www.hvacr-drives.com Tech Support: (800) 893-23216
Action Detail
Before power-up Ensure:
• The Drive Enable signal is not given (terminal 29)
• Run signal is not given
• Motor is connected
Power-up the
drive
Verify that Open Loop mode is displayed as the drive powers up.
If the mode is incorrect see section 5.7 of the H300 Installation
and Commissioning Guide.
Ensure that the drive displays ‘Inhibit’
Enter motor
nameplate details
Enter:
• Motor rated voltage in Pr 00.018 (V) - check if or connection
• Motor rated speed in Pr 00.019 (rpm)
• Motor rated current in Pr 00.020 (A)
• Motor rated frequency in Pr 00.021 (Hz)
Set frequency Enter:
• Minimum frequency in Pr 00.010 (Hz) recommend 20 Hz
• Maximum frequency in Pr 00.011 (Hz) recommend 60 Hz
Set acceleration
/ deceleration
rates
Enter:
• Acceleration rate in Pr 00.012 (s to Pr 01.006)
• Deceleration rate in Pr 00.013 (s to Pr 01.006)
Autotune The drive is able to perform either a stationary or a rotating
autotune. The motor must be at a standstill before an autotune
is enabled. A rotating autotune should be used whenever
possible so the measured value of power factor of the motor is
used by the drive.
A rotating autotune will cause the motor to accelerate up to 2/3
base speed in the direction selected regardless of the reference
provided. Once complete, the motor will coast to a stop. The
Drive Enable signal must be cycled before the drive can be made
to run at the required reference. The drive can be stopped at any
time by removing the run signal or removing the Drive Enable.
A stationary autotune can be used when the
motor is loaded and it is not possible to uncouple
the load from the motor shaft. A stationary
autotune measures stator resistance and transient
inductance of the motor and values relating to
deadtime compensation from the drive. These are
required for good performance in vector control
modes. A stationary autotune does not measure
the power factor of the motor so the value on the
motor nameplate must be entered into Pr 05.010.
• A rotating autotune should only be used if the motor is
uncoupled. A rotating autotune rst performs a stationary
autotune before rotating the motor at 2/3 base speed in the
direction selected. The rotating autotune measures the power
factor of the motor.
• To perform an autotune:
Set Pr 00.024 = Basic for a stationary autotune or set Pr 00.024 =
Improved for a rotating autotune
• Close the Drive Enable signal (terminal 29). The drive will
display ’Ready’.
• Press the green “hand” button. The upper row of the display
will ash ’Auto Tune’ while the drive is performing the
autotune.
• Wait for the drive to display ’Ready’ or ‘Inhibit’ and for the
motor to come to a standstill.
• Remove the Drive Enable from the drive.
Save Parameters
• Select ‘Save Parameters’ in Pr mm.000 (alternatively enter a
value of 1000 in Pr mm.000) and press the red reset button or
toggle the reset digital input.
Run Drive is now ready to run.
Open Loop Startup
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55 I.cl F C 40 s S1
°
VHzmin -1 kW cosA
230
400
50 14452.200.80 8.50
4.90
CN = 14.5Nm
240
415
50 14452.200.768.50
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
I.E.C 34 1(87)