Regular checks
Your HRV unit requires minimal maintenance after commis-
sioning. However, it is recommended that you check your
installation regularly.
If something unusual occurs, messages about the malfunc-
tion, in the form of different alarm texts, appear in the main
product display.
NOTE
Always switch off the power and wait until the
fans have stopped before opening ERS 30.
CLEANING THE VENTILATION DEVICES
The building’s ventilation
devices should be cleaned
regularly with, for example, a
small brush to maintain the
correct ventilation.
The device settings must not
be changed.
NOTE
If you take down more than one ventilation device
for cleaning, do not mix them up.
REPLACING THE AIR FILTER
The filters in ERS 30 are of a type that should not be cleaned;
they have to be replaced instead. These must be replaced
regularly, although how often depends of factors such as
the amount of particles in the ventilation air. Test to find
out what is most appropriate for your installation.
Caution
The efficiency of the installation can be reduced
by a dirty air filter.
In the main product’s display, you will receive a reminder to
check the filters. The factory setting for the reminder is
every three months, although the countdown begins again
if the power to the main product is interrupted.
1. Switch off the main product.
2. Remove the filters.
3. Check the condition of the filters andreplace if needed.
4. Carry out assembly in reverse order.
Even if the filters look clean, dirt collects in them and this
affects the efficiency of the filters. For this reason, replace
them after approx. 1 years. New filters can be ordered via a
dealer for NIBE.
Exhaust air filter: Coarse 65%
Supply air filter: ePM1 55%
Supply air filter Exhaust air filter
CHECK THE WATER LOCK FOR CONDENSATION
WATER
The water seal must be checked at least once a year, ideally
in the autumn.
The water seal is located outside ERS 30. Contact your in-
staller if you are unsure of where to find it.
No condensation water is generated in the HRV unit during
the warm period of the year and the water seal will dry out.
During the colder parts of the year, ERS 30 can produce
several litres of condensation water every day. If the con-
densation outlet is not working, this may cause water dam-
age inside the home.
The water seal must not dry out during this part of the year,
because air will be drawn into the HRV unit due to the neg-
ative pressure in the unit, which will then prevent the con-
densation water from running out.
1. Check that the condensation drain and the water seal
are not clogged with dirt.
2. Pour approx. one litre of water into the water seal.
3. Check that the water runs through unobstructed.
7Chapter 3 | Maintenance of ERS 30NIBE ERS 30
Maintenance of ERS 30