections 1 and 3
Johnson Channel “xA”
(wired across terminal sections 1 and 3) ALC Channel
1A 11
2A 12
3A 13
4A 14
5A 15
6A 16
7A 17
8A 18
Table 6. Input Channel Numbers
Point Signal Type Channel
Number †Range Offset Gain

Revised 7/10/01 • InterOP8500 17 © 2001 Automated Logic Corporation
Transferring Memory
You should download memory whenever you
make changes to your modules (for example,
change the module number, upgrade the
module driver, or change the FB).
The InterOP8500 module can store one
module driver and several FBs. The number
of FBs stored depends on the software you
are using (see the table on page 3).
NOTE This type of download should be
performed with caution. When the module is
automatically restarted before and after
transferring memory, any equipment
controlled by the module is shut down and
restarted. Downloading memory also
overwrites all Function Blocks in the module
causing the module to lose any stored data.
Transferring Memory in WebCTRL
The InterOP8500 module using the
DRV_InterOP8500 module driver can store up
to 100 FBs, depending on their size. You must
be logged in to WebCTRL with the appropriate
privilege to download memory.
1. Click the CFG button at the bottom of the
navigation pane.
2. Click Download in the CFG tree control.
3. Click the Memory, Parameters, or
Schedules boxes, depending on what you
want to download.
NOTE A memory download includes a
parameter and schedule download.
4. Expand the tree in the action pane, click
the module you want to download to,
then click Add. Click on and Add any
other modules you want to download to.
5. Click the Execute Download button.
If any downloads failed, they are listed in
the Failures section under the tree in the
action pane. To retry a failed download,
click on the module in the Failures list,
click Add, and click the Execute
Download button again.
NOTE Since a failed download indicates
a system problem, you should never clear
a failure. Locate and resolve the problem,
then retry the download.
6. Click the Properties button to refresh the
screen. This removes the items from the
Download Items list.
Table 8. Maintained Binary Output
Channel Numbers across sections 2 and 4
Johnson Channel “xB”
(wired across terminal sections 1 and 3) ALC Channel
1B 19
2B 1A
3B 1B
4B 1C
5B 1D
6B 1E
7A 1F
8A 10
Table 9. Position Binary Output Channel
Numbers across sections 1 and 2
Channel Number Open Channel Number Closed
11 19
12 1A
13 1B
14 1C
15 1D
16 1E
17 1F
18 10

Revised 7/10/01 • InterOP8500 18 © 2001 Automated Logic Corporation
Transferring Memory in SuperVision
The InterOP8500 module using the 85M
module driver can store up to 59 FBs,
depending on their size.
1. Log in to SuperVision on a workstation
connected to the module network. You
can also connect directly to the module
using the Access Port; see
“Communicating with the Workstation” on
page 8.
2. Navigate to the module driver and look at
the module status report in SuperVision to
make sure the module type and number
agree with the module.
• To view the module status report in
SuperVision v3.0, click Tools -
Troubleshooting - Module Status.
• To view the module status report in
SuperVision v2.6b, press the Esc key,
type MO ,,module address,15 and
press Enter.
3. Transfer memory to the module.
• In SuperVision v3.0, click Tools -
Troubleshooting - Transfer Memory to
Module.
• In SuperVision v2.6b, download
memory for This Module.
4. When the memory transfer is finished,
check the module status report again.
Make sure the FB List shows all the FBs
you intended to transfer.
Troubleshooting
Formatting the Module
If you are unable to communicate with a
module after transferring memory, you can,
as a last resort, manually format the module
to try to restore communication. Formatting
the module erases all memory, so you need to
transfer memory back to the module once it is
formatted.
NOTE Since the module is automatically
formatted when you transfer memory, you
should only manually format the module if
communication was not established after the
memory transfer.
1. Turn the module’s power off. Make sure
the module’s address switches are not set
to ‘0 0’.
2. Press and hold the Format button (see
Figure 1 on page 2 for location).
3. While continuing to hold the Format
button, turn the module’s power on.
4. Continue to hold the button until the Error
LED flashes three times in sync with the
Run LED.
5. Release the Format button.
6. Transfer memory to the module. Refer to
“Transferring Memory” on page 17.
LEDs
The InterOP8500 module has several LED
indicators to show the status of certain
functions. Table 10 on page 19 explains the
Run (LED 3) and Error (LED 4) LED signals in
detail to assist troubleshooting.
LED 1 Rx - lights when the InterOP8500
receives data through the network segment.
LED 2 Tx - lights when the InterOP8500
transmits data over the network segment.
LED 5 Communications Power - Indicates
power is being supplied to the
communications circuitry.
LED 6 Logic Power +5V - indicates power is
being supplied to the logic circuitry.
LED 7 Power +12V - indicates power is
being supplied to the analog circuitry.
LED 8-23 Binary Outputs - indicates 12V
on the individual output.

Revised 7/10/01 • InterOP8500 19 © 2001 Automated Logic Corporation
LED 24 Output Power - indicates power is
being received from field termination board
from the external power supply for binary
outputs and isolated binary inputs.
Protection
The InterOP8500 module is protected by
internal solid state Polyswitches on the
incoming power and network connections.
These Polyswitches are not replaceable and
will reset themselves if the condition that
caused the fault returns to normal.
Production Date
To determine when a module was
manufactured, check the module status
report for the module in WebCTRL or
SuperVision. Refer to the appropriate user’s
guide for more information about the module
status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next two characters show the year and month
of manufacture.
Table 10. LED Signals
Run LED Error LED Condition
2 flashes
per second
Off Normal
2 flashes
per second
1 flash,
then pause
Normal, but module is
alone on the CMnet
(this sequence doesn’t
occur in WebCTRL)
2 flashes
per second
2 flashes,
alternating
with Run
LED
Five minute auto-restart
delay after system error
2 flashes
per second
2 flashes,
in sync
with Run
LED, then
pause
Module is configured for a
different baud rate than the
rest of the network
segment
2 flashes
per second
3 flashes,
then off
Module has just been
formatted
2 flashes
per second
4 flashes,
then pause
Two or more devices on
this network have the
same ARC156 network
address
2 flashes
per second
On Exec halted after frequent
system errors or GFBs
halted
5 flashes
per second
On Exec start-up aborted, Boot
is running
5 flashes
per second
Off Firmware transfer in
progress, Boot is running
7 flashes
per second
7 flashes
per second,
alternating
with Run
LED
Ten second recovery
period after brownout
14 flashes
per second
14 flashes
per second,
alternating
with Run
LED
Brownout

Revised 7/10/01 • InterOP8500 20 © 2001 Automated Logic Corporation
Sample GFB
Figure 17. Sample GFB
Table of contents
Other Automated Logic Control Unit manuals

Automated Logic
Automated Logic M220NX Owner's manual

Automated Logic
Automated Logic G4106 Owner's manual

Automated Logic
Automated Logic UNI/16 Owner's manual

Automated Logic
Automated Logic UNI/32 Owner's manual

Automated Logic
Automated Logic S6104 Owner's manual

Automated Logic
Automated Logic T-Line Series Owner's manual

Automated Logic
Automated Logic UNI/59 Owner's manual

Automated Logic
Automated Logic R683 Owner's manual

Automated Logic
Automated Logic U253 Owner's manual

Automated Logic
Automated Logic LGE Owner's manual