8.2 Checking the reference pressure.
The burner aeration is non-adjustable. The
appliance is preset to give the correct heat
input on Natural Gas at 20 mbar (8in w.g)
inlet pressure and no further adjustment is
necessary. The burner pressure should be
checked at the pressure test point located
at the side of the control unit (See figure
13). The pressure check should be carried
out using a calibrated pressure gauge after
removing the test point screw. The fire should be alight and the left hand control knob at
its fully anticlockwise setting (Maximum flame height). The pressure setting should be
within the limits shown on page 3 of this manual (Appliance data). After checking the
pressure, turn the fire off, remove the pressure gauge and replace the pressure test
sealing screw. Relight the fire and test all gas joints for soundness using a suitable leak
detection fluid.
9. FINAL REVIEW & SERVICING
Final Review
! Visually inspect the appliance. Clean off any marks incurred during installation.
! Advise the customer how to operate the appliance. Advise the customer that they
should read their Owner's guide before operating the fire and always follow the advice
in the section headed "Cleaning your stove".
!
Advise the customer that the top, front, sides and back of the appliance are working
surfaces and become very hot during use. Therefore care should be exercised,
particularly with the young, elderly or infirm.
!
Explain to the customer that the appliance has a flame failure device. Point out the
explanation of this system shown in the Owner Guide under "Operating your stove".
Advise that if the fire goes out for any reason wait at least three minutes before
relighting. Stress that if the monitoring system repeatedly shuts off the fire, the
appliance should be switched off and a specialist should be consulted.
!
Advise the customer that the door can be opened for cleaning the interior by using
the special key supplied. Stress that the door locking screw should be refitted afterwards
to prevent inadvertent opening when the stove is alight.
! Stress that no extra coals must be added over and above those supplied with the
appliance and that any replacements must only be the authorised spares. Warn that
ignoring this advice could cause incomplete clearance of the products of combustion
with consequent health hazards.
! Explain to the customer that when operating the stove for the first time, some
Page 16
INSTALLER GUIDE
Figure 13.