Table 10: TEC-N2 Features
Feature Description
Control
Algorithm
Over time, the TEC-N2 learns how long it takes the system to meet the load. If the system
can change the room temperature quickly, the TEC-N2 allows the thermostat to drift further
from setpoint before starting the equipment. If the system takes a longer period of time to
change the room temperature, the TEC-N2 does not allow the temperature to drift as far
from setpoint. The TEC-N2 also takes into account the minimum on/off times.
The 2-minute on/off time allows the equipment to cycle more frequently at smaller
differentials than the 4-minute on/off time.
For multistage applications, the TEC-N2 does not bring on the next stage of cooling or
heating if it knows that the system can change the temperature by 6° in one hour or 1° in
10 minutes. To verify thermostat operation, force the next stage on by changing the setpoint
by more than 2° (see the Verifying Proper Thermostat Operation section).
Clock Terminals
CLK1 - CLK2
The TEC-N2 thermostat accepts a contact closure for a clock/timer to allow the use of
alternate or setback heating and cooling setpoints in place of a BAS.
When the contact is open, the day icon ( ) appears, and the thermostat adjusts to the day
setpoint. When the contact is closed, the night icon ( ) appears, and the thermostat adjusts
to the night setpoint. Pressing the DAY/NIGHT button when the thermostat is in night mode
will switch the thermostat to day mode, even if a clock/timer is used. The clock (CLK)
contacts on the thermostat are in parallel with the thermostat DAY/NIGHT button and will
change to the next command given by the clock. Therefore, if the thermostat is in night mode
(contacts closed) and the thermostat is switched to the day mode from the front panel, then
at the next clock control time, the thermostat will stay in the day mode. When the contacts
close again the following night, the thermostat will switch to night setpoints.
Temporary
Occupied with
Keyboard Lock
When in night mode, select this feature by pushing DAY/NIGHT button to put TEC-N2 in
1-hour timed override to occupied setpoints.
Remote Sensor When using a remote sensor (NT-IDS), the TEC-N2 internal sensor is disabled. If two to
six remote sensors are connected, then they can be used for temperature averaging.
Outdoor/Duct
Temperature
Sensor
There are two separate analog inputs on the TEC-N2, which are the room sensor and a
duct or outdoor air sensor on a slave bus. The duct temperature displays when the
OUTDOOR button is pushed. On the GE22-N2, the outdoor/duct sensor simply is a
monitor of temperature. On the HP32-N2, the outdoor temperature provides a low
temperature lockout (see Displaying Outdoor/Duct Air Temperature under the
Commissioning section later in this document). Both of these can be displayed on the LCD
at the Metasys system. The outdoor temperature can be a global N2 override from a
single sensor.
Power Failures or
N2 Failures
In the event of a power failure, or ten minutes after an N2 communication loss, the
N2 Address Push FAN and MODE buttons simultaneously and hold for ten seconds to view address.
thermostat retains the last setpoints. When power is restored, it remains in normal operation
and does not require resetting. If power was lost when the thermostat was in night mode, it
returns to day mode.
N2 Dial Module
(NDM)
There are three binary input points to cause a COS that triggers the remote NDM to dial out.
Binary inputs 1 and 3 (wrench and filter) are general purpose inputs powered by 24 VAC or
22-30 VDC. Binary input 2 is the temperature alarm binary data point that will cause a COS
if the zone temperature is moving away from the setpoint after 45 minutes. The COSs