MPE SC100 User manual

SC100
SC100SC100
SC100
INSTRUCTION MANUAL
INSTRUCTION MANUALINSTRUCTION MANUAL
INSTRUCTION MANUAL
2464 Vulcan Road
Apopka, Florida 32703
Revision Date: 6-23-14
M
MM
MOTOR
OTOROTOR
OTOR
P
PP
PROTECTION
ROTECTIONROTECTION
ROTECTION
E
EE
ELECTRONICS, INC.
LECTRONICS, INC.LECTRONICS, INC.
LECTRONICS, INC.
Phone:
Website: (407) 299-3825
www.mpelectronics.com
Order from: C A Briggs Company; 622 Mary Street; Suite 101 - Warminster, PA 18974
Phone: 267-673-8117 - 800-352-6265 - Fax: 267-673-8118; E-Mail: Sales@cabriggs.com - www.cabriggs.com

ORDERING INFORMATION:
SC100 - XX
Product Type
Scale Range
05 = 11.5 Ft/H2O
10 = 23.1 Ft/H2O
15 = 34.6 Ft/H2O
APPLICATIONS:
• Duplex Pumping Stations that Control Liquid Level
• Pump Down (Empty a Tank) or Pump Up (Fill a Tank) - See note by Ordering Information below
SPECIFICATIONS:
Input Power: 120VAC +/- 10%, 7.8 VA max
Power for Analog Input: 24VDC+/- 1V, Transient Protected
Agency Approval: UL 508, CAN/CSA UL FILE #: E101681
Operating Temperature: -20 °C to +65 °C
Storage Temperature: -45 °C to +85 °C
Indicators: LED
Relay Outputs: 10A Resistive @ 120VAC
3.6A Inductive @ 120VAC
Level Analog Input: 4-20 mA, 250 Ohms Load
Transient Protected
Color: White with Blue Lettering
Enclosure Material: Aluminum
5psi Transducer used with: SC100-05
10psi Transducer used with: SC100-10
15psi Transducer used with: SC100-15
For Pump Up Applications (Fill a Tank)
add UP to Part No. after Scale Range
STANDARD FEATURES:
• Bar Graph Level Display - 30 segment LED
• All Level Settings may be viewed or changed from the front of the unit
• Level Input Source – Analog Level Input [4-20mA from Pressure Transducer]
May be used with 5, 10, or 15 psi Pressure Transducer when correct Scale Range is selected
See Ordering Information below
• Level Input Zero and Span Calibration
• 24VDC Power Supply for analog Level Input
• Phoenix style connectors used
• 2 Pump Call Relay outputs
• High Level and Low Level Alarm Relay outputs
• Duplex Alternation
• 10 second Power Up Delay – After a power interruption, the first pump is delayed by 10 seconds
• 5 second Lag Pump Delay – After lead pump call, lag pump call is delayed by 5 seconds
• 90 second Low Level Alarm Delay – After a power interruption, low alarm is delayed by 90 seconds
• Level Simulation – Automatically ends after 1 minute
1
STATION CONTROLLER SC100

VIEW OR CHANGE LEVEL SETTINGS
Menu:
To enter the menu press the Setting Select pushbutton once. To move in the menu from left to
right, press the Setting Select pushbutton again. To exit the menu, press the Setting Select
pushbutton once while at the right most end of the menu.
Viewing Settings:
When the menu indicator over one of the Level Setting potentiometers is on, the current setting will
be shown on the bar graph display.
Changing Settings:
When the menu indicator over one of the Level Setting potentiometers is on, the potentiometer may
be turned to adjust the setting.
Note: The Off setting should be adjusted first, and then adjust the Lead and Lag settings. The
Lead and Lag settings are prevented from being too close to the Off setting. If the Off setting is
moved too close to the Lead and Lag settings, the Lead and Lag settings will be shoved away from
the Off setting and away from what is set on their respective potentiometers.
LEVEL SIMULATION
Entering Level Simulation Mode:
To enter the Level Simulation mode press the Setting Select pushbutton until the “Level Simula.“
menu indicator is turned on. Note that the Level Display bar graph will initially show what the actual
level was prior to entering the Level Simulation Mode.
Changing the Simulated Level:
To change the simulated level, press the Increase or Decrease pushbuttons as desired. The pump
1 and 2 call relays, and the high and low level alarm relays will operate just as though the water
level were actually changing.
Exiting the Level Simulation Mode:
To exit the Level Simulation mode, press the Setting Select pushbutton once. Unless you wish to
view the Level Settings continue to press the Setting Select pushbutton until all of the menu indica-
tors are off. If the controller is left in the Level Simulation mode, a one minute timer will time out
and return the controller to normal operation. The one minute timer is reset whenever the Increase
or the Decrease pushbutton is pressed.
2

LEVEL DISPLAY
Scale Range:
The Level Display Scale shows level in feet of water. In order for the level to be accurate, the cor-
rect pressure transducer must be used with the controller. The following shows which pressure
transducer goes with the different controllers:
Level Input Calibration:
The analog Level Input on the controller is calibrated at the factory and will not normally need to be
adjusted. If minor adjustments are required, they can be made using the Span and Zero calibration
potentiometers accessible from the front of the unit. When either the Span or Zero calibration is
changed, the other will be affected and should be re-checked and calibrated if necessary, until both
are correct.
Zero Calibration:
First – Use an analog calibration device to apply a 4.0mA signal to the Level Input.
(Alternate Method – Raise the pressure transducer (or bubbler tube) out of the water.)
Next – Adjust the Zero Potentiometer until the lowest bar graph segment is on steady.
Note: The lowest segment will blink when the Zero calibration is too low. It will also blink
if the 4-20mA signal is absent or connected backwards.
Span Calibration:
First – Use an analog calibration device to apply a 20.0mA signal to the Level Input.
(Alternate Method – Place the pressure transducer (or bubbler tube) under a know depth
of water.)
Next – Adjust the Span Potentiometer until the highest bar graph segment is on steady.
(Alternate Method – Adjust the Span Potentiometer until the display reads the known
depth of water covering the pressure transducer (or bubbler tube).)
Note: The highest segment will blink when the Span calibration is too high.
3
Scale Range
11.5 Ft/H2O
23.1 Ft/H2O
34.6 Ft/H2O
Part Number
SC100-05
SC100-10
SC100-15
Transducer Calibration
20mA at 5 psi
20mA at 10 psi
20mA at 15 psi

4
ELECTRICAL CONNECTION DIAGRAM
SUBMERSIBLE PRESSURE TRANSDUCER CONNECTION
BUBBLER SYSTEM BS2000 CONNECTION
LEVEL INPUT CONNECTION DIAGRAMS

5
CONTROL SCHEMATIC EXAMPLE – DUPLEX With 24V Float Backup

ENCLOSURE MECHANICAL LAYOUT
6

7
PANEL CUTOUT
Not Printed to Scale. Do Not Use as a Template.
Table of contents
Other MPE Controllers manuals
Popular Controllers manuals by other brands

AbsolutAire
AbsolutAire LX-4 user guide

Smartgen
Smartgen HAT600R Series user manual

Emerson
Emerson EC3-X33 Operating instruction

Disaster Area Designs
Disaster Area Designs DMC.micro PRO manual

Vanderbilt
Vanderbilt ACT365 VCU Installation and operating instructions

Diodes
Diodes ZETEX ZXLD1370EV2 user guide