Nittan EV-ABS User manual

Technical Manual: EV-ABS - 000011 (Changes are subject to DCRN)
Section 1 - INTRODUCTION
The EV-ABS analogue addressable base sounder for indoor use is a
part of the evolution addressable range of devices.
EV-ABS gives system designers a new, low profile designed sounder,
whilst giving installers reduced installation time with the sounder’s
wide cable access entry and rising clamp terminals.
16 different tone options can be selected on the sounder, each of
them having one main alarm tone and a separate alert tone.
Activating the main alarm tone overrides the alert tone.
Section 2 - CONFIGURATIONS
The low current analogue addressable sounder EV-ABS can be
configured in two ways.
As a sounder base to an Evolution detector, the EV-ABS is fitted with
a STB4-EV-AB base.
EV-ABS can also be used as a stand-alone ceiling or wall mounted
sounder, available with an option of either a red or a white
cap/plate depending on your fire system requirements.
Installation and address setting is easily accomplished as there is a
large address window especially cut out of the base area of the
STB4-EV-AB enabling the address to be set without the need to
remove the base from the sounder.
Section 3 - OPERATION
The EV-ABS is connected directly on the detector line as all other
Nittan Evolution detectors and devices.
The control equipment must be capable of controlling and operating
the EV-ABS base sounder. If in doubt, please check with the panel
manufacturer for compatibility confirmation.
CONTENTS:-
Section 1
Introduction Page 2
Section 2
Configurations Page 2
Section 3
Operation Page 2
Section 4
Technical
Specification Page 3
Section 5
Dimensions Page 4
Section 6
Connection Page 4
Section 7
Address Setting Page 5
Section 8
Volume Page 5
Section 9
Tone Configuration Page 5
Section 10
Disposal Page 6
Section 11
ROHS Compliance
Statement Page 6
Ref No: 000011 Date: 16.04.09 Issue: 7
• evolution • EV-ABS • addressable base sounder instruction manual
2
www.acornfiresecurity.com
www.acornfiresecurity.com

Technical Manual: EV-ABS - 000011 (Changes are subject to DCRN)
Section 4 - TECHNICAL
SPECIFICATION
Ref No: 000011 Date: 16.04.09 Issue: 7
• evolution • EV-ABS • addressable base sounder instruction manual
3
Model Name EV-ABS
Application Type A, indoor use
Part Number F16N82010
Product range Evolution Addressable
Address setting 8-way DIP Switch
Available separately: Part Number:
Detector base STB4-EV-AB F03N84020
Red Cover VCT-03-CPR F06N82411
White Cover VCT-03-CPW F06N82410
Operating Voltage 20-38VDC
Nominal Voltage 34VDC
Current Consumption:
Quiescent 350 µA
Alarm, low 3mA
Alarm, high 6mA
Operating Temperature -10ºC to +55ºC
Storage Temperature -20ºC to +60ºC
Relative Humidity RH95% Non-condensing
IP Rating IP21C
Weight 91 g
Primary materinal Staroy PC/ABS VB-1202F
UL94 V-0
Alternative material GE Plastics Cyclolac S157
UL94 V-0
Dimensions:
EV-ABS Ø114mm, H 28mm
EV-ABS/STB4-EV-AB Ø114mm, H40mm
Tone Types 15, see tone table
(3 tones are certified)
Volume Settings Low/High
Frequence Range 440-3000 Hz
Sound Pressure @1m:
Alarm, Low/High Volume (Tone 1) 79/82 dBA
Note 1
Alert, Low/High Volume (Tone 10) 79/82 dBA
Note 1
Certified To Standard EN54-3:2001
(Ceiling mounted)
CPD Number CE 0832-CPD-0541
Note 1 : See document ‘T-EVABS-SPLREF-001’ for reference sound pressure
level measurements.
www.acornfiresecurity.com
www.acornfiresecurity.com

Technical Manual: EV-ABS - 000011 (Changes are subject to DCRN)
Section 5 - DIMENSIONS
Section 6 - CONNECTION
Ref No: 000011 Date: 16.04.09 Issue: 7
• evolution • EV-ABS • addressable base sounder instruction manual
4
EV-ABS with
red/white cover
EV-ABS with
STB4-EV-AB
Detector
base
www.acornfiresecurity.com
www.acornfiresecurity.com

Technical Manual: EV-ABS - 000011 (Changes are subject to DCRN)
Section 7 - ADDRESS SETTING
To set the address of the device, set the address switch by adding
up the numbers on the left or right side. For example to set
address 24, set switch 4 and 5 to the ‘ON’ position. Switch 4 gives
you 8 and setting switch 5 adds 16 which gives the address 24. In
the example to the left, the address is set to 49 (1 + 16 + 32).
Section 8 - VOLUME
To set the volume, place the link in high or low volume position.
Section 9 - TONE CONFIGURATION
To set the sound pattern, set the tone selection switch according
to the table below. In the example to the left, tone 13 is selected
as switch 1 and 2 is on and switch 3 and 4 is off.
Ref No: 000011 Date: 16.04.09 Issue: 7
• evolution • EV-ABS • addressable base sounder instruction manual
5
Tone Alarm Alert SW1 SW2 SW3 SW4
1 Standard alarm tone. 750Hz/1000Hz alternating, 0.5s for each tone 10 ON ON ON ON
2 Warble tone, general use. 850-950Hz sweep at 9Hz 10 OFF ON ON ON
3 Sweep 1s (UK). 800Hz to 970Hz sweep over 1s, repeating 10 ON OFF ON ON
4 French fire tone. 440Hz for 400ms, 554Hz for 100ms, repeating 10 OFF OFF ON ON
5 German DIN tone. 1200Hz to 500Hz sweep over 1s, repeating 10 ON ON OFF ON
6 Dutch tone. 500Hz to 1200Hz over 3.5s, 0.25s gap, repeating 10 OFF ON OFF ON
7 Pulsed tone 1s on, 1s off at 750Hz 10 ON OFF OFF ON
8 Continuous, 750Hz 10 OFF OFF OFF ON
9 Continuous, 1000Hz 10 ON ON ON OFF
10 Pulsed tone 1s on, 1s off at 1000Hz 10 OFF ON ON OFF
11 Alternating at 2250Hz for 0.5s, 3000Hz, for 3s 10 ON OFF ON OFF
12 Sweep 9Hz. 2250Hz to 3000Hz, repeating 10 OFF OFF ON OFF
13 Sweep 1Hz. 2250Hz to 3000Hz, repeating 10 ON ON OFF OFF
14 Continuous, 3000Hz 10 OFF ON OFF OFF
15 Pulsed tone 1s on, 1s off at 3000Hz 10 ON OFF OFF OFF
16 Silent (no sound) 10 OFF OFF OFF OFF
www.acornfiresecurity.com
www.acornfiresecurity.com

Technical Manual: EV-ABS - 000011 (Changes are subject to DCRN)
Section 10 - DISPOSAL
This symbol on the EV-ABS indicates that this product must not be
disposed of with household waste. Instead, it is your responsibility
to dispose of your waste equipment by handing it over to a
designated collection point for the recycling of waste electrical and
electronic equipment. The separate collection and recycling of your
waste equipment at the time of disposal will help to conserve
natural resources and ensure that it is recycled in a manner that
protects human health and the environment. For more information
about where you can drop off your waste equipment for recycling,
please contact your local city office or your household waste
disposal service.
Section 11 - ROHS COMPLIANCE
STATEMENT
(RoHS compliant and lead-free)
This product complies with the RoHS (Restriction of Hazardous
Substances) directive.
This product complies with the RoHS (Restriction of Hazardous
Substances) directive which restricts the use of six hazardous
materials in the manufacture of electronic and electrical
equipment.
This product complies with the European Union RoHS (Restriction
of Hazardous Substances) directive 2002/95/EC which restricts the
use of the following six hazardous materials in the manufacture
of electronic and electrical equipment.
• Lead (Pb)
• Hexavalant Chromium
• Mercury (Hg)
• Cadmium (Cd)
• Polybrominated biphenyls (PBB’s)
• Polybrominated diphenyl ethers (PBDE’s)
Ref No: 000011 Date: 16.04.09 Issue: 7
• evolution • EV-ABS • addressable base sounder instruction manual
6
www.acornfiresecurity.com
www.acornfiresecurity.com
Table of contents