MTR260C User Manual
Connection settings
Use Mekuwin program or Nokeval 6790 hand held programmer to configure the device. You can
download Mekuwin from Nokeval’s web site for free.
Communication settings for configuration:
Baud rate 9600
protocol SCL
address 0
Programming connector
Use RS232-POL or POL cable and POL – pin header adaptor to connect the device to PC’s serial
port or Nokeval 6790 hand held programmer. When the programming connector is connected the
device sends measurement data about three times per second. When the configuration connection
is open no measurement data is sent.
Menus
In submenu
Input submenu is reserved for factory settings.
Out submenu
Period
Number of periods between consecutive
transmissions. The minimum value for this
setting is two and maximum value is 127.
One period is approximately 2.7 seconds
(25 °C). The duration of a period depends on
temperature and varies from 1.5 to 3 seconds.
It is not recommended to set the period value
smaller than necessary because it has quite a
significant effect on battery life.
Period Nominal Transmission Interval
2 5 s
11 30 s
22 1 min
67 3 min
127 5 min 40 s
Programming connector