The Venting Graph: P42DF*
Measure the vertical height from the replace hearth to the centre of
the termination and the horizontal run from the replace ue collar to
the wall ange of the termination. Plot on the Venting Graph Figure 10
or 10a with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall ange of the vent termination is 144", this would be
an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 36" and the horizontal
run to the wall ange of the vent termination is 84", this would not
be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the oor of the replace is 60" and
the horizontal run to the wall ange of the vent termination is 144",
this would not be an acceptable installation.
Figure 10b. Top Vented, wall mounted installation with 1 elbow (1
one 90° bend). The vent run must comply with Venting Graph for
Top vent, wall mounted terminations, Figure 10 and 10a.
Figure 10d. Top Vented, wall mounted Multi-elbow installation. See
Venting Graph for Top vent, wall mounted terminations, Figure 10.
Section 3-3-1: VENTING LAYOUT: Wall mounted termination.
Selection of components and details of venting layout should adhere
to the following guidelines:
Vent terminations must not be recessed in walls or siding.
All through-the–wall terminations within 4’ of the replace must
have a Montigo Heat Shield (RHS101) installed. See Section
3-3-3.
All through-the-wall terminations beyond 4' of the replace must
have a Montigo Heat Shield (RHS8) installed. See Section 3-3-3.
Once the proposed venting layout has been determined refer to
Figure 10 or 10a to ensure the layout is acceptable.
Notes Wall Mounted Terminations: Top Vent
All measurements for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graph,
see Figure 10 or 10a.
Wall mounted Terminations
The following details are some possible congurations for Wall mounted
terminations. See below.
Solid Section
Flex Section
Hearth
30”min
15’foot Max.
RHS8 Heat
Shield
Termination
Exterior
Wall
8' MIN AT MAX
Horizontal
Figure 10. P42DF* LP Top Vent Venting Graph for wall mounted
terminations.
Figure 10a. P42DF* NG Top Vent Venting Graph for wall mounted terminations.
WARNING:
An inspection of the explosion relief appers and door MUST be
made prior to lighting the replace. A faulty seal on the door gasket ...
and/or explosion ports will result in products of combustion leaking
into the living space and may result in carbon monoxide poisoning.
12”
53”
A
C
B
If your installation does not fall
within the venting graph para-
meters, please contact Montigo
for Power Venting options.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
44”
40 1/2”
A
C
B
If your installation does not fall
within the venting graph para-
meters, please contact Montigo
for Power Venting options.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
RHS8 Heat
Shield
Termination
Hearth Exterior
Wall
40 1/2" Min. (NG)
Flex
Flex section
53 Min. (LP)
44" Min. (NG)
12 Min. (LP)
Page 11
P42DF* Indoor Gas Fireplace
XG0195 -030712
Installation