Modine Manufacturing Atherion MPR User guide

MCP15-525.0
5H0837230000
September, 2012
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
MODINE CONTROL SYSTEM MANUAL
commercial packaged ventilation system
Models MPR and ERM
WARNING IMPORTANT
1. Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death. Read the installation,
operating and maintenance instructions
thoroughly before installing or servicing this
equipment.
2. Improper control adjustments and manual
mode control can cause property damage,
injury or death. Read the installation,
operating and maintenance instructions
thoroughly before making adjustments.
3. Disconnect power supply before installing the
accessory to prevent the unit from operating
during installation.
1. The use of this manual is specifically intended
for a qualified installation and service agency.
All installation and service of this unit must be
performed by a qualified installation and
service agency.
2. These instructions must also be used in
conjunction with the Installation and Service
Manual originally shipped with the appliance,
in addition to any other accompanying
component supplier literature.
3. This manual applies to Modine Control
System program version series 3 and 4 only.
For any other version, please contact Modine.
The program version that resides in the unit
controller can be found in the Information
section of the Service Sub Menu. Refer to the
manual for instructions on accessing this
screen.

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
2
MCP15-525.0
General Information
Controls are one of the most important components of specialized HVAC equipment. The Modine Control System is designed
and engineered around the design of the Atherion™ to ensure that the unit operates safely, reliably, with optimized performance,
and maintaining maximum energy efficiency.
Table of Contents
Model Nomenclature – Model MPR .............................................................4
Model Nomenclature – Model ERM .............................................................5
Identification of Superheat Control.....................................................................................................6
Controller Overview......................................................................................7
Description and Features...................................................................................................................7
Standard and Optional Sensors Monitored........................................................................................8
PCO3Controller Layout .....................................................................................................................9
Display/Keypad Functions.........................................................................10
Standard Buttons.............................................................................................................................10
Extra Function Button Sequences ...................................................................................................10
Menu Navigation..............................................................................................................................11
Navigation Sub Menus.....................................................................................................................11
Example Navigation to On/Off Sub Menus ......................................................................................11
Password Protection........................................................................................................................12
Adjusting Customer Control Settings...............................................................................................12
Main Menu – Tree of Functions .................................................................13
Main Status Screen.....................................................................................14
Main Status Screen Parameters......................................................................................................14
On/Off Sub Menu.........................................................................................18
Setpoint Sub Menu .....................................................................................19
Clock/Scheduler Sub Menu........................................................................22
Input / Output Sub Menu ............................................................................23
Analog Inputs:..................................................................................................................................23
Digital Inputs:...................................................................................................................................23
Analog Outputs:...............................................................................................................................24
Digital Relay Outputs:......................................................................................................................24
Data Logger Sub Menu...............................................................................25
Board Switch Sub Menu.............................................................................25
Programming the Remote Display Keypad to the Controller ...........................................................26
Service Sub Menu.......................................................................................27
Information.......................................................................................................................................27
Working Hours.................................................................................................................................28
BMS Configuration...........................................................................................................................29
Working Hour Setpoint.....................................................................................................................30
Probe adjustment.............................................................................................................................30
Control Settings...............................................................................................................................31
User DEV/Change PW1 ..................................................................................................................39
Manual Management.......................................................................................................................40

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
3
Manual Control Reset ......................................................................................................................40
Analog Input:....................................................................................................................................40
Digital Input:.....................................................................................................................................41
Relay Output:...................................................................................................................................41
Analog Output:.................................................................................................................................41
Manufacturer Sub Menu.............................................................................42
Configuration....................................................................................................................................42
I/O Configuration – Digital Input Configuration.................................................................................51
I/O Configuration – Analog Input Configuration................................................................................56
I/O Configuration – Relay Output Configuration:..............................................................................63
I/O Configuration – Analog Output Configuration.............................................................................66
ERM.................................................................................................................................................67
Initialization ......................................................................................................................................70
pAD Settings....................................................................................................................................70
EVO -EVD Settings (Electronic Expansion Valve Driver).................................................................73
Digital Scroll Compressors........................................................................78
Starting Frequency and Minimum Compressor Running Time.........................................................78
Digital Scroll Compressor Operation................................................................................................78
Electronic Expansion Valves Carel CDSS Mode......................................79
Unit Alarms .................................................................................................80
Main Unit Controller Inputs/Outputs.........................................................83
pCO3Inputs......................................................................................................................................83
pCO3Outputs...................................................................................................................................84
pCOe Expansion Module Inputs/Outputs (for Emerson EC3 Superheat Control only).....................85
EVO/EVD Driver Module Inputs/Outputs (for Carel EVD Superheat Control only)...........................85
Energy Recovery Module Controller Inputs/Outputs (if equipped)........86
pCOxs Inputs ...................................................................................................................................86
pCOxs Outputs.................................................................................................................................86
Typical BMS – EMS – BAS System Variables ..........................................87

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
4
MCP15-525.0
Model Nomenclature – Model MPR
1, 2, 3 4, 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UT UNC CS AC EC CMP HGR CA SB HP MT SV SA HT UNH TR HC
Digits 1, 2, 3 - Unit Type (UT)
MPR - Commercial Packaged Ventilation Unit
Digits 4, 5 - Unit Nominal Cooling (UNC)
15 - 15 ton
20 - 20 ton
26 - 26 ton
30 - 30 ton
6 - Cabinet Size (CS)
C - "C" Cabinet
7 - Air Control Configuration (AC)
A - Fresh & Return Air Dampers
D - Fresh Air Dampers (no Return Air)
E - Fresh Air Dampers (with Exhaust Air Opening and
Interface to Energy Recovery Module)
F - Fresh Air Dampers (with Exhaust Air Opening and
Interface to Power Exhaust Module)
G - Return Air Opening only (No Dampers or Fresh Air)
8 - Evaporator Coil (EC)
1 - High Capacity 4 Row, 14fpi DX Coil
2 - High Capacity 4 Row, 14fpi DX Coil with E-Coat
9 - Compressor Staging (CMP)
A - Tandem Digital Scroll Compressor
10 - Hot Gas Reheat (HGR)
0 - No Hot Gas Reheat
1 - Modulating Hot Gas Reheat
2 - Modulating Hot Gas Reheat with E-Coat
11 - Condenser Arrangement (CA)
A - Standard Fans, VFD Control, Microchannel Coils
B - Standard Fans, VFD Control, Microchannel Coils
with E-Coat and UV Top Coat
12 - Supply Blower Configuration (SB)
3 - 20" Backward Inclined Airfoil Plenum Fan
5 - 25” Backward Inclined Airfoil Plenum Fan
6 - 28" Backward Inclined Airfoil Plenum Fan
13 - Supply Blower Motor HP (HP)
C or Q - 1hp
D or R - 1-1/2hp
E or S - 2hp
F or T - 3hp
G o r U - 5hp
H or V - 7-1/2hp
J or W - 10hp
K or X - 15hp
C thru K include a factory mounted/wired motor starter.
Q thru X are Variable Frequency Drive (VFD) ready.
14 - Supply Blower Motor Type (MT)
1 - ODP - NEMA Premium Efficiency
2 - TE - NEMA Premium Efficiency
15 - Unit Supply Voltage (SV)
4 - 208V/3ph
5 - 230V/3ph
6 - 460V/3ph
7 - 575V/3ph
16 - Supply Blower Sheave Assy (SA)
Refer to AccuSpec
17 - Heating Section Type (HT)
0 - None
1 - Electric
2 - Natural Gas
3 - Natural Gas with 20kW Aux Elec Heat
- Nominal kW rating, derated for 208V/3ph.
18 - Nominal Heat Capacity (UNH)
N - No Heating
A - 20kW Electric
B - 40kW Electric
C - 60kW Electric
D - 80kW Electric
E - 100kW Electric
J - 300 MBH Gas - 80%
K 400 MBH Gas - 80%
L - 500 MBH Gas - 80%
- Nominal kW rating, derated for 208V/3ph.
19 - Temperature Rise (TR)
N - Not Applicable
(300MBH Gas Only and Electric)
H - High Air Temp Rise (75°F and Higher)
(400 and 500 MBH Gas Only)
L - Low Air Temp Rise (Under 75°F)
(400 and 500 MBH Gas Only)
20 - Heat Control (HC)
N - No Heating
A - Single Stage (Electric Only)
B - Two Stage (Electric Only)
C - Four Stage (Electric Only)
D - Modulating (Gas or Electric)

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
5
Model Nomenclature – Model ERM
1, 2, 3 4, 5 6 7 8 9 10 11 12 13 14
UT NWD CS ERT EBP EBC HP MT SV SA PH
Digits 1, 2, 3 - Unit Type (UT)
ERM - Energy Recovery Module
Digits 4, 5 – Nominal Wheel Diameter (NWD)
48 - 48” (6000 CFM limit)
58 - 58” (8700 CFM limit)
6 - Cabinet Size (CS)
C - "C" Cabinet
7 – Energy Recovery Type (ERT)
T - Total Energy Recovery Wheel
8 – Economizer Bypass (EBP)
E - Economizer Bypass
9 – Exhaust Blower Configuration (EBC)
3 - 20" Backward Inclined Airfoil Plenum Fan
6 - 28" Backward Inclined Airfoil Plenum Fan
10 - Exhaust Blower Motor HP (HP)
C or Q - 1hp
D or R - 1-1/2hp
E or S - 2hp
F or T - 3hp
G o r U - 5hp
H or V - 7-1/2hp
J or W - 10hp
C thru J include a factory mounted/wired motor starter.
Q thru W are Variable Frequency Drive (VFD) ready.
11 - Exhaust Blower Motor Type (MT)
1 - ODP - NEMA Premium Efficiency
2 - TE - NEMA Premium Efficiency
12 - ERM Supply Voltage (SV) (must match base model MPR unit)
4 - 208V/3ph
5 - 230V/3ph
6 - 460V/3ph
7 - 575V/3ph
13 - Exhaust Blower Sheave Assy (SA)
Refer to AccuSpec
14 – Electric Preheat (PH)
0 - No Heating
A - 20kW Electric (Nominal kW rating, derated for 208V/3ph.)

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
6
MCP15-525.0
Identification of Superheat Control
This manual includes information that varies based on the superheat controller used. The Atherion uses one of two different
superheat controllers. The controller can be identified in the unit serial number as follows:
If Digit 12=1, Emerson EC3 Superheat Control is used: If Digit 12=2, Carel EVD Superheat Control is used:
Sample Unit Serial Plate

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
7
Controller Overview
Description and Features
The Modine Control System utilizes a Carel pCO3programmable microprocessor controller. Highly advanced with a powerful
microprocessor and fast processing speed, the controller features a high number of I/O’s for complex HVAC/R applications.
The main controller board is housed in a plastic case that ensures a high index of protection and reduces the risk of electrostatic
discharges due to incorrect handling. The controller offers greater safety due to the optical isolation of the serial pLAN, protection
of the analog inputs in the event of incorrect connections, and an extended range of operating temperatures. Given the increasing
demand for integration, pCO3 can interface with BMS systems via many of the most commonly-used serial communication
standards, using optional boards.
Some of the features of the Carel pCO3programmable microprocessor controller include:
•10 Analog Inputs
oUses 10K NTC temperature sensors
o4-20ma Humidity and CO2 sensors for reliability
•6 Analog Outputs
o0-10vdc for easy fault finding
•18 Digital inputs
oUsed to monitor all aspects of the unit
•18 Digital Outputs
oTrue relayed outputs for reliability
•Real Time Clock
oWith battery backup and day light savings adjustment
•pLAN Communication
oTo allow connectivity to space sensors and other controllers
•Built In Display
oBacklit easy to use and easy to read
•Alarm Logging
oWith a snapshot of the unit sensors
•Run Hours logging
oWith maintenance setpoints
•Password Protection
oThree levels of password protection
•Manual Control
oFor easy startup and service
•Simple Interface
oEasy to understand menus and settings
•Built in Scheduler
oUp to 7 periods per day – Either On/Off control or Occupied/Unoccupied
oHoliday Scheduler with up to 20 holiday periods
•Remote Display option
oCan be 100ft from unit using standard RJ12 cable
•All reset points fully adjustable

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
8
MCP15-525.0
Standard and Optional Sensors Monitored
The Modine Control System monitors a number of sensors within the Atherion unit as follows:
Standard sensors monitored:
•Supply Air (Field Installed – see main unit Installation Manual)
oMain DOAS – HOAS control
•Outside Temperature (Unit Mounted) and Outside Humidity (Unit Mounted)
oUsed to calculate OA enthalpy and dew point
•Suction Pressure (Unit Mounted)
oUsed for superheat and dehumidification control
•Liquid Line Pressure (Unit Mounted)
oUsed for head pressure control
•Compressor High Pressure Switch (Unit Mounted)
oWith retry control
•Compressor Low Pressure Switch (Unit Mounted)
oWith retry control
•Supply Fan Air Proving Switch (Unit Mounted)
oPressure differential switch
•Damper End Switch (Unit Mounted)
oUsed to enable the supply fan
•Digital Compressor Alarm (Unit Mounted)
oMonitors the compressor protection and superheat modules
•Cooling Coil Condensate High Level Alarm (Unit Mounted)
oDisables the compressors if the drain pan is not draining properly
Optional sensors available:
•CO2Sensor (Field Installed)
oUsed for demand ventilation control
•Building Pressure Sensor (Field Installed)
oUsed to control supply fan, exhaust fan, or dampers
•Duct Pressure Sensor (Field Installed)
oUsed to control supply fan
•Return Air Sensor (Unit Mounted)
oOnly applicable if the unit has return air
•pAD Space Temperature and Humidity (Field Installed)
oUsed for space temperature and humidity control
•Filter Dirty Switch (Unit Mounted)
oPressure differential switch

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
9
PCO3Controller Layout
Reference Description
1 Power supply connector [G (+), G0 (-)]
2 Yellow power LED and 3 status LEDs
3 Additional power supply for the terminal and 0 to 5 V ratiometric probes
4 Universal analogue inputs: NTC, 0 to 1 V, 0 to 5 V ratiometric, 0 to 10 V, 0 to 20 mA, 4 to 20 mA
5 Passive analog inputs: NTC, PT1000, ON/OFF
6 0 to 10 V analog outputs
7 24 Vac/Vdc digital inputs
8 230 Vac or 24 Vac/Vdc digital inputs
9 Connector for the display panel (external panel with direct signals)
10 Connector for all standard pCO series terminals and for downloading the application program
11 Relay digital outputs
12 Connector for connection to the I/O expansion board
13 pLAN network connector
14 Cover for inserting the supervisor and maintenance option
15 Cover for inserting the field card option
16 Built-In terminal (LCD, buttons and LEDs)

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
10
MCP15-525.0
Display/Keypad Functions
pCO3Display Keypad pGD1 Remote Display Keypad (Optional)
Refer to Literature #MCP15-543 for installation instructions. Refer to
the Board Settings section for instructions on programming the remote
display keypad to the controller.
Standard Buttons
pCO3 Built-
in Display pGD1
Remote
Display Function Description
ALARM When one or more alarms are active the ALARM button will illuminate red.
Pressing the ALARM button once will indicate information regarding any active alarms.
Pressing the ALARM button twice will reset any active manual-reset alarms.
PRG Pressing the PRG button will select the main navigation menu.
ESC Pressing the ESC button will return the user to the main display screen showing unit
status.
UP Pressing the UP button can either:
Scroll through the various display screens, providing the cursor is in the top left position.
Increase the value of a set point adjustment.
ENTER Pressing the ENTER button will confirm any set point adjustments and move the cursor to
the next available set point.
DOWN Pressing the DOWN button can either:
Scroll through the various display screens, providing the cursor is in the top left position.
Decrease the value of a set point adjustment.
Extra Function Button Sequences
pCO3
Built-in Display pGD1
Remote Display Key
Combinations Description
+ + .+. .+.
UP + DOWN+
ENTER Allows access to controller address.
+ +
ALARM +
ENTER Allows access to controller system information.
+ + ENTER + UP Change unit on remote display keypad. (ERM Only)
Prg
Esc

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
11
Menu Navigation
The following instructions refer to the built-in display keypad buttons. See the table on the previous page for the corresponding
buttons if using the remote keypad.
The Main Status Screen is displayed when the unit is first turned on or after one minute of keypad inactivity. From this Main
Status Screen, eight sub menus can be accessed by pressing the button and using the or buttons to move to the
desired menu. The selected menu will be highlighted with a black bar. Press to enter the selected menu.
Navigation Sub Menus
Sub Menu Description
A. Unit On/Off Switch on or switch off the unit.
B. Setpoints View the user setpoints.
C. Clock/Scheduler View the current time and date and set on/off time zones.
D. Input/Output View the status of the controller inputs and outputs.
E. Alarm Log View the alarm log.
F. Board Switch Change the controller pLAN board address.
G. Service View maintenance related parameters, such as hours run, sensor calibration and manual overrides.
H. Manufacturer Manufacturer menu and adjustment of various manufacturer related parameters, such as unit
configuration and timing settings.
Details on the Main Status Screen and each sub menu will be covered in the following sections of this manual.
Example Navigation to On/Off Sub Menus
(Similar for all other sub menus):
From the Main Status Screen, press the key to access the Sub Menu selection screen. Use the or buttons to
navigate to the On/Off sub menu as shown in the following picture:
Press to access the On/Off sub menu screen:
Press to navigate to the parameter to change, then use the or button to change the value. Press again to confirm
the setting. Press the button to exit the sub menu screen, back to the Main Status Screen.
Prg
Prg
Esc

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
12
MCP15-525.0
Password Protection
WARNING
Improper control adjustments and manual mode
control can cause property damage, injury or
death. Read the installation, operating and
maintenance instructions thoroughly before
making adjustments.
To prevent unauthorized adjustments, a password is required to gain access to certain menus. When a password is requested
use the or keys to enter the number and to access the page. The passwords for the sub menus are as follows:
SETPOINTS: None
CLOCK/SCHEDULER: None
SERVICE SETTINGS: 0001
MANUFACTURER: Contact Modine
Adjusting Customer Control Settings
The following procedure is used to access and adjust control parameters (refer to Parameters List and Factory Values).
1. After entering the correct password the cursor will appear at the top left corner (Home location).
2. Use the or keys to move to the desired menu.
3. To move the flashing cursor to the required adjustable fields press .
4. Use the or keys to change the values and press the key to move the cursor to the next field or Home location.
5. When the cursor is Home either use the or keys to scroll to the next sub-menu or the key to exit and return to
the Main Menu page.
Esc

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
13
Main Menu – Tree of Functions
Irrespective of the current screen displayed, pressing the key accesses the main menu, as shown below:
Unit Status
A.
On/Off By Display
On/Off By pAD (Optional)
B.
Supply Air Setpint
Damper Min Position
Room Space Temperature (Optional)
Room Space Humidity (Optional)
Building Pressure (Optional)
C.
Date/time
Daylight Savings
Scheduler
Holidays
D.
a. Analog inputs
b. Digital inputs
c. Analog outputs
d. Digital outputs
E.
F.
G. Service
b. Information
d. Working Hours
e. BMS config.
f. Service Settings
a. Working hours set
b. Probe adjustment
c. Control Settings
d. User Dev/Change PW1
g. Manual Management
H. Manufacturer
a. Configuration
b. I/O Configuration
c. ERM (Optional)
d. Initialization
e. pAD settings (Optional)
To access the
branches in this
area, enter password
PW1
To access the
branches in this
area, enter password
PW2
Data Logger
Board Switch
On/Off Unit
Setpoints
Clock/Scheduler
Input/Output
Prg

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
14
MCP15-525.0
Main Status Screen
The Main Status Screen is displayed when the unit is first turned on or after one minute of keypad inactivity.
The following information is displayed on the Main Status Screen:
•Time/date
•Unit number
•Supply Air Temperature
•Current Supply Air Setpoint
•Unit Status
•Unit Mode
Once this screen is displayed, the user can navigate up and down through the list of Main Status Screen Parameters by using the
+ buttons. These screens are described in further detail in the next section.
Note that the main unit controller will always show as Unit: 01. If the unit is also equipped with an ERM module, it has its own
controller, which is Unit: 02. The keypad at the main controller or the remote key pad can be used to change the Main Status
Screen to display either Unit 01 or 02.
To change the controller being displayed, press the + buttons. If you are viewing the main controller display, pressing
those buttons will switch to displaying the ERM controller. Pressing those buttons again will revert back to displaying the main
controller.
Main Status Screen Parameters
The status screens can be seen when the + buttons are pressed on the Main Status Screen. The following table
describes the menu parameters (Note: Change in shading indicates change to next screen):
PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Time and date Current time and date
Unit network address Actual Value 1
Supply Air Temperature Actual Value °F / °C
Supply Air Setpoint Actual Value °F / °C
Unit Status Current status of unit
Unit On
OFF by Alarm
OFF by pLAN
OFF by BMS
OFF by Clock
OFF by Digital In
OFF by Keypad
OFF by Demand
OFF - Door Open
Off Manually
Wait - Damper
Wait Sup Fan
Occupied Mode Current Occupied Mode
Note: Unless a pAD Wall Stat is installed the
unit only operate in Occupied Mode
Unoccupied
Occupied – BMS
Occupied – CLK
Occupied – DIG
Occupied
Unit Mode Current Mode of operation
Venting
Cooling
Heating
Dehum
(continued on next page)

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
15
Main Status Screen Parameters (continued)
The status screens can be seen when the + buttons are pressed on the main status screen. The following table
describes the menu parameters (Note: Change in shading indicates change to next screen):
PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Note: The screen below will only be displayed if
the optional Space wall stat is installed (pAD)
pAD Space Temperature Actual Value °F / °C
pAD Space Humidity Actual Value %RH
pAD Space Enthalpy Actual Value (Calculated) BTU/Lb
pAD Space Dew Point Actual Value (Calculated) °F / °C
Note: The screen below will only be displayed if
the unit has a Return Air Damper or ERM
Return Temperature Actual Value °F /°C
Return Air Humidity Actual Value %RH
Return Air Enthalpy Actual Value (Calculated) BTU/Lb
Return Air Dew Point Actual Value (Calculated) °F /°C
Outside Air Temperature Actual Value °F /°C
Outside Air Humidity Actual Value %RH
Outside Air Enthalpy Actual Value (Calculated) BTU/Lb
Outside Air Dew Point Actual Value (Calculated) °F /°C
Note: The screen below will only be displayed if
the unit has an ERM module
ERM Leaving Air Temperature Actual Value °F /°C
ERM Leaving Air Humidity Actual Value %RH
ERM Leaving Air Enthalpy Actual Value (Calculated) BTU/Lb
ERM Leaving Air Dew Point Actual Value (Calculated) °F /°C
Cooling Demand Actual Value 0-100 %
Heating Demand Actual Value 0-100 %
Outside Air Damper Position Actual Value 0-100 %
Return Air Damper Position (Optional) Actual Value 0-100 %
Hot Gas Reheat Valve (If Enabled) Actual Value 0-100 %
Dehum Demand (If Enabled) Actual Value 0-100 %
Supply Fan Actual Value On or Off
Supply Fan Modulation (If Enabled) Actual Value 0-100 %
Exhaust Fan (If Enabled) Actual Value On or Off
Exhaust Fan Modulation (If Enabled) Actual Value 0-100 %
Note: The screen below will only be displayed if
the unit has an ERM module
ERM Exhaust Fan (If Enabled) Actual Value On or Off
ERM Exhaust Fan Modulation (If Enabled) Actual Value 0-100 %
(continued on next page)

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
16
MCP15-525.0
Main Status Screen Parameters (continued)
The status screens can be seen when the + buttons are pressed on the main status screen. The following table
describes the menu parameters (Note: Change in shading indicates change to next screen):
PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Note: The screen below will only be displayed if the unit
has an ERM module
ERM Wheel Actual Value On or Off
ERM Wheel Status (Optional) Actual Value Stopped or Running
Count On: Off:
Wheel minimum on and off counter Actual Value Sec
ERM By-Pass Damper Actual Value Open or Closed
ERM Pre-Heater On or Off
ERM Door Switch Open or Closed
Note: The screen below will only be displayed if the unit
has Gas or Electric Heat
Gas Or Electric Stages On Actual Value 0-2 (gas) 0-4 Elec. Heat
Heat Modulation Actual Value 0-100 %
Heating Lockout Warning Heating is locked out
Note: The screen below will only be displayed if the unit
is in EC3 Mode
Compressor 1 Status On or Off
Compressor 1 Minimum On Time Actual Value (Counts Down) 0-120 S
Compressor 1 Minimum Off Time Actual Value (Counts Up) 0-120 S
Compressor 2 Status On or Off
Compressor 2 Minimum On Time Actual Value (Counts Down) 0-120 S
Compressor 2 Minimum Off Time Actual Value (Counts Up) 0-120 S
Digital Compressor Modulation Actual Value 0-100 %
Note: The screen below will only be displayed if the unit
is in CDSS mode
Status (Digital Compressor)
Off
Start-up
On
Alarm
Off By Time
On By Time
Countdown Actual value S
Maximum Power Admitted Actual Value 0-100 %
Digital Compressor Actual Value On or Off
Valve Actual Value On or Off
Requested Capacity Actual Value 0-100 %
Current Capacity Actual Value 16.6-100 %
(continued on next page)

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
17
Main Status Screen Parameters (continued)
The status screens can be seen when the + buttons are pressed on the main status screen. The following table
describes the menu parameters (Note: Change in shading indicates change to next screen):
PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Note: The screen below will only be displayed if the unit
is in CDSS mode
Compressor 2 Status On or Off
Compressor 2 Minimum On Time Actual Value (Counts Down) 0-120 S
Compressor 2 Minimum Off Time Actual Value (Counts Up) 0-120 S
Note: The screen below will only be displayed if the unit
is in CDSS mode
Cooling Lockout
Compressor Enthalpy Lockout
No Enthalpy Lockout
Enthalpy LO Comp 1
Enthalpy LO Comp 2
Enthalpy LO Comp 1&2
Compressor Lockout Compressor Held Off by
Lockout timers
Condenser Fan Modulation Actual Value 0-100 %
Discharge Pressure Actual Value PSIG
Discharge Temperature (If in CDSS Mode) Actual value °F /°C
Suction Pressure Actual Value PSIG
Note: The screen below will only be displayed if the unit
is in CDSS mode
Liquid Line Temperature Actual value F /°C
Condensing Temperature Calculated F /°C
Sub-Cool Calculated F /°C
Capacity Reduction Actual Value 0-100 %
Note: The screen below will only be displayed if the unit
is in CDSS mode
Super-Heat Calculated F /°C
Suction Line Temperature Actual Value F /°C
Suction Pressure Actual Value PSIG
Evaporating Temperature Calculated F /°C
EEV Valve Steps Actual Value Depends On Valve Type Steps
EEV Value Percentage Actual Value 0-100 %
Valve Regulation
Close
On
Position
Wait
Stand-By
Note: The next screen will only be displayed if a clock
schedule is enabled
Clock Override On or Off
Override Time 1-9 Hrs.
Manual Control Status & Reset Actual Value
I/O Automatic or
I/O Manual
Reset Manual Controls

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
18
MCP15-525.0
On/Off Sub Menu
Main Status Screen On/Off
The following table describes the menu parameters (Note: Change in shading indicates change to next screen):
PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Unit Address 1
Power By Display Actual Value On or Off
Status Actual Value
Unit On
OFF by Alarm
OFF by pLAN
OFF by BMS
OFF by Clock
OFF by Digital In
OFF by Keypad
OFF by Demand
OFF - Door Open
Off Manually
Wait - Damper
Wait Sup Fan
Note: The screen below will only be displayed if the
optional Space wall stat is installed (pAD)
pAD Number Actual Value 1
On / Off Permanently Off - On or Off

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
MCP15-525.0
19
Setpoint Sub Menu
Main Status Screen Setpoint
The following table describes the menu parameters (Note: Change in shading indicates change to next screen):
PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Supply Air Setpoint 70 50-99 °F /°C
Current Setpoint Actual Value °F /°C
Note: The screen below will only be displayed if the optional Space wall
stat is installed (pAD)
pAD Thermostat Number Actual Value
Space Cooling Temperature Setpoint
Note:Heating Setpoint equals cooling setpoint minus 4°F 74 50-100 °F / °C
Space Humidity Setpoint 60 30-100 %RH
Space Humidity Differential 5 0-10 %
Unoccupied Cooling Setpoint 85 60-100 °F / °C
Unoccupied Heating Setpoint 62 40-100 °F / °C
Note: The screen below will only be displayed if Dew Point
Dehumidification is enabled
Occupied OA Dew point Setpoint 55 40-70 °F /°C
Occupied OA Dew point Differential 3 0-10 °F /°C
Unoccupied Space Dew point Setpoint 55 40-70 °F /°C
Unoccupied Space Dew point Differential 3 0-10 °F /°C
Note: The screen below will only be displayed if the optional space wall
stat is installed (pAD)
Occupied Space Humidity Setpoint 60 30-100 %RH
Occupied Space Humidity Differential 5 0-10 %
Unoccupied Space Humidity Setpoint 60 30-100 %RH
Unoccupied Space Humidity Differential 5 0-10 %
Note: The screens below will only be displayed if the unit is setup for
HOAS damper control
Outside Air Minimum Damper Position
Note:The Return Air Damper (Optional) will be the inverse of this value Setting depends on Unit type 0-100 %
OA Damper Position 1
Note:The Return Air Damper (Optional) will be the inverse of this value 30% ID15 and ID 16 Open 0-100 %
OA Damper Position 2 50% ID15 Closed ID 16 Open 0-100 %
OA Damper Position 3 75% ID15 Open ID 16 Closed 0-100 %
OA Damper Position 4 100% ID15 and ID 16 Closed 0-100 %
Note: The Screen below will only be displayed if Damper CO2 Control is
selected
CO2 Setpoint 800 0-2000 PPM
CO2 Level Actual Value 0-2000 PPM
(continued on next page)

MODINE CONTROL SYSTEM MANUAL
Models MPR & ERM
20
MCP15-525.0
Setpoint Sub Menu (continued)
Main Status Screen Setpoint
The following table describes the menu parameters (Note: Change in shading indicates change to next screen):
PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Note: The Screen below will only be displayed if Damper Building
Pressure Control is selected
Building Pressure Setpoint 0.2 0-0.5 Inch W.G.
Building Pressure Actual Value 0-0.5 Inch W.G.
Note: The screen below will only be displayed if Supply Fan CO2 Control
is selected
CO2 Setpoint 800 0-2000 PPM
CO2 Level Actual Value 0-2000 PPM
Note: The Screen below will only be displayed if Supply Fan Building
Pressure Control is selected
Building Pressure Setpoint 0.2 0-0.5 Inch W.G.
Building Pressure Actual Value 0-0.5 Inch W.G.
Note: The screen below will only be displayed if Supply Fan Duct Static
Pressure Control is selected
Duct Static Pressure Setpoint 1.0 0-5 Inch W.G.
Duct Pressure Actual Value 0-5 Inch W.G.
Note: The Screen below will only be displayed if Supply Fan Constant
Volume Control is selected
Supply Fan Speed 1
100% ID15 and ID 16 Open 0-100 %
Supply Fan Speed 2 85% ID15 Closed ID 16 Open 0-100 %
Supply Fan Speed 3 75% ID15 Open ID 16 Closed 0-100 %
Supply Fan Speed 4 50% ID15 and ID 16 Closed 0-100 %
Note: The screen below will only be displayed if Exhaust Fan Building
Pressure On/Off Control is selected
Building Pressure Setpoint 0.2 0-0.5 Inch W.G.
Building Pressure Differential 0.1 0-0.5 Inch W.G.
Building Pressure Actual Value 0-5 Inch W.G.
Note: The Screen below will only be displayed if Exhaust Fan Building
Pressure Control is selected
Building Pressure Setpoint 0.2 0-0.5 Inch W.G.
Building Pressure Actual Value 0-0.5 Inch W.G.
Note: The screen below will only be displayed if Exhaust Fan Offset
(from Supply Fan) Control is selected
Exhaust Fan Offset Setpoint (From Sup. Fan) 20 0-100 %
(continued on next page)
Other manuals for Atherion MPR
1
This manual suits for next models
1
Table of contents
Other Modine Manufacturing Control System manuals

Modine Manufacturing
Modine Manufacturing 5H104766 User manual

Modine Manufacturing
Modine Manufacturing Airedale ClassMate CMD User manual

Modine Manufacturing
Modine Manufacturing Varsity User manual

Modine Manufacturing
Modine Manufacturing pGD-t User manual

Modine Manufacturing
Modine Manufacturing Airedale Sentinel User manual