Modine Manufacturing Airedale ClassMate CMD User manual

THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
IMPORTANT
1. The use of this manual is specifically intended
for a qualified installation and service agency.
All installation and service of this unit must be
performed by a qualified installation and service
agency.
2. These instructions must also be used in
conjunction with the Installation and Service
Manual originally shipped with the appliance, in
addition to any other accompanying component
supplier literature.
3. This manual applies to Modine Controls System
program version series 1. For any other version,
please contact Modine. The program version
that resides in the unit controller can be found
in the Information section of the Installer Sub
Menu. Refer to the manual for instructions on
accessing this screen.
WARNING
1. Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death. Read the installation,
operating and maintenance instructions
thoroughly before installing or servicing this
equipment.
2. Disconnect power supply before making wiring
connections to prevent electrical shock and
equipment damage.
3. Improper control adjustments and manual mode
control can cause property damage, injury or
death. Read the installation, operating and
maintenance instructions thoroughly before
making adjustments.
MODINE CONTROLS SYSTEM MANUAL
ClassMate® and SchoolMate® Units
Models CMD/CMP/CMS, and SMG/SMW
AIR74-525.1
5H1046210000
July, 2016

2
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
2
General Information
Table of Contents
Table 2.1 - Acronyms Used
Controls are one of the most important components of
specialized HVAC equipment. The Modine Controls
System is designed and engineered for the ClassMate and
SchoolMate units to ensure that they will operate safely,
reliably, with optimized performance, and maintain maximum
energy efficiency.
AcronymsCommonlyUsedInController.................................2
Controller Overview...............................................................3
DescriptionandFeatures..........................................3
StandardandOptionalSensors Monitored................3
ModelNomenclature-ClassMate...........................................4
ModelNomenclature-SchoolMate.........................................4
Figure8.1pCOOEM+ControllerLayout.....................3
Display/Keypad Functions.....................................................6
Table9.1StandardButtons......................................10
Table9.12ExtraFunctionButtonSequences............10
MenuNavigation.....................................................11
Table10.1NavigationSubMenus............................11
ExampleNavigationtoOn/OffSubMenus.................11
Password Protection..............................................12
AdjustingCustomerControlSettings.......................12
MainMenu–TreeofFunctions..............................................12
MainStatusScreenParameters..............................10
On/OffSubMenu..................................................................13
SetpointSub Menu...............................................................14
Clock/SchedulerSubMenu..................................................15
Input/OutputSubMenu........................................................14
DataLoggerSubMenu.........................................................15
BoardSwitchSubMenu........................................................12
RemoteDisplayKeypadtoController.......................10
ServiceSubMenu................................................................16
Information............................................................16
WorkingHours........................................................17
BMS Configuration.................................................17
WorkHourSetpoint.................................................18
ProbeAdjustment...................................................19
ManualManagement..............................................17
Analog Input...........................................................18
Digital Input............................................................19
Relay Output..........................................................19
Analog Output........................................................19
Unit Alarms..........................................................................20
MainUnitControllerInputs/Outputs......................................22
TypicalBMS–EMS–BASSystemVariables..........................23
Acronym Phrase
BMS Building Management System
BPS Bits Per Second
CCS Capacity Control Solenoid
CF Condenser Fan
CFM Cubic Feet per Minute
Comp Compressor
Dehum De-humidify
Diff Difference
EA Exhaust Air
Econ Economizer
Elec Electric
ERV Energy Recovery Ventilator
Ex Exhaust
HGRH Hot Gas Re-Heat
hr Hour
Ht Heat
ID Fan Indoor Fan
LL Liquid Line
min “Minutes” or “Minimum”
Mod Mode
OA Outside Air
Perc Percentage “%”
psig Pounds per Square Inch gage
RA Return Air
Rev Vl Reversing Valve
RH Relative Humidity
s Seconds
SA Supply Air
SetPt Setpoint
Sp Speed
St-by Standby
Str Start
Temp Temperature
Vlv valve

3
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1 3
Controller Overview
Description and Features
The Modine Controls System utilizes a Carel pCOOEM+
programmable microprocessor controller. Highly ad-
vanced with a powerful microprocessor and fast process-
ing speed, the controller features a high number of I/O’s
for complex HVAC/R applications.
The main controller board is housed in a plastic case that
ensures a high index of protection and reduces the risk
of electrostatic discharges due to incorrect handling. The
controller offers greater safety due to the optical isolation
of the serial pLAN, protection of the analog inputs in the
event of incorrect connections, and an extended range of
operating temperatures. Given the increasing demand for
integration, pCOOEM+ can interface with BMS systems
via many of the most commonly-used serial communi-
cation standards, using optional boards. Some of the
features of the Carel pCOOEM+ programmable micropro-
cessor controller are listed below.
pCOOEM+ Main Features:
●12 Universal Inputs
◦Uses 10K NTC temperature sensors
◦4-20mA humidity and CO2 sensors for reliability
●5 Analog Outputs
◦0-10 Vdc for emodulating control
●8 Digital inputs
◦Used to monitor all aspects of the unit
●13 Digital Outputs
◦True relayed outputs for reliability
●Real Time Clock
◦With battery backup and daylight savings adjust-
ment
●pLAN Communication
◦To allow connectivity to space sensors and other
controllers
●Alarm Logging
◦With a snapshot of the unit sensors
●Run Hours Logging
◦With maintenance setpoints
●Password Protection
◦Two levels of password protection
●Manual Control
◦For easy startup and service
●Simple Interface
◦Easy to understand menus and settings
●Built in Scheduler
◦Up to 7 periods per day - Either On/Off control or
Occupied/Unoccupied
◦Holiday scheduler with up to 16 holiday periods
●Remote Display Option
◦Can be 100 ft from unit using standard RJ12 cable
●All reset points fully adjustable

4
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Standard and Optional Sensors Monitored
The Modine Controls System monitors a number of sensors within the ClassMate and SchoolMate units as follows:
Standard sensors monitored:
●Supply Air Temperature (Unit Mounted)
◦Used to monitor supply air temperature; supply air
limit control
●Return Air Temperature (Unit Mounted)
◦Used to monitor space temperature
●Indoor Coil Temperature (Unit Mounted)
◦Used as a limit on the indoor coil to prevent frost
buildup
●Outside Air Temperature (Unit Mounted)
◦Used in Econ Control, Hot Water Control and Com-
pressor Lockout
●Compressor High Pressure Switch (Unit Mounted)
◦With retry control
●Compressor Low Pressure Switch (Unit Mounted)
◦With retry control
●Geo Water Out (Unit Mounted On Schoolmate Units
only)
◦Displays the liquid temperature while leaving the
unit
●Outside Coil Temperature (Unit Mounted)
◦Used for defrost control
Optional sensors available:
●CO2 Sensor (Unit Mounted)
◦Measures Return Air CO2 level for ventilation
●Outside Temperature and Outside Humidity
◦Used to calculate OA enthalpy and dew point
●pAD Space Temperature and Humidity (Field In-
stalled or Unit Mounted)
◦Used for space temperature and humidity control
●Liquid Line Pressure (Unit Mounted)
◦Used for head pressure control for dehumidifica-
tion
●Dirty Filter Switch (Unit Mounted)
◦Used to monitor pressure drop through the filter
●Condensate Float Switch High Level Alarm (Unit
Mounted)
◦Disables the compressors if the drain pan is not
draining properly
●Mechanical Temperature only Thermostat (Field
installed or Unit Mounted)
◦Slight manual adjustment of temperature set-
points
●Freeze Thermostat (Unit Mounted)
◦Coil Freeze protection
●Occupancy Sensor (Field Installed or Unit Mounted)
◦Infrared motion detector
●Current Switch (Unit Mounted)
◦Verifies component is functioning

5
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
5
Model Nomenclature - ClassMate
1,234,56789101112131415,16
PT UC MBH SV G C VC F CC DS DO D HO
1,2 - Product Type (PT)
CM - ClassMate
3 - Unit Configuration (UC)
D - DX Cooling
P - HP Heating & Cooling
S - Split Fan Coil Unit
4,5 - Nominal Capacity (MBH)
24 - 24,000 Btu/Hr
36 - 36,000 Btu/Hr
48 - 48,000 Btu/Hr
60 - 60,000 Btu/Hr
6 - Supply Voltage (SV)
B - 208/60/1
C - 230/60/1
D - 208/60/3
E - 230/60/3
F - 460/60/3
G - 575/60/3
H - 277/60/1
7 - Generation (G)
A - Current Design
8 - Control (C)
M - Modine Control System
F - Factory Installed Free Issue
B - By Others - Field Installed
9 - Ventilation Configuration (VC)
CMD & CMP
A - Economizer
B - Economizer with OA Damper
C - ERV with OA Damper
D - ERV with OA Damper & Economizer
E - ERV with OA & RA Damper & Economizer
Z - Return Air Only
CMS - No Exhaust
A - Economizer
B - Economizer with OA Damper
Z - Return Air Only
CMS - Gravity Damper
F - Economizer
G - Economizer with OA Damper
H - ERV with OA Damper
J - ERV with OA Damper & Economizer
K - ERV with OA & RA Damper & Economizer
CMS - Powered Exhaust
L - Economizer
M - Economizer with OA Damper
N - ERV with OA Damper & Economizer
P - ERV with OA & RA Damper & Economizer
10 - Filtration (F)
A - MERV 8
B - MERV 11
C - MERV 13
D - MERV 16
11 - Case Construction (CC)
A - 20Ga (Standard)
B - 16Ga
S - STUDY Package 20Ga
12 - Door Mounted Stat (DS)
N - None
V - Vertical Stat
H - Horizontal Stat
13 - Door Mounted Other (DO)
N - None
K - Key Over-ride
S - Occupancy Sensor
L - Indicator Light
T - Twist Timer
14 - Dehumidification (D)
N - None
A - HGRH Coil
15,16 - Heating Option (HO)
00 - None
02 - 2 kW (1-stage)
03 - 3 kW (1-state)
04 - 4 kW (1-stage)
05 - 5kW (1-stage)
08 - 7.5 kW (1-stage)
09 - 9kW (1-stage)
10 - 10 kW (2-stage)
12 - 12kW (2-stage)
15 - 15 kW (2-stage)
18 - 18 kW (2-stage)
20 - 20 kW (2-stage)
81 - 1R HW Coil (1/2") - Bottom Connection
82 - 1R HW Coil (3/4") - Bottom Connection
83 - 2R HW Coil (1/2") - Bottom Connection
84 - 2R HW Coil (3/4") - Bottom Connection
91 - 1R HW Coil (1/2") - Top Connection
92 - 1R HW Coil (3/4") - Top Connection
93 - 2R HW Coil (1/2") - Top Connection
94 - 2R HW Coil (3/4") - Top Connection

6
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Model Nomenclature - SchoolMate
1,2 - Product Type (PT)
SM - SchoolMate
3 - Unit Configuration (UC)
G - Ground Source
W - Water Source
4,5 - Nominal Capacity (MBH)
24 - 24,000 Btu/Hr
30 - 30,000 Btu/Hr
36 - 36,000 Btu/Hr
42 - 42,000 Btu/Hr
48 - 48,000 Btu/Hr
60 - 60,000 Btu/Hr
6 - Supply Voltage (SV)
B - 208/60/1
C - 230/60/1
D - 208/60/3
E - 230/60/3
F - 460/60/3
G - 575/60/3
H - 277/60/1
7 - Generation (G)
A - Current Design
8 - Control (C)
M - Modine Control System
F - Factory Installed Free Issue
B - By Others - Field Installed
9 - Ventilation Configuration (VC)
No Exhaust
A - Economizer
B - Economizer with OA Damper
Z - Return Air Only
Gravity Exhaust
F - Economizer
G - Economizer with OA Damper
H - ERV with OA Damper
J - ERV with OA Damper & Economizer
K - ERV with OA & RA Damper & Economizer
Powered Exhaust
L - Economizer
M - Economizer with OA Damper
N - ERV with OA Damper & Economizer
P - ERV with OA & RA Damper & Economizer
10 - Filtration (F)
A - MERV 8
B - MERV 11
C - MERV 13
D - MERV 16
11 - Case Construction (CC)
A - 20Ga (Standard)
B - 16Ga
S - STUDY Package 20Ga
12 - Door Mounted Stat (DS)
N - None
V - Vertical Stat
H - Horizontal Stat
13 - Door Mounted Other (DO)
N - None
K - Key Over-ride
S - Occupancy Sensor
L - Indicator Light
T - Twist Timer
14 - Dehumidification (D)
N - None
A - HGRH Coil
15,16 - Heating Option (HO)
00 - None
02 - 2 kW (1-stage)
03 - 3 kW (1-state)
04 - 4 kW (1-stage)
05 - 5kW (1-stage)
08 - 7.5 kW (1-stage)
09 - 9kW (1-stage)
10 - 10 kW (2-stage)
12 - 12kW (2-stage)
15 - 15 kW (2-stage)
18 - 18 kW (2-stage)
20 - 20 kW (2-stage)
81 - 1R HW Coil (1/2") - Bottom Connection
82 - 1R HW Coil (3/4") - Bottom Connection
83 - 2R HW Coil (1/2") - Bottom Connection
84 - 2R HW Coil (3/4") - Bottom Connection
91 - 1R HW Coil (1/2") - Top Connection
92 - 1R HW Coil (3/4") - Top Connection
93 - 2R HW Coil (1/2") - Top Connection
94 - 2R HW Coil (3/4") - Top Connection
17 - Coaxial Coil Option (CO)
1 - Copper (Standard Bottom Pipe Connections)
2 - Cupro-nickel (Standard Bottom Pipe Connections)
3 - Copper (Top Pipe Connections)
4 - Cupro-nickel (Top Pipe Connections)
1,234,56789101112131415,16 17
PT UC MBH SV G C VC F CC DS DO D HO CO

7
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1 7
Figure 7.1 - pCOOEM+ Controller Layout
Table 7.1 - pCO1Controller Layout Descriptions
Reference Description
1 Power supply connector [G (+), G0 (-)]
2 Button for setting pLAN Address and secondary display, LEDs
3 Universal inputs/outputs (Refer to page 31-32 for descriptions)
4 +Vdc: power to active probes ; +5VR power to ratiometric probes
5 Analog outputs
6 DI (Digital inputs): voltage free contact digital inputs
7DI..: digital inputs at 24Vac or 28 to 36 Vdc ; DIH (Digital Inputs High): digital inputs at 230Vac -50/60
Hz.
8 +Vout: power to additional terminal
9 Fieldbus 1 Connector
10 BMS2 Connector
11 Unipolar Valve Connectors
12 pLAN plug-in connector
13 pLAN telephone connector for remote terminal/downloading application program
14 BMS1 optional card connector
15 PLD terminal connector
16 Relay digital outputs
17 Powered-on relay digital outputs
18 Power supply for “powered-on relay digital outputs”
19 Fieldbus2 Connector
20 Microswitch to select Rs485/tLAN level on Fieldbus1

8
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Display/Keypad Functions
Figure 8.1 pGD1 Remote Display Keypad (Optional)¹
1 Refer to Literature AIR 2-542 for installation instructions and AIR 2-526 for quick start guide. Normally the keypad
display is automatically addressed by the controller. In the event that the keypad is not recognized refer to the Board
Settings section for instructions on programming the remote display keypad to the controller.
Table 8.1 - Standard Buttons
pGD1
Remote
Display
Function Description
ALARM
When one or more alarms are active the ALARM button will blink/flash red.
Pressing the ALARM button once will indicate information regarding any active alarms.
Pressing the ALARM button twice will reset any active manual-reset alarms.
PRG Pressing the PRG button will select the main navigation menu.
ESC Pressing the ESC button will return the user to the main display screen showing unit status.
UP
Pressing the UP button can either:
Scroll through the various display screens, providing the cursor is in the top left position.
Increase the value of a setpoint adjustment.
ENTER Pressing the ENTER button will confirm any set point adjustments and move the cursor to the next
available setpoint.
DOWN
Pressing the DOWN button can either:
Scroll through the various display screens, providing the cursor is in the top left position.
Decrease the value of a setpoint adjustment.
pGD1
Remote
Display
Function Description
UP + DOWN+ ENTER Allows access to controller address.
ALARM + ENTER Allows access to controller system information.
Table 8.2 - Extra Function Button Sequences

9
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Menu Navigation
The following instructions refer to using the remote keypad for navigating the menu and changing settings.
The Main Status Screen is displayed when the unit is first turned on or after five minutes of keypad inactivity. From this
Main Status Screen, eight sub menus can be accessed by pressing the PRG button and using the UP or DOWN buttons
to move to the desired menu. The selected menu will be highlighted with a black bar. Press ENTER to enter the selected
menu.
Sub Menu Description
A. Unit On/Off Switch on or switch off the unit.
B. Setpoints View the user setpoints.
C. Clock/Scheduler View the current time and date, and set time zones on/off.
D. Input/Output View the status of the controller inputs and outputs.
E. Alarm Log View the alarm log.
F. Board Switch Change the controller pLAN board address.
G. Service View maintenance related parameters, such as hours run, sensor calibration
and manual overrides.
H. Manufacturer Manufacturer menu and adjustment of various manufacturer related
parameters.
Table 9.1 - Navigation Sub Menus
From the Main Status Screen, press the PRG key to access the Sub Menu selection screen. Use the UP or DOWN
buttons to navigate to the On/Off sub menu as shown in the following picture:
Example Navigation to On/Off Sub Menus (Similar for all other sub menus):
Details on the Main Status Screen and each sub menu will be covered in the following sections of this manual.
Press ENTER to access the On/Off sub menu screen:
Press ENTER to navigate to the parameter to change, then use the UP or DOWN button to change the value. Press
again to confirm the setting. Press the ESC button to exit the sub menu screen and to return to the Main Status Screen

10
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Main Menu - Tree of Functions
WARNING
Improper control adjustments and manual mode
control can cause property damage, injury or
death. Read the installation, operating and
maintenance instructions thoroughly before making
adjustments.
Password Protection
To prevent unauthorized adjustments, a password is
required to gain access to certain menus. When a
password is requested use the UP or DOWN keys to
enter the number and ENTER to access the pate. The
passwords for the sub menus are as follows:
SETPOINTS: None
CLOCK/SCHEDULER: None
PW1: SERVICE SETTINGS: 1500
MANUFACTURER: Contact Modine
Adjusting Customer Control Settings
The following procedure is used to access and adjust control
parameters (refer to Parameters List and Factory Values
pages 13-28).
1. After entering the correct password the cursor will appear
at the top left corner (home location).
2. Use the UP or DOWN keys to move to the desired menu.
3. To move the flashing cursor to the required adjustable
fields press ENTER.
4. Use the UP or DOWN keys to change the values and
press the ENTER key to move the cursor to the next field or
home location.
5. When the cursor is home either use the UP or DOWN
keys to scroll to the next sub-menu or the ESC key to exit
and return to the main menu page.
Regardless of the current screen displayed,
pressing the PRG key accesses the main
menu as shown below:

11
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Main Status Screen
The main status screen is displayed when the unit is first turned on or after five minutes of keypad inactivity.
The following information is displayed on the main screen:
●Time/date
●Unit number
●Return / space air temperature
●Current return / space air setpoint
●Unit status
●Unit mode
Figure 12.1 Main Status Screen
Once this screen is displayed, the user can navigate up and down through the list of main status screen parameters by
using the UP or DOWN buttons. These screens are described in further detail in the next section
Main Status Screen Parameters
The status screens can be seen when the UP or DOWN buttons are pressed on the main status screen. The following
table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using the UP or
DOWN buttons):
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Main Screen
Time and date Current time and date - -
Unit network address Actual Value 1 to 32 -
Control Temperature Source Actual Value Return Air
Space pAD
Space FW Stat -
Control Temperature Actual Value - °F / °C
Econ (If Enabled) Actual Value 0-100 %
SetPt C-H: (Cooling and Heating Setpoints) Actual Value - °F / °C
Unit Status Current status of unit
Waiting
Unit On
OFF by Alarm
OFF by pLAN
OFF by BMS
OFF by Clock
OFF by Input
OFF by Keypad
OFF by Manual
Unoccupied
Warmup
Occupied
Standby
Unit Mode Current Mode of
operation
Cooling
Econ Cooling
Heating
Dehum
-
Space Temperatures
(Screen Visible only if
pAD is Enabled)
pAD Temperature: Actual Value - °F / °C
pAD Humidity: (If Available on pAD) Actual Value 0-100 %

12
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Main Status Parameters (continued)
The status screens can be seen when the UP or DOWN buttons are pressed on the main status screen. The following
table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using the UP or
DOWN buttons):
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Temperatures
Return Air: Actual Value - °F / °C
Outside Air: (If Enabled) Actual Value - °F / °C
Supply Air: Actual Value - °F / °C
Indoor Coil: Actual Value - °F / °C
Outdoor Coil / Coax Water Out: (If Enabled) Actual Value - °F / °C
Control Temp: Actual Value - °F / °C
Faceless Wall Stat
Modbus Address: Actual Value 0-128 -
Temperature: Actual Value - °F / °C
Humidity: Actual Value 0-100% %
Dew Point: Actual Value (Calculated) - °F / °C
Humidity / CO2
(Screen Visible only
if CO2 or Humidity
sensors are Enabled)
CO2 Level: (If Enabled) Actual Value 0-2000 PPM
Outside Air Humidity: (If Enabled) Actual Value 0-100 %RH
Return Air Humidity: (If Enabled) Actual Value 0-100 %RH
Outside Air Enthalpy: (If Enabled) Actual Value (Calculated) 0-9999.9 BTU/Lb.
Inside Air Enthalpy: (If Enabled) Actual Value (Calculated) 0-9999.9 BTU/Lb.
Compressor Status
Defrosting Status: Actual Value ON/OFF -
Compressor: Actual Value ON/OFF -
Countdown On: Actual Value 0-60 s
Countdown Off: Actual Value 0-60 s
Coax Valve Poss: Actual Value 0-100 %
LL Pressure : (If Enabled) Actual Value 0-600 psig
ERM Output Status
(Screen only visible if
ERM is Enabled)
ERM Wheel: (If Enabled) Actual Value Running or Stopped -
Defrosting Status: Actual Value ON/OFF -
Outside Air Fan: (If Enabled) Actual Value ON/OFF -
EA Vent Fan: (If Enabled) Actual Value ON/OFF -
ERM Fan Mod: (If Enabled) Actual Value 0-999 cfm
Outside Air Damper: (If Enabled) Actual Value Closed or Open -
Output Status (Page
1)
ID Fan: (Supply Fan) Actual Value ON/OFF -
Fan HI: (Supply Fan Hi Setting) Actual Value ON/OFF -
Comp: (Compressor 1st stage) Actual Value ON/OFF -
Comp HI: (Compressor 2nd stage) Actual Value ON/OFF -
Rev Vl: (Reversing Valve) (If Enabled) Actual Value ON/OFF -
HGRH: (If Enabled) Actual Value ON/OFF -
Electric Heat 1: (If Enabled) Actual Value ON/OFF -
Electric Heat 2: (If Enabled) Actual Value ON/OFF -

13
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Main Status Parameters (continued)
The status screens can be seen when the UP or DOWN buttons are pressed on the main status screen. The following
table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using the UP or
DOWN buttons):
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Output Status
(Page 2)
(Screen only visible
with Exhaust fan.)
Exhaust Fan: (If Enabled) Actual Value ON/OFF -
Exhaust Fan speed: (If Enabled) Actual Value 0-100 %
Demand Status
Cooling Demand: Actual Value 0-100 %
Heating Demand: (If Enabled) Actual Value 0-100 %
Hot Water Valve position: (If Enabled) Actual Value 0-100 %
Baseboard Heating: (If Enabled) Actual Value 0-100 %
BaseBoard Heat Baseboard Heat Type: Actual Value Analogue 0-10vDC
Digital 1 Stage
Digital 2 Stage -
Baseboard Heat Demand: Actual Value 0-100 %
BaseBoard Heat Digital Stage 1: Actual Value ON/OFF -
Digital Stage 2: (if Enabled) Actual Value ON/OFF -
Scheduler Clock Override: Actual Value ON/OFF -
Override Time: Actual Value 0-4 Hours
Manual Control
Status Unit in Manual: No No or Yes -
Reset Unit to Auto: Actual Value No or Yes -
On/Off Sub Menu
The following table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using
the UP or DOWN buttons):
Main Status Screen = On/Off
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
On/Off Unit
Unit address Actual Value 1-32 -
Power by Display Off On or off -
Status Off By Keypad
WAITING
UNIT ON
OFF by pLAN
OFF by BMS
OFF by CLOCK
OFF by INPUT
OFF by KEYPAD
OFF by MANUAL
Unoccupied
Warmup
Occupied
Standby
-
On/Off Unit
(Screen visible only
With pAD Enabled)
pAD Address 1-32 -
On/Off Off On
Off
Permanently Off -

14
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Setpoint Sub Menu
The following table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using
the UP or DOWN buttons):
Main Status Screen = Setpoint
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Occupied Setpoints
Cooling setpoint: 74.0°F 50.0°F-90.0°F °F / °C
Heating Offset: (if unit has Heat) 4.0°F 0.0°F-40.0°F °F / °C
Heating setpoint: (Calculated by : Cooling setpoint - Heating
Offset) 70.0°F -°F / °C
Unoccupied Setpoints Unoccupied Cooling Setpoint: 85.0°F 50.0°F-90.0°F °F / °C
Unoccupied Heating Setpoint: (if unit has Heat) 62.0°F 50.0°F-90.0°F °F / °C
Standby Setpoints
( Screen only Visible If
Occupancy Type is Clock or
BMS)
St-by Cool Set: (Standby Cooling Setpoint) 78.0°F 50.0°F-90.0°F °F / °C
St-by Heat: (Standby Heating Setpoint) 66.0°F 50.0°F-90.0°F °F / °C
St-by Hum: (Standby Humidity Setpoint) 60%RH 0%-100% %RH
Dehum Setpoints Humidity
Control
( Screen only Visible with
Humidity Sensor)
Occupied Set: 60%RH 0%-100% %RH
Unoccupied Set: 70%RH 0%-100% %RH
Differential: 5%RH 0%-10% %RH
Temp Low Diff Above Ht. Setpt.: 1.0°F 1.0°F-4.0°F °F / °C
Ventilation Setpoints
(Screen Only visible with Econ
Damper Only - CO2 Disabled) Econ. Damper Min. Position: 20.0% 0-100 %
Ventilation Setpoints
(Screen Only visible with ERM
Only - CO2 Disabled) ERM OA & EA Fans Vent Rate: 350CFM 0-500 CFM
Ventilation Setpoints
(Screen Only visible with Econ
Damper & ERM - CO2 Disabled)
Econ. Damper Min. Position: 0.0% 0-100 %
ERM OA & EA Fans Vent Rate: 350CFM 0-500 CFM
Ventilation Setpoints
(Screen Only visible with Econ
Damper Only - CO2 Enabled)
CO2 Control Econ. Damper
Low CO2 Setp: 800PPM 0-9999 PPM
Min. Position: 20.0% 0.0-100.0 %
Hi. CO2 Setp: 100PPM 0-9999 PPM
Hi. CO2 Min Pos: 40.0% 0.0-99.9 %
Ventilation Setpoints
(Screen Only visible with ERM
Only - CO2 Enabled)
CO2 Control ERM OA & EA Fans
Low CO2 Setp: 800PPM 0-9999 PPM
Low Vent Rate: 350CFM 0-500 CFM
Hi. CO2 Setp: 1000PPM 0-9999 PPM
Hi. Vent Rate: 500CFM 0-500 CFM
Ventilation Setpoints
(Screen Only visible with Econ
Damper & ERM - CO2 Enabled)
Low CO2 Setp: 800PPM 0-9999 PPM
Low Vent Rate: 350CFM 0-500 CFM
Hi. CO2 Setp: 1000PPM 0-9999 PPM
Hi. Vent Rate: 500CFM 0-500 CFM
Low CO2 Econ Min: 0.0% 0.0-99.9 %
Hi. CO2 Econ Min: 40.0% 0.0-99.9 %
CO2 Setpoints
(Screen Only visible CO2 Sensor
& CO2 Standby enabled) CO2 Standby Enable Setpoint: 500PPM 0-2000 PPM

15
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Clock/Scheduler Sub Menu
NOTE: The schedule/holidays can b used to either turn the unit On/Off or to cycle the unit from Occupied to Unoccupied.
The following table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using
the UP or DOWN buttons):
Main Status Screen = Clock/Scheduler
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Clock
Date: Actual Date MM/DD/YY -
Hour: (Military Time) Actual Time 00:00-23:59 Hrs:Min
Day Actual Day (Calculated) MTWTFSS -
Scheduler Number of Schedules 0 0-7 -
Scheduler
(This Screen is repeated
based on number of
Schedules Selected)
Schedule #: Actual Value 1-7 -
Time On: 00:00 00:00-23:59 Hrs:Min
Time Off: 00:00 00:00-23:59 Hrs:Min
Days Enabled: none MTWTFSS -
Holidays Number: 0 0-16 Days
Holidays
(Screen will show only
if 1 or more holidays are
selected)
Holiday 1 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 2 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 3 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 4 Start - Stop 00/00-00/00 1/1-12/31 Days
Holidays
(Screen will show only
if 5 or more holidays are
selected)
Holiday 5 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 6 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 7 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 8 Start - Stop 00/00-00/00 1/1-12/31 Days
Holidays
(Screen will show only
if 9 or more holidays are
selected)
Holiday 9 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 10 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 11 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 12 Start - Stop 00/00-00/00 1/1-12/31 Days
Holidays
(Screen will show only if
13 or more holidays are
selected)
Holiday 13 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 14 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 15 Start - Stop 00/00-00/00 1/1-12/31 Days
Holiday 16 Start - Stop 00/00-00/00 1/1-12/31 Days
Clock
DST: (daylight Savings Time) On On / Off -
Transition Time: 60 0-60 Minute
Start: (Date placement in month) Last Last, 1st-4th -
Start: (Day) Sunday Mon-Sun Day
Start: (Month) March Jan-Dec Month
Start: (Time) 2:00 0-12 Hour
End: (Date placement in month) Last Last, 1st-4th -
End: (Day) Sunday Mon-Sun Day
End: (Month) October Jan-Dec Month
End: (Time) 3:00 0-13 Hour

16
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Input/Output Sub Menu
The following table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using
the UP or DOWN buttons):
Main Status Screen = Input/Output
SCREEN NAME PARAMETER DESCRIPTION INPUT FACTORY VALUE RANGE UNITS
a. Analog Inputs
Return Air U1 Actual Value - °F / °C
Indoor coil U2 Actual Value - °F / °C
Outside coil U3 Actual Value - °F / °C
Coax Water out (Schoolmate units) U3 Actual Value - °F / °C
Supply Air U4 Actual Value - °F / °C
CO2 (optional) U5 Actual Value 0-2000 ppm
OA Humidity (Optional) U6 Actual Value 0-100 %RH
Inside Humidity (Optional) U7 Actual Value 0-100 %RH
OA Temperatures (Optional) U8 Actual Value - °F / °C
Temp. adjust (Optional) U10 Actual Value - °F / °C
LL Pressure (Optional) U11 Actual Value 0-650 PSI
Faceless Wall Stat
Serial Probe 128 Actual Value - -
Temperature - Actual Value - °F / °C
Humidity - Actual Value 0-100 %
Dew Point - Actual Value - °F / °C
b. Digital Inputs
Condensate Float DI1 Actual Value Closed or Open -
Freeze Stat DI2 Actual Value Closed or Open -
Supply Fan DI3 Actual Value Closed or Open -
Outdoor fan DI4 Actual Value Closed or Open -
Filter DI5 Actual Value Closed or Open -
Occupied (Optional) DI6 Actual Value Closed or Open -
Low pressure DI7 Actual Value Closed or Open -
High Pressure DI8 Actual Value Closed or Open -
c. Relay Outputs
Supply Fan High NO1 Actual Value ON/OFF -
Hot Gas Re-Heat (Optional) OUT 2 Actual Value ON/OFF -
Reversing Valve (Heatpump) OUT 3 Actual Value ON/OFF -
Compressor OUT 4 Actual Value ON/OFF -
Compressor CCS OUT 5 Actual Value ON/OFF -
Supply Fan NO6 Actual Value ON/OFF -
Electric Heat 1 (Optional) NO7 Actual Value ON/OFF -
Electric Heat 2 (Optional) NO8 Actual Value ON/OFF -
Outside Air damper NO9 Actual Value ON/OFF -
Exhaust Fan (Optional) NO10 Actual Value ON/OFF -
ERM Wheel (Optional) NO11 Actual Value ON/OFF -
Exhaust Vent Fan NO12 Actual Value ON/OFF -
Outside Air Vent Fan NO13 Actual Value ON/OFF -
d. Analog Output
Economizer (Optional) Y1 Actual Value 0-10 VDC
Hotwater (Optional) Y2 Actual Value 0-10 VDC
Outdoor Fan (ClassMate Units) Y3 Actual Value 0-10 VDC
ERM Fans (Optional) Y4 Actual Value 0-10 VDC
Baseboard Heat (Optional) Y5 Actual Value 0-10 VDC
Coax Water Valve (Schoolmate Units) Y5 Actual Value 0-10 VDC

17
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Data Logger Sub Menu
To access contents of the Data Logger menu simply
press the ENTER button. The most recent alarm will be
displayed on the screen. The upper bar will display the
time and date of the most recent alarm. The second
line will indicate the alarm generated. The rest of the
page will contain readings of certain variables at the
time of the alarm.
Use the UP button to navigate through previous alarms
and the DOWN button to navigate to the most recent.
The alarms are chronologically stored and the most
recent alarm will be the first displayed.
Main Status Screen = Data Logger Figure 18.1 Alarm Log
Board Switch Sub Menu
The Board Switch screen will indicate the current
devices connected to the pLAN network (Keypad and
pAD Wall Stat). In the screen below, the main controller
is on address 1.
The pCOOEM+ controller is factory defaulted to the
following for modules communiated with on the pLAN:
Main Status Screen = Board Switch Figure 18.2 Board Switch
●pCOOEM+ Controller: Address1
●Remote Wall Stat (pAD): Address 4
●Remote Display (pGD1): Address 32
In the situation that module addresses need to be set
up, the board address can be changed within the Board
Switch sub menu

18
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Programming the Remote Display Keypad to the Controller
Normally the Remote Display Keypad is addressed by
the controller, however in the situation that the Remote
Display address is required to be set up, the following
procedure applies:
Figure 19.1 Display Address Screen
1. Connect the handheld remote display keypad to the
controller and then power up the unit.
2. By simultaneously pressing and holding ENTER +
UP + DOWN, the display will show the Display Address
screen (Figure 19.1) to the right.
3. Pressing UP will change the I/O board address to
the controller address 1. Press ENTER to display the
terminal configuration screen (Figure 19.2) to the right:
4. Press ENTER again. The display will show the terminal
configuration screen (Figure 19.3) to the right:
5. To select Termiinal 1, press ENTER until the cursor is
underneath Trm1 00 Pr (PRIVATE).
6. Pressing UP or DOWN will change the to the required
value to 32.
7. To set as Private or Shared, press ENTER until the
cursor is underneath the Pr symbol.
8. Pressing UP or DOWN will change the Pr to Sh
(SHARED) symbol. Pr for Normal.
9. Press ENTER until the cursor is underneath the NO.
10. Pressing UP or DOWN will change the NO to YES.
Press ENTER and the display is programmed.
Figure 19.2 Terminal Configuration
Figure 19.3 Terminal Configuration

19
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Service Sub Menu
The following table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using
the UP or DOWN buttons):
Main Status Screen = Service = Information
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
INFORMATION
Code (Name of Program) Actual Value - -
Ver. (Software Version) & Date Actual Value - MM/DD/YY
Bios Version & Date Actual Value - MM/DD/YY
Boot Version & Date Actual Value - MM/DD/YY
INFORMATION
PAGE 2
pCO Type pCOOEM+ - -
FLASH Actual Value - Kb
RAM Actual Value - Kb
FLASH 2 Actual Value - Kb
FLASH 3 Actual Value - Kb
Memory Type Actual Value - Mb
T Memory Writes Actual Value - -
Main Cycle Actual Value - Cycles/s
INFORMATION
(Power Cycle Status)
PAGE 3
Last Off Time Actual Value - MM/DD/YY
HH:MM:SS
Last On Time Actual Value - MM/DD/YY
HH:MM:SS
Length Time Off Actual Value - Days/Hrs./Min.
Information
Control Power Status Voltage Actual Value - Voltage
Current Actual Value - Current
Information
EVO
Fw Version: Actual Value - -
Service Version: Actual Value - -
Information
Main Status Screen = Service = Working Hours
Working Hours
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
Run Hours
Unit ON Run Hours Actual Value 0-32,767,999 Hours
Number of Starts Actual Value 0-32,767,999 Starts
Run Hours Supply Fan Actual Value 0-32,767,999 Hours
Supply Fan High Actual Value 0-32,767,999 Hours
Run Hours Compressor Actual Value 0-32,767,999 Hours
Comp. CSS: Actual Value 0-32,767,999 Hours
Run Hours Exhaust Fan Actual Value 0-32,767,999 Hours
Run Hours ERM Wheel Actual Value 0-32,767,999 Hours
Run Hours Exhaust Air Vent Fan: Actual Value 0-32,767,999 Hours
Outside Air Vent Fan: Actual Value 0-32,767,999 Hours

20
MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Service Sub Menu (continued)
The following table describes the menu parameters (NOTE: changes in shading indicates change to next screen by using
the UP or DOWN buttons):
Main Status Screen = Service = BMS Configuration
BMS Configuration
SCREEN NAME PARAMETER DESCRIPTION FACTORY VALUE RANGE UNITS
BMS Configuration
(Modine Control System Supports the Following
Protocols:
Lon
BACnet IP/Eth
BACnet MSTP)
BMS CARD Protocol: BACnet MSTP
Lon
BACnet IP\Eth
BACnet MSTP
PCOLOAD
MODBUS EXT
MODBUS
MODEM
CAREL
-
BMS PORT 2 Protocol PCOLOAD
Lon
BACnet IP\Eth
BACnet MSTP
PCOLOAD
TH-TUNE
MODBUS EXT
CAREL
-
BMS Configuration (Page 2)
(Select “YES” to Change BACnet IP/Eth and
BACnet MSTP Settings) Termconf PlugIn? No No
Yes -
BMS Configuration
Enable heartbeat: No No/Yes
Thresholds: 5 0-999 -
Timeout: 300s 0-9999 s
Period: Actual Value 0-999.9 s
BMS Configuration If BMS Offline turn unit: Off On/Off -
MSTP SETUP
(Screen only Visible When BACnet MSTP is
Selected and Termconf Plugin is Enabled.)
Instance 0 0-4194999 -
Baud rate N/A
N/A
9600
18200
36400
76800
bps
MAC Address: 0 0-127 -
MaxMasters: 0 0-127 -
MaxInfoFrames: 0 0-99 -
TCP/IP Setup
(Screen Only Visible when BACnet IP/Eth is
Selected and Termconf Plugin is Enabled.)
Instance: Actual Value 0-99,000 -
IP: Actual Value 0.0.0.0-255.255.255.255 -
SubNet: Actual Value 255.0.0.0-255.255.255.0 -
Gateway: Actual Value 0.0.0.0-255.255.255.255 -
TCP/IP Setup (Page 2)
(Screen Only Visible when BACnet IP/Eth is
Selected and Termconf Plugin is Enabled.)
DNS 1 Actual Value 0.0.0.0-255.255.255.255 -
DNS 2 Actual Value 0.0.0.0-255.255.255.255 -
Type Actual Value IP, Ethernet -
BACnet Read/Write Function: Read Read/Write -
Update? No No/Yes -
Bms Configuration
Heartbeat Select: No No/Yes -
Heartbeat Delay: 120s 0-999 seconds
Heartbeat Active: Actual Value No/Yes -
This manual suits for next models
4
Table of contents
Other Modine Manufacturing Control System manuals

Modine Manufacturing
Modine Manufacturing 5H104766 User manual

Modine Manufacturing
Modine Manufacturing Varsity User manual

Modine Manufacturing
Modine Manufacturing Airedale Sentinel User manual

Modine Manufacturing
Modine Manufacturing pGD-t User manual

Modine Manufacturing
Modine Manufacturing Atherion MPR User guide