MS Electronics E315 User manual

today, tomorrow and in the future
E315
E315/24V
Product Guide
Programmable Extension Timer
today, tomorrow and in the future
mselectronics.co.uk

Issue 3.0 2
Product Overview
The E315 is a single-shot extension mer designed to control plant equipment such as heang, lighng or
aircondioning systems outside of normal occupancy hours. A voltage-free changeover relay output capable of
switching loads of up to 16A, 250V AC is acvated for a congurable Extension me period. This enables equipment
to be immediately acvated then automacally deacvated at the correct me in the future without the user being
present, also bypassing dicult reprogramming procedures oen encountered when used in conjuncon with
convenonal control equipment. The E315 is an extremely user-friendly device with touch-sensive pushbuons, LED
displays and fully adjustable mings, providing simple yet powerful control of devices outside of occupancy hours.
Eecve energy control and benecial me-management of personnel is obtained through the fully congurable
“Extension” period which is adjustable from 0.5 hours to 99 hours (steps of 0.5 hours up to 9.5, then steps of 1 hour
thereaer). A maximum limit for the Extension me can be programmed, ensuring the end-user cannot generate an
extension longer than the authorised user allows.
When not in use, the extension mer enters a power-saving standby mode in an eort to reduce its energy usage.
Product Wiring
IMPORTANT: ensure all electrical connecons are isolated before commencing any work on the unit.
1. Power to the extension mer is provided via the power supply terminals (see Figure 1). The 230V version accepts
a worldwide universal voltage of between 85V and 265V (50/60Hz). The 24V version accepts a wide input range
of 18V to 28V DC or AC (50/60Hz).
2. A voltage-free relay contact output capable of switching loads of up to 16(8)A 250V AC is provided by the
extension mer.
• The Common “COM” terminal is connected to the Normally Open “NO” terminal during the extension period
and is disconnected at all other mes.
Installaon
1. IMPORTANT: ensure all electrical connecons are isolated before commencing any work on the unit.
2. The E315 is designed to be mounted into a 20mm (or deeper) single-gang UK paress or back box.
3. Connect the wiring to the terminal blocks on the extension mer as shown in Figure 1 (or any suitably appropriate
form).
4. Secure the E315 into the paress box using the two supplied M3.5 screws.
5. Fit the supplied screw covers to complete the installaon.
Figure 1
Typical wiring example

Issue 3.0 3
• To remove the screw covers without damage, use an adhesive puy such as blu-tack as an aid.
Operaon
Operaon Modes
The E315 has 3 operang modes:
Standby:
Power-saving mode where the dimmed LED displays show “0” on all digits.
Seng Up:
Bright LED displays with the currently selected display blinking. This mode is used to choose the desired Extension
period.
Running:
Bright LED displays show the me remaining with the “Running” LED blinking. The “Output On” LED illuminates
when the output is acve. Once the extension is complete the unit will revert back to Standby mode.
Conguraon:
The “Running” and “Output On” LEDs blink alternately. This mode is used to congure the maximum Extension
period that the user will be allowed to select up to in the Seng Up mode.
Selecng and Running an Extension
1. Press the “Adjust” buon to wake up the mer from Standby mode (enters Seng Up mode).
•The “Extension” display will start blinking to show it is selected.
2. Repeatedly press or hold down the “Adjust” buon to count up to the required Extension period.
3. Hold down the “Start” buon to start the extension running (enters Running mode).
•The “Running” LED will start blinking to show the extension is running and the “Output On” LED will illuminate to show
the output is acve.
4. To cancel an acve extension at any me, hold down the “Start” buon.
•The unit will go back to the Seng Up mode.
Notes - Seng Up mode
1. If no buon is pressed for 8 seconds, the unit will revert back to Standby mode.
2. If you accidentally go past the desired extension period, you must either:
•Keep going unl the period reaches the end and wraps back to the beginning.
•Wait for the unit to automacally go back into Standby by not pressing any buon for 8 seconds.
Conguring the Maximum Selectable Extension
1. NOTE: Conguraon mode can only be entered once within the rst 2 minutes of the extension mer powering up.
2. From the Standby mode, hold down the “Start” buon.
•The “Running” and “Output On” LEDs will start blinking alternately to show that Conguraon mode has been entered.
The display will also show the current maximum extension that was previously stored.
3. Select the desired maximum extension period by using the “Adjust” buon, the same as described in step 2 of Selecng and
Running an Extension.
4. Hold down the “Start” buon to save the new maximum extension period.
•The new value will be permanently stored and the unit will revert back to Standby mode. Conguraon mode cannot be
entered again unless the unit is power-cycled.
Notes - Conguraon Mode
1. If you accidentally select the Conguraon mode and do not want to save any changes, you must either:
•Overwrite the maximum with the same original value.
•Wait 2 minutes without pressing any buons so the unit automacally reverts back to Standby mode. All changes will be
lost.
•Reset the extension mer by powering it o and on again. All changes will be lost.
Technical Specicaon
Power supply:
230V version: 85 - 265V AC 50/60Hz (worldwide universal)
24V version: 18 - 28V DC or AC (50/60Hz)
Output switch rang:
16(8)A, 250V AC
Output switch type:
SPNO relay (volt-free)
Output terminals:
3.3mm2 solid/stranded wire, rising clamp
Operang temperature:
-10°C to +40°C
Suitable for:
20mm (or deeper) single-gang UK paress or back box
Ingress protecon rang:
IP40
Guarantee:
3 Years
Weight:
95g
Dimensions:
86mm x 86mm x 26.9mm
2

IMPORTANT INSTALLATION NOTICE
The installaon of this product should be carried out in accordance with the latest IEE
wiring regulaons and all wiring completed by a qualied electrician.
Technical Support
For further help or informaon on this and the other products in the MS Electronics range
visit www.mselectronics.co.uk or call 0333 666 1176.
Alternavely, email techsupport@mselectronics.co.uk
Addional copies of this product guide can be downloaded from our website.
Product Warranty
MS Electronics guarantees all their products against manufacturing defects for
3 years from the purchase date. If your product is found to be faulty, MS Electronics will,
at their discreon, repair or replace the product free of charge.
Note
Any modicaon or damage to the outer casing of the product, as well as any
damage to the product due to abuse or incorrect wiring may invalidate the guarantee.
t: 0333 666 1176/01708 448566
MS Electronics reserves the right to alter or change this specicaon without prior noce.
This manual suits for next models