
MEES21K047
PQRY-P-Z(S)LMU-A1
12
1. SPECIFICATIONS WR2-Series-575V
Heat Source Model PQRY-P240ZSLMU-A1
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 575 V ±10% 60 Hz
Cooling capacity *1 BTU/h 240,000
(Nominal) kW 70.3
Power input kW 16.89
(575) Current input A 18.8
(Rated) BTU/h 228,000
kW 66.8
Power input kW 15.57 16.15
(575) Current input A 17.3 18.0
Temp. range of Indoor W.B. 59~75°F (15~24°C)
cooling Inlet water ºF 50~113°F (10~45°C)
Heating capacity *2 BTU/h 270,000
(Nominal) kW 79.1
Power input kW 14.58
(575) Current input A 16.2
(Rated) BTU/h 258,000
kW 75.6
Power input kW 13.45 12.02
(575) Current input A 15.0 13.4
Temp. range of Indoor D.B. 59~81°F (15~27°C)
heating Inlet water ºF 50~113°F (10~45°C)
Indoor unit Total capacity 50~150% of heat source unit capacity
connectable Model/Quantity P04~P96/2~50 (Connectable branch pipe number is max. 48.)
Sound pressure level (measured in anechoic room) dB <A> 57.0
Refrigerant High pressure in. (mm) 7/8 (22.2) Brazed (1-1/8 (28.58) Brazed for the part that exceeds 65 m)
piping diameter Low pressure in. (mm) 1-3/8 (34.93) Brazed
Set Model
Model PQRY-P120ZLMU-A1 PQRY-P120ZLMU-A1
Minimum Circuit Ampacity A 11 11
Maximum Overcurrent Protection A 15 15
Circulating water Water flow rate G/h 1,522 + 1,522
G/min (gpm) 25.4 + 25.4
m3/h 5.76 + 5.76
L/min 96 + 96
cfm 3.4 + 3.4
Pressure drop psi 3.48 3.48
kPa 24 24
Operating volume G/h 793 + 793 ~ 1,902 + 1,902
range G/min (gpm) 13.2 + 13.2 ~ 31.7 + 31.7
m3/h 3.0 + 3.0 ~ 7.2 + 7.2
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Starting method Inverter Inverter
Motor output kW 7.7 7.7
Case heater kW - -
Lubricant MEL32 MEL32
External finish Galvanized steel sheets Galvanized steel sheets
External dimension H x W x D in. 43-5/16 x 34-11/16 x 21-11/16 43-5/16 x 34-11/16 x 21-11/16
mm 1,100 x 880 x 550 1,100 x 880 x 550
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
Inverter circuit Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Refrigerant Type x original charge R410A x 11 lbs + 1 oz (5.0 kg) R410A x 11 lbs + 1 oz (5.0 kg)
Control Indoor LEV and BC controller
Net weight lbs (kg) 411 (186) 411 (186)
Heat exchanger plate type plate type
Water volume in plate G 1.32 1.32
l 5.0 5.0
Water pressure Max. psi 290 290
MPa 2.0 2.0
HIC circuit (HIC: Heat Inter-Changer) - -
Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 3/4 (19.05) Brazed
distributor Low pressure in. (mm) - 7/8 (22.2) Brazed
Drawing External KL94C251
Wiring KE94G421 KE94G421
Standard Document Installation Manual
attachment Accessory Details refer to External Drw
Optional parts Heat Source Twinning kit: CMY-Q100CBK2
joint: CMY-Y102SS-G2, CMY-Y102LS-G2, CMY-R160-J1
Main BC controller: CMB-P108,1012,1016NU-JA1, CMB-P1016NU-KA1
Sub BC controller: CMB-P104,108NU-KB1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation
Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the Heat Source Unit needs to be kept below 104°FD.B. (40°CD.B.)
The ambient relative humidity of the Heat Source Unit needs to be kept below 80%.
The Heat Source Unit should not be installed at outdoor.Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
The Heat Source twinning kit (low pressure) should be connected to the low pressure side of the heat source unit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
When the high pressure piping length is 65 m or less, use 7/8 (22.2) pipe.
When the high pressure piping length exceeds 65 m, use 7/8 (22.2) pipe until 65 m, use 1-1/8 (28.58) pipe for the part that exceeds 65 m.
The cooling tower and the water circuit must be a closed circuit (water is not exposed to the atmosphere).
Notes: Unit converter
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 81°FD.B./66°FW.B. (27°CD.B./19°CW.B.), Inlet water temperature: 86°F (30°C)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 68°FD.B. (20°CD.B.), Inlet water temperature: 68°F (20°C)
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is
subject to rounding variation.
0000006382.BOOK 12 ページ 2021年7月19日 月曜日 午後4時14分