
16
Error Code Abnormal point and detection method Cause Countermeasure
E0
or
E4
Remote controller transmission
error(E0)/signal receiving error(E4)
1Abnormal if main or sub remote controller
cannot receive any transmission
normally from indoor unit of refrigerant
address “0” for 3 minutes.
(Error code : E0)
2Abnormal if sub remote controller could
not receive any signal for 2 minutes.
(Error code: E0)
1Abnormal if indoor controller board can
not receive any data normally from
remote controller board or from other
indoor controller board for 3 minutes.
(Error code: E4)
2Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Error code: E4)
1Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2Set one of the remote controllers “main”
if there is no problem with the action above.
3Check wiring of remote controller.
• Total wiring length: max. 500m
(Do not use cable x 3 or more.)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote
controller: max. 2 units
When it is not the above-mentioned problem of
1~3
4Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c) When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
* If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0” may
be abnormal.
E3
or
E5
Remote controller transmission
error(E3)/signal receiving error(E5)
1Abnormal if remote controller could not
find blank of transmission path for 6
seconds and could not transmit.
(Error code: E3)
2Remote controller receives transmitted
data at the same time and compares the
received and transmitted data. Abnormal
if these data are judged to be different
30 continuous times. (Error code: E3)
1Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2Indoor controller board receives
transmitted data at the same time and
compares the received and transmitted
data. Abnormal if these data are judged
to be different 30 continuous times. (Error
code: E5)
1Set a remote controller to main, and the
other to sub.
2Remote controller is connected with only one
indoor unit.
3The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK” is displayed, remote
controllers have no problem.
Turn the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is
displayed, noise may be causing
abnormality.
1Contact failure at transmission
wire of remote controller
2All remote controllers are set
as “sub” remote controller.
In this case, E0 is displayed
on remote controller, and E4
is displayed at LED (LED1,
LED2) on the outdoor controller
circuit board.
3Miswiring of remote controller
4Defective transmitting receiving
circuit of remote controller
5Defective transmitting receiving
circuit of indoor controller board
of refrigerant addresses “0”.
6Noise has entered into the
transmission wire of remote
controller.
12 remote controllers are set as
“main.”
(In case of 2 remote controllers)
2Remote controller is connected
with 2 indoor units or more.
3Repetition of refrigerant
address
4Defective transmitting receiving
circuit of remote controller
5Defective transmitting receiving
circuit of indoor controller board
6Noise has entered into
transmission wire of remote
controller.
E6
1Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
2Defective transmitting receiving
circuit of indoor controller board
3Defective transmitting receiving
circuit of indoor controller board
4Noise has entered into indoor/
outdoor unit connecting wire.
* Check LED display on the outdoor control
circuit board. (Connect A-control service
tool, PAC-SK52ST.)
Refer to outdoor unit service manual.
1 Check disconnection or looseness of
indoor/ outdoor unit connecting wire of
indoor unit or outdoor unit.
Check all the units in case of twin triple
indoor unit system.
2-4Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board or
outdoor controller circuit board.
* Other indoor controller board may have
defect in case of twin triple indoor unit
system.
Indoor/outdoor unit communication
error (Signal receiving error)
1Abnormal if indoor controller board can
not receive any signal normally for 6
minutes after turning the power on.
2Abnormal if indoor controller board can
not receive any signal normally for 3
minutes.
3Consider the unit abnormal under the
following condition: When 2 or more
indoor units are connected to an outdoor
unit, indoor controller board cannot
receive a signal for 3 minutes from
outdoor controller circuit board, a signal
which allows outdoor controller circuit
board to transmit signals.