INSTALLATION AND WIRING 7
Table 5 Truth table of safety related signals
The terminal ON state shows that the terminal is conducted (the line is closed), and the OFF state shows that the terminal is
not conducted (the line is open).
When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and SD to use the inverter.
(In the initial status, terminals S1 and PC, S2 and PC, and SIC and SD are respectively shorted with shorting wires.)
If any of the faults shown in the following table occurs, terminal So (SO) and the SAFE signal turn OFF.
When the internal safety circuit is operated normally (no faults occurs), terminal So (SO) and the SAFE signal remains ON
until "E.SAF" is displayed. Terminal So (SO) and the SAFE signal turns OFF when "E.SAF" is displayed.
"SA" is displayed when terminals S1 and S2 are identified as OFF due to a fault occurred in the internal safety circuit.
If another fault occurs when the fault E.SAF occurs, the other fault indication may be displayed.
If another warning occurs when the warning SA occurs, the other warning indication may be displayed.
The ON/OFF state of the output signal is the one for the positive logic. The ON and OFF are reversed for the negative logic.
To assign the function of the SAFE signal to an output terminal, set either value shown in the following table in any of Pr.190
to Pr.196 (Output terminal function selection).
The use of SAFE signal has not been certified for compliance with safety standards.
NOTE
• The response time from safety stop signal input to drive shutoff (safe state) is faster than 8ms.
• Hold the ON or OFF status for 2 ms or longer to input signal to terminal S1 or S2.
Signal input shorter than 2 ms is not recognized.
Input
power
Internal
safety
circuit
status
Input terminal, Output
terminal
Output
signal
, ,
Inverter
running
status
Operation panel
indication
S1 S2 So (SO) SAFE E.SAF SA
OFF OFF OFF Output shutoff
(Safe state)
Not
displayed
Not
displayed
ON
NormalONONON
OFF Drive enabled Not
displayed
Not
displayed
Normal ON OFF OFF OFF Output shutoff
(Safe state) Displayed Displayed
Normal OFF ON OFF OFF Output shutoff
(Safe state) Displayed Displayed
Normal OFF OFF ON ON Output shutoff
(Safe state)
Not
displayed Displayed
FaultONONOFFOFF
Output shutoff
(Safe state) Displayed Not
displayed
Fault ON OFF OFF OFF Output shutoff
(Safe state) Displayed Displayed
Fault OFF ON OFF OFF Output shutoff
(Safe state) Displayed Displayed
Fault OFF OFF OFF OFF Output shutoff
(Safe state) Displayed Displayed
Output
signal
Pr.190 to Pr.196 settings
Positive logic Negative logic
SAFE 80 180
Error definition Operation panel indication
Option fault E.OPT
Communication option fault E.OP1 to E.OP3
Internal storage device fault E.PE6
Parameter storage device fault
(control circuit board) E.PE
Retry count excess E.RET
Parameter storage device fault
(main circuit board) E.PE2
Operation panel power supply short circuit/
RS-485 terminals power supply short circuit E.CTE
24 VDC power fault E.P24
Safety circuit fault E.SAF
Overspeed occurrence E.OS
Speed deviation excess detection E.OSD
Signal loss detection E.ECT
Excessive position fault E.OD
Encoder signal loss for orientation E.ECA
Brake sequence fault E.MB1 to E.MB7
CPU fault E.CPU
E.5 to E.7
Encoder phase fault E.EP
Magnetic pole position unknown E.MP
Internal circuit fault E.13
Error definition Operation panel indication