netvox R718AB User manual

Mod:R718AB
Wireless Temperature And Humidity Sensor
Wireless TemperatureAnd Humidity Sensor
R718AB
User Manual
Copyright© Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX
Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole
or in part, without written permission of NETVOX Technology. The specifications are subject to change
without prior notice.

1
Table of Content
1. Introduction .......................................................................................................................2
2. Appearance ........................................................................................................................2
3. Main Features....................................................................................................................3
4. Set up Instruction............................................................................................................... 4
5. Data Report........................................................................................................................6
6. Installation.......................................................................................................................10
7. Important Maintenance Instruction.................................................................................12

2
1. Introduction
R718AB, mainly used to detect the temperature and humidity. It collects data over LoRa network and
sends it to devices to be shown, fully compatible with LoRa protocol.
LoRa Wireless Technology:
LoRa is a wireless communication technology dedicated to long distance and low power consumption.
Compared with other communication methods, LoRa spread spectrum modulation method greatly
increases to expand the communication distance. Widely used in long-distance, low-data wireless
communications. For example, automatic meter reading, building automation equipment, wireless
security systems, industrial monitoring. Main features include small size, low power consumption,
transmission distance, anti-interference ability and so on.
LoRaWAN:
LoRaWAN uses LoRa technology to define end-to-end standard specifications to ensure interoperability
between devices and gateways from different manufacturers.
2. Appearance
Built-in temperature and humidity sensor
Indicator
Function Key

3
3. Main Features
⚫Compatible with LoRa protocol.
⚫2 x ER14505 AA lithium batteries(3.6V/ section)
⚫Capable to detect the ambient temperature and humidity
⚫Simple and easy installation
⚫IP rating IP65
⚫Compatible with LoRaWANTM Class A
⚫Frequency hopping spread spectrum
⚫Configuration parameters can be configured via a third-party software platform, data can be read and
alerts can be set via SMS text and email (optional)
⚫Applicable to third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne
⚫Improved power management for longer battery life
⚫Battery Life:
⁻Please refer to web: http://www.netvox.com.tw/electric/electric_calc.html
⁻At this website, users can find battery life time for variety models at different configurations.
1. Actual range may vary depending on environment.
2. Battery life is determined by sensor reporting frequency and other variables.

4
4. Set up Instruction
On/Off
Power on
Insert batteries. (users may need a flat blade screwdriver to open)
Turn on
Press and hold the function key for 3 seconds till the green indicator flashes once.
Turn off
(Restore to factory setting)
Press and hold the function key for 5 seconds till green indicator flashes for 20
times.
Power off
Remove Batteries.
Note
1. Remove and insert the battery; the device is at off state by default.
2. On/off interval is suggested to be about 10 seconds to avoid the interference of
capacitor inductance and other energy storage components.
3. At 1st -5th second after power on, the device will be in engineering test mode.
Network Joining
Never joined the network
Turn on the device to search the network to join.
The green indicator stays on for 5 seconds: success
The green indicator remains off: fail
Had joined the network
(not at factory setting)
Turn on the device to search the previous network to join.
The green indicator stays on for 5 seconds: success
The green indicator remains off: fail
Fail to join the network
(when the device is on)
First two mins: wake up every 15 seconds to send request.
After two mins: enter sleeping mode and wake up every 15 minutes to send request.
Note: Suggest to remove batteries if the device is not used to save power.
Suggest to check the device verification information on the gateway
or consult your platform server provider.

5
Function Key
Press and hold for 5 seconds
Restore to factory setting / Turn off
The green indicator flashes for 20 times: success
The green indicator remains off: fail
Press once
The device is in the network: green indicator flashes once and sends a report
The device is not in the network: green indicator remains off
Sleeping Mode
The device is on and in the
network
Sleeping period: Min Interval.
When the reportchange exceeds setting value or the state changes: send a data report
according to Min Interval.
The device is on but not in
the network
First two mins: wake up every 15 seconds to send request.
After two mins: enter sleeping mode and wake up every 15 minutes to send request.
Note: Suggest to remove batteries if the device is not used.
Suggest to check device verification on gateway.
Low Voltage Warning
Low Voltage
3.2V

6
5. Data Report
Data report configuration and sending period are as following:
Min Interval
(Unit:second)
Max Interval
(Unit:second)
Reportable Change
Current Change≥
Reportable Change
Current Change<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval
The device will immediately send a version packet report along with an uplink packet including temperature,
humidity and battery voltage.
The device sends data in the default configuration before any configuration is done.
Default setting:
MaxTime : Max Interval = 15 min = 900s
MinTime : Min Interval = 15 min = 900s
BatteryChange: 0x01 (0.1V)
TemperatureChange:0x0064 (1℃)
HumidityChange:0x064 (0.1%)
Note:
The device report interval will be programmed based on the default firmware which may vary.
The interval between two reports must be the minimum time.
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver
http://www.netvox.com.cn:8888/page/index to resolve uplink data.

7
Example of Report configuration
FPort:0x07
Bytes
1
1
Var(Fix =9 Bytes)
CmdID
DeviceType
NetvoxPayLoadData
CmdID–1 bytes
DeviceType–1 byte –Device Type of Device
NetvoxPayLoadData–var bytes (Max=9bytes)
(1)Command Configuration:
MinTime = 1min、MaxTime = 1min、BatteryChange = 0.1v、TemperatureChange = 1℃、
HumidityChange = 1%
Downlink:0113003C003C0100640064 003C(Hex) = 60(Dec) 0064(Hex) = 100(Dec)
Response:
8113000000000000000000(Configuration success)
8113010000000000000000(Configuration failure)
(2)Read Configuration:
Downlink:0213000000000000000000
Response:
8213003C003C0100640064(Current configuration)
Description
Device
CmdI
D
Device
Type
NetvoxPayLoadData
Config
ReportReq
R718AB
0x01
0x13
MinTime
(2bytes Unit:s)
MaxTime
(2bytesUnit:s)
Battery
Change
(1byte
Unit:0.1v)
Temperature
Change
(2byte
Unit:0.01℃)
Humidity
Change
(2byte
Unit:0.01%)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
Battery
Change
(1byte
Unit:0.1v)
Temperature
Change
(2byte
Unit:0.01℃)
Humidity
Change
(2byte
Unit:0.01%)

8
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e.
BatteryVoltageChange=0.1V
MaxTime MaxTime
Sleeping(MinTime) Sleeping(MinTime)
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration
regardless BatteryVoltageChange value.
Example#2 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e.
BatteryVoltageChange= 0.1V.
MaxTime
Sleeping(MinTime) sleeping sleeping sleeping
0H 15th M 30th M 45th M 1H
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
REPORTS 3.6V
Wakes up and
collects data
REPORT 3.6V
Wake up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V

9
Example#3 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e.
BatteryVoltageChange= 0.1V.
MaxTime
sleeping sleeping ...
0H 15th M 30th M 45th M 1H 1H 10th M 1H 25th M
1H 40th M 1H 55th M 2H 10th M
Notes :
1) The device only wakes up and performs data sampling according to MinTime Interval. When it is
sleeping, it does not collect data.
2) The data collected is compared with the last data reported. If the data variation is greater than the
ReportableChange value, the device reports according to MinTime interval. If the data variation
is not greater than the last data reported, the device reports according to MaxTime interval.
3) We do not recommend to set the MinTime Interval value too low. If the MinTime Interval is too
low, the device wakes up frequently and the battery will be drained soon.
4) Whenever the device sends a report, no matter resulting from data variation, button pushed or
MaxTime interval, another cycle of MinTime/MaxTime calculation is started.
Wakes up and
collects data
REPORTS 3.6V
Wakes up and collects data
3.5V |3.5-3.6|=0.1
REPORTS 3.5V
Wakes up and
collects data
3.5V
Does not report
Wakes up and
collects data
3.5V
Does not report
Wakes up and
collects data
3.5V
Does not report
Wakes up and
collects data 3.5V
Does not report
Wakes up and
collects data
3.6V
Does not report
Users push the button,
REPORTS 3.5V.
Recalculate MaxTime.

10
6. Installation
This product comes with waterproof function.
When using it, the back of it can be adsorbed on the iron surface, or the two ends can be fixed to the wall
with screws.
1. The Wireless Temperature and Humidity
Sensor sensor(R718AB) has a built-in magnet
(see Figure 1 below). When installed, it can be
attached to the surface of an object with iron
which is convenient and quick.
To make the installation more secure, use screws
(purchased) to secure the unit to a wall or other
surface (see Figure 2 below).
Note: Do not install the device in a metal
shielded box or in an environment with other
electrical equipment around it to avoid affecting
the wireless transmission of the device.
The figure shows the scene where the temperature and
humidity sensor (R718AB) is applied in the refrigerator.
It can also be applied to the following scenarios:
⚫Restaurant (refrigerator or freezer)
⚫Shopping mall supermarket (freezer)
⚫Engine room
⚫Environmental monitoring
⚫Smart city and intelligent building
⚫Storage and transportation of food and medicine
⚫Flowers and other perishable foods
⚫Wall or logistics refrigerator
When it is necessary to detect temperature or humidity.
4. When the temperature and humidity detected by
R718AB is compared with the last reported values,
when the temperature change is exceeded 1°C (default)
or the humidity change is exceeded 1%(default),it will
report current values.

11
Note:
Please do not disassemble the device unless it is required to replace the batteries.
Do not touch the waterproof gasket, LED indicator light, function keys when replacing the batteries.
Please use suitable screwdriver to tighten the screws (if using an electric screwdriver, it is recommended
to set the torque as 4kgf) to ensure the device is impermeable.
Note on battery use:
Because the passivation of the ER battery electrode surface is an inherent characteristic of lithium thionyl
chloride batteries, before using the ER14505 3.6V 2400mAh lithium thionyl chloride battery, the user can
use a 33 ohm resistor to activate the battery for 1 minute to actively eliminate the battery hysteresis.

12
7. Important Maintenance Instruction
Kindly pay attention to the following in order to achieve the best maintenance of the product:
•Keep the device dry. Rain, moisture, or any liquid, might contain minerals and thus corrode
electronic circuits. If the device gets wet, please dry it completely.
•Do not use or store the device in dusty or dirty environment. It might damage its detachable parts
and electronic components.
•Do not store the device under excessive heat condition. High temperature can shorten the life of
electronic devices, destroy batteries, and deform or melt some plastic parts.
•Do not store the device in places that are too cold. Otherwise, when the temperature rises to
normal temperature, moisture will form inside, which will destroy the board.
•Do not throw, knock or shake the device. Rough handling of equipment can destroy internal
circuit boards and delicate structures.
•Do not clean the device with strong chemicals, detergents or strong detergents.
•Do not apply the device with paint. Smudges might block in the device and affect the operation.
•Do not throw the battery into the fire, or the battery will explode. Damaged batteries may also
explode.
All of the above applies to your device, battery and accessories.
If any device is not working properly, please take it to the nearest authorized service facility for repair.
Other manuals for R718AB
1
Table of contents
Other netvox Temperature Controllers manuals

netvox
netvox R720C User manual

netvox
netvox R720A User manual

netvox
netvox R718A User manual

netvox
netvox R720E User manual

netvox
netvox R718PB14 User manual

netvox
netvox R718A01 User manual

netvox
netvox RA0716 User manual

netvox
netvox R718EC User manual

netvox
netvox R718AD User manual

netvox
netvox R711A User manual
Popular Temperature Controllers manuals by other brands

KMC Controls
KMC Controls STE-6010 installation guide

Honeywell
Honeywell T775C user guide

Full Gauge Controls
Full Gauge Controls MICROSOL II plus manual

KELD
KELD KLT11BB-WXYZ Specification and operating instructions

Tekmar
Tekmar tN2 house control 400 Installation and operation manual

AURATON
AURATON 200 RT owner's manual