NORDAC SK 200E Manual Safety information
BU 0200 GB 3
N O R D A C SK 200E frequency inverters
Safety and operating instructions for
drive power converters
(as per: Low Voltage Directive 2006/95/EEC )
1. General
During operation, drive power converters may, depending on their
protection class, have live, bare, moving or rotating parts or hot
surfaces.
Unauthorised removal of covers, improper use, incorrect installation
or operation causes a risk of serious personal injury or material
damage.
Further information can be found in this documentation.
All transportation, installation, initialisation and maintenance work
must be carried out by qualified personnel (compliant with IEC
364, CENELEC HD 384, DIN VDE 0100, IEC 664 or DIN VDE 0110,
and national accident prevention regulations).
For the purposes of these basic safety instructions, qualified
personnel are persons who are familiar with the assembly,
installation, commissioning and operation of this product and who
have the relevant qualifications for their work.
2. Proper use in Europe
Drive power converters are components intended for installation in
electrical systems or machines.
When installed in machines, the drive power converter cannot be
commissioned (i.e. commencement of the proper use) until it has
been ensured that the machine meets the provisions of the EC
Directive 98/37/EEC (Machine Directive); EN 60204 must also be
complied with.
Commissioning (i.e. implementation of the proper use) is only
permitted if the EMC Directive (2004/108/EEC) is complied with.
The drive power converters meet the requirements of the Low
Voltage Directive 2006/95/EEC. The harmonized standards stated in
the Declaration of Conformity are used for the drive power
converters.
Technical data and information for connection conditions can be
found on the rating plate and in the documentation, and must be
complied with.
The drive power converters may only be used for the safety
functions which are described and for which they have been
explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must
be complied with.
4. Installation
The installation and cooling of the equipment must be implemented
according to the regulations in the corresponding documentation.
The drive power converters must be protected against
impermissible loads. Especially during transport and
handling, components must not be deformed and/or
insulation distances must not be changed. Touching of
electronic components and contacts must be avoided.
Drive power converters have electrostatically sensitive
components, which can be easily damaged by incorrect
handling. Electrical components must not be mechanically
damaged or destroyed (this may cause a health hazard!).
5. Electrical connections
When working on live drive power converters, the applicable
national accident prevention regulations must be complied
with (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according to
the applicable regulations (e.g. cable cross-section, fuses,
ground lead connections). Further information is contained
in the documentation.
Information about EMC-compliant installation – such as
shielding, earthing, location of filters and installation of
cables can be found in the drive power converter
documentation. These instructions must be complied with
even with CE marked drive power converters. Compliance
with the limiting values specified in the EMC regulations is
the responsibility of the manufacturer of the system or
machine.
6. Operation
Where necessary, systems where drive power converters
are installed must be equipped with additional monitoring
and protective equipment according to the applicable safety
requirements, e.g. legislation concerning technical
equipment, accident prevention regulations, etc.
The parameterisation and configuration of the drive power
converter must be selected so that no hazards can occur.
All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is disconnected from the
power supply, live equipment components and power
connections should not be touched immediately, because of
possible charged capacitors. Observe the relevant
information signs located on the drive power converter.
Further information can be found in this documentation.
These safety instructions must be kept in a safe place!

NORDAC SK 200E Manual Concerning this document
4 BU 0200 GB
Documentation
Designation: BU0200 GB
Part No.: 607 20 01
Device series: SK 205E, SK 215E, SK 225E, SK 235E
Device types: SK 2xxE-250-112-O ... SK 2xxE-750-112-O,
0.25 - 0.75kW, 1~ 100-120V, Output. 230V
SK 2xxE-250-123-A ... SK 2xxE-111-123-A, 0.25 - 1.1kW, 1~ 220-240V
SK 2xxE-250-323-A ... SK 2xxE-401-323-A, 0.25 - 4.0kW, 3~ 220-240V
SK 2xxE-550-340-A ... SK 2xxE-751-340-A, 0.55 - 7.5kW, 3~ 380-480V
Version list
Designation of
previous versions Software
Version Comments
BU 0200 GB, March 2009
Part No. 607 2001 / 1009
V 1.1 R1 First version based on BU 0500 DGB / 2008
BU 0200 GB, March 2010
Part No. 607 2001 / 1310
V 1.2 R0 Extensively revised version including:
general correction of errors, adaptation of section structure,
inclusion of parameters for software V 1.2
CSA-Filter (Section 2.4)
Incremental encoder connection (Section 2.8.3)
ATEX (Section 2.9)
Options (incl. detailed description of I/O extension) (Section 3)
Quick commissioning (5.1.1)
KTY-84 Temperature measurement (Section 5.3)
AS Interface (Section 5.4)
Publisher
Getriebebau NORD GmbH & Co. KG
Rudolf-Diesel-Str. 1 •D-22941 Bargteheide, Germany •http://www.nord.com/
Tel.: +49 (0) 45 32 / 401-0 •Fax +49 (0) 45 32 / 401-555

NORDAC SK 200E Manual Concerning this document
BU 0200 GB 5
Intended use of the frequency inverter
Compliance with the operating instructions is necessary for fault-free operation and the
acceptance of possible warranty claims. These operating instructions must be read before
working with the device!
These operating instructions contain important information about servicing. They must
therefore be kept close to the device.
SK 200E frequency inverters are devices for industrial and commercial plants for operating
three-phase asynchronous motors with squirrel-cage rotors. These motors must be suitable
for operation with frequency inverters. Other loads must not be connected to the devices.
SK 200E frequency inverters are devices for fixed installation on motors or in systems in the
vicinity of the motors to be operated. All details regarding technical data and
permissible conditions at the installation site must be complied with.
Commissioning (commencement of the intended use) is not permitted until it has been ensured
that the machine complies with the EMC Directive 2004/108/EEC and that the conformity of
the end product meets the Machinery Directive 2006/42/EEC (observe EN 60204).
©Getriebebau NORD GmbH & Co. KG, 2010

NORDAC SK 200E Manual
6 BU 0200 GB
1 GENERAL INFORMATION...................................................................................................... 9
1.1 Overview............................................................................................................ 10
1.2 Delivery.............................................................................................................. 11
1.3 Scope of supply................................................................................................. 11
1.4 Safety and installation information .................................................................... 12
1.5 Certifications...................................................................................................... 14
1.5.1 European EMC Directive........................................................................................14
1.5.2 Approval for UL and cUL ........................................................................................14
1.5.3 C-Tick labelling.......................................................................................................15
1.5.4 RoHS compliance...................................................................................................15
1.6 Nomenclature / type codes................................................................................ 16
1.6.1 Type codes / Frequency inverter - basic device......................................................16
1.6.2 Type codes / Adapter unit - frequency inverter.......................................................17
1.6.3 Type codes / Adapter unit - Technology Unit..........................................................18
1.6.4 Type codes / Optional modules ..............................................................................19
1.7 Version with protection class IP55 / IP66.......................................................... 20
2 ASSEMBLY AND INSTALLATION ....................................................................................... 21
2.1 Installation and assembly.................................................................................. 21
2.1.1 Mounting the adapter unit.......................................................................................22
2.1.2 Adapters for Different Motors..................................................................................23
2.1.3 Installation of the SK 200E .....................................................................................24
2.1.4 Optional locations for the "SK TI4-…" adapter unit.................................................25
2.2 Dimensions: SK 200E........................................................................................ 26
2.2.1 Power rating / Motor size........................................................................................26
2.2.2 SK 200E mounted on motor ...................................................................................27
2.2.3 SK 200E Wall-mounting..........................................................................................28
2.3 Brake resistor (BR)............................................................................................ 29
2.3.1 Internal brake resistor SK BRI4-…..........................................................................29
2.3.2 External brake resistor SK BRE4-….......................................................................30
2.3.3 External brake resistor dimensions.........................................................................30
2.3.4 Brake resistor, electrical data..................................................................................31
2.4 Voltage limitation filter SK CIF........................................................................... 32
2.4.1 General information................................................................................................32
2.4.2 Type code...............................................................................................................32
2.4.3 Installation ..............................................................................................................33
2.4.4 Connection plan......................................................................................................33
2.4.5 Technical data ........................................................................................................34
2.5 Wiring guidelines............................................................................................... 35
2.6 Electrical Connection......................................................................................... 36
2.7 Electrical connection of the power unit.............................................................. 37
2.7.1 Mains connections (X1 - L1, L2, L3, EARTH).........................................................38
2.7.2 Motor cable (X2 - U, V, W, earth)............................................................................39
2.7.3 Brake resistor connection (X2 - +B, -B) ..................................................................39
2.7.4 Electro-mechanical brake.......................................................................................40
2.7.5 Mains supply jumpers.............................................................................................40
2.7.6 Internal jumper wiring .............................................................................................41
2.8 Electrical connection of SK 200E control unit.................................................... 42
2.8.1 Control terminals, SK 2x5E versions ......................................................................43
2.8.2 Details of the SK 2x5E control connections............................................................44
2.8.3 Colour and contact assignments for incremental encoders (HTL)..........................47
2.9 ATEX Zone 22 for SK 2x5E............................................................................... 48
2.9.1 Modified SK 2x5E for compliance with Category 3D...............................................49
2.9.2 Options for ATEX Zone 22 3D................................................................................49
2.9.3 Maximum output voltage and torque reduction.......................................................52

Table of Contents
BU 0200 GB 7
2.9.4 Commissioning information.....................................................................................53
2.9.5 EC declaration of conformity...................................................................................54
2.10 Outdoor installation ..........................................................................................55
3 OPTIONS ................................................................................................................................56
3.1 Overview of optional modules............................................................................57
3.1.1 Overview of internal customer units SK CU4-… .....................................................57
3.1.2 Overview of external technology units SK TU4-…..................................................58
3.2 Installation of optional modules..........................................................................61
3.2.1 Installation of internal customer units SK CU4-…...................................................61
3.2.2 Installation of external technology units SK TU4-…................................................62
3.3 Control connections and configuration...............................................................64
3.4 Details of internal Customer Units SK CU4-…...................................................65
3.4.1 Mains Unit, SK CU4-24V-…....................................................................................65
3.4.2 Potentiometer Adapter, SK CU4-POT.....................................................................68
3.4.3 SK CU4-IOE-, I/O extension ...................................................................................70
3.4.4 PROFIBUS DP, SK CU4-PBR................................................................................76
3.4.5 CANopen, SK CU4-CAO.........................................................................................78
3.4.6 DeviceNet, SK CU4-DEV........................................................................................80
3.5 Details of external Technology Units SK TU4-…...............................................82
3.5.1 Adapter Unit SK TI4-TU-BUS /-NET.......................................................................82
3.5.2 Mains Unit, SK TU4-24V-…....................................................................................85
3.5.3 PotentiometerBox SK TU4-POT-….........................................................................86
3.5.4 I/O Extension, SK TU4-IOE, ...-M12 .......................................................................87
3.5.5 PROFIBUS DP, SK TU4-PBR, ...-M12 ...................................................................92
3.5.6 CANopen, SK TU4-CAO, ...-M12............................................................................96
3.5.7 DeviceNet, SK TU4-DEV, ...-M12.........................................................................100
4 SK 200E DISPLAYS AND CONTROL .................................................................................104
4.1 Overview of external control devices ...............................................................105
4.1.1 SimpleBox, SK CSX-3H........................................................................................106
4.1.2 ParameterBox SK PAR-3H...................................................................................111
4.1.3 ParameterBox parameters....................................................................................117
4.1.4 ParameterBox error messages .............................................................................119
5 COMMISSIONING, SK 200E................................................................................................122
5.1 Minimal configuration without options ..............................................................122
5.1.1 Quick commissioning............................................................................................123
5.1.2 DIP switch configuration........................................................................................125
5.1.3 Potentiometers P1 and P2 and diagnostic LEDs ..................................................127
5.2 Factory settings................................................................................................130
5.3 KTY84-130 connection.....................................................................................131
5.4 AS Interface......................................................................................................132
5.4.1 The bus system.....................................................................................................132
5.4.2 Features................................................................................................................132
5.4.3 Bus structure and technology................................................................................133
5.4.4 Commissioning of the AS Interface.......................................................................134
5.4.5 Technical data for AS interface.............................................................................137
5.4.6 Certificate..............................................................................................................138
6 PARAMETERISATION.........................................................................................................139
6.1 Parameterisation of frequency inverter SK 200E.............................................140
6.1.1 Operating displays................................................................................................142
6.1.2 Basic parameters (Frequency inverter).................................................................144
6.1.3 Motor data / characteristic curve parameters........................................................150
6.1.4 Control parameters...............................................................................................156
6.1.5 Control terminals...................................................................................................159
6.1.6 Additional parameters...........................................................................................176
6.1.7 Positioning ............................................................................................................188

NORDAC SK 200E Manual
8 BU 0200 GB
6.1.8 Information (Frequency inverter)...........................................................................189
6.2 Parameterisation of I/O - extension SK xU4-IOE-…....................................... 198
6.2.1 Basic parameters (I/O - extension).......................................................................198
6.2.2 Information (I/O - extension).................................................................................200
6.3 Parameter overview, User settings ................................................................. 202
6.3.1 Overview of frequency inverter parameters..........................................................202
6.3.2 Parameter overview, I/O extension.......................................................................215
7 OPERATING STATUS MESSAGES ................................................................................... 216
7.1 SimpleBox display........................................................................................... 217
7.2 Table of possible error messages ................................................................... 217
7.2.1 Table of possible frequency inverter error messages...........................................217
7.2.2 Table of possible error messages in the I/O extension module ............................224
7.3 Table of possible warning messages.............................................................. 225
7.4 Table of possible reasons for the operating status "Switch-on block"............. 227
8 TECHNICAL DATA.............................................................................................................. 228
8.1 General data Frequency inverter series SK 200E........................................... 228
8.2 General data for mains/setpoint modules........................................................ 229
8.3 Electrical data for frequency inverter............................................................... 230
8.3.1 Electrical data 1~115V..........................................................................................231
8.3.2 Electrical data 1~230V..........................................................................................232
8.3.3 Electrical data 3~230V..........................................................................................233
8.3.4 Electrical data 3~400V..........................................................................................235
8.3.5 Electrical data for UL certification .........................................................................237
9 ADDITIONAL INFORMATION............................................................................................. 240
9.1 Setpoint processing in the SK200E................................................................. 240
9.2 Process controller............................................................................................ 241
9.2.1 Process controller application example ................................................................241
9.2.2 Process controller parameter settings ..................................................................242
9.3 Electromagnetic compatibility.......................................................................... 243
9.4 EMC limit value classes................................................................................... 244
9.5 Reduced output power .................................................................................... 245
9.5.1 Increased heat dissipation due to pulse frequency...............................................245
9.5.2 Reduced overcurrent due to time..........................................................................246
9.5.3 Reduced overcurrent due to output frequency......................................................247
9.5.4 Reduced output current due to mains voltage ......................................................248
9.5.5 Reduced output current due to the heat sink temperature....................................248
9.6 Operation with FI circuit breakers.................................................................... 249
9.7 System bus...................................................................................................... 249
9.8 Energy efficiency............................................................................................. 251
9.9 Motor data - characteristic curves ................................................................... 252
9.9.1 50Hz characteristic curve .....................................................................................252
9.9.2 87Hz characteristic curve (only 400V devices).....................................................254
9.9.3 100Hz characteristic curve (only 400V devices)...................................................255
9.10 Standardisation of setpoint/actual values...................................................... 256
9.11 Maintenance and servicing information......................................................... 257
9.12 Abbreviations in this Manual ......................................................................... 258
10 KEYWORD INDEX............................................................................................................. 259

1 General
BU 0200 GB Subject to technical alterations 9
1 General information
The NORDAC SK 200E is based on the tried and tested NORD platform. These devices feature a compact
design with optimum control characteristics.
These devices are provided with sensorless vector current control which in combination with asynchronous
three-phase motor types constantly ensures an optimised voltage-to-frequency ratio. This has the following
significance for the drive: Peak start-up and overload torques at constant speed.
This series of devices can be adapted to individual requirements by means of extension modules.
Due to the numerous setting options, these inverters are capable of operating all three-phase motors. The
power range is from 0.25kW to 7.5kW with an integrated mains filter.
This manual is based on the device software V1.2 R0 (see P707) of the SK 200E. If the frequency inverter
used has a different version, this may lead to some differences. If necessary, you can download the current
manual from the Internet (http://www.nord.com/).
For the SK 215E/225E/235E there are additional descriptions for functional safety
(BU 0230), the integrated AS interface (BU 0200, Section 5.4) and the positioning system (BU 0210). These
contain all the necessary additional information for start-up.
If a bus system is used for communication, a corresponding description (e.g. BU 0220 für PROFIBUS DP) is
provided, or this can be downloaded from the Internet (http://www.nord.com/).
Typically, this series of devices is installed directly on a three-phase asynchronous motor. Alternatively,
there are optional accessories for mounting the devices in the vicinity of the motor, e.g. on a wall or the
frame of a machine.
In the simplest configuration, even without an EEPROM, there is the possibility of setting all important
parameters via two potentiometers and eight DIP switches. LEDs are provided for the diagnosis of the
operating status. The use of a control module is therefore not absolutely necessary.
In order to gain access to all parameters, the internal RS232 PC interface (RJ12) can be used, or an
optional SimpleBox or ParameterBox may be used. In this case, the parameter settings which have been
changed by the operator are stored in the plug-in EEPROM. The EEPROM must then always remain
plugged in during operation.
ATTENTION
For changes to the frequency inverter software V 1.2 R0, the structure of individual
parameters has been changed for technical reasons.
(E.g.: up to version V 1.1 R2, (P417) was a simple parameter. As of version V 1.2. R0 this has been
divided into two arrays ((P417) [-01] and [-02]))
When plugging an EEPROM from a frequency inverter with an earlier software version into
a frequency inverter with a software version higher than V 1.2, the stored data is
automatically adapted to the new format. the new parameters are saved in the default
settings. Correct functioning is therefore ensured.
However, it is not permissible to plug an EEPROM with a software version higher
than V 1.2 into a frequency inverter with a lower software version, as this may lead to
a complete loss of data.

NORDAC SK 200E Manual
10 Subject to technical alterations BU 0200 GB
1.1 Overview
Features of the basic device SK 205E:
•High starting torque and precise motor speed control setting with sensorless current vector control
•Can be installed directly on, or near to the motor.
•Permissible ambient temperature range -25°C to 50°C (refer to the technical data)
•Integrated EMC mains filter for limit curve A Category C2 or C3 (not for 115V devices)
•Automatic measurement of the stator resistance for precise determination of motor data
•Programmable direct current braking
•External 24V supply voltage
•Integrated brake chopper for 4 quadrant operation, optional brake resistors (internal/external)
•4x digital inputs (DIN1-4), 1x digital output (DO1), temperature sensor input (TF+/TF-)
•Evaluation of an incremental encoder possible via digital inputs
•NORD System bus for connection of additional modules
•Electromagnetic brake control (MB+/MB-)
•Four separate online switchable parameter sets
•2x potentiometers and 8x DIP switches for minimal configuration
•LEDs for diagnosis
•RS232/RS485 interface via RJ12 plug
•Plug-in EEPROM data storage
•Integrated PosiCon positioning control (Manual BU 0210)
•CANopen absolute value encoder via the NORD System bus
Additional features of the SK 215E compared with the SK 205E:
•Integrated Safe Pulse Block (Manual BU 0230)
•However, only 3 free digital inputs available
Additional features of the SK 225E compared with the SK 205E:
•AS1, integrated AS interface (4I/4O)
Additional features of the SK 235E compared with the SK 205E:
•Integrated Safe Pulse Block (Manual BU 0230)
•However, only 3 digital inputs
•AS1, integrated AS interface (4I/4O)
NOTE: The features of the particular basic devices are different for the series
SK 205E/215E/225E/235E. These differences will be pointed out in the course of this
description, Section 2.8.1.

1 General
BU 0200 GB Subject to technical alterations 11
1.2 Delivery
Check the equipment immediately after delivery/unpacking for transport damage such as deformation or
loose parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
1.3 Scope of supply
Standard version: IP55 (optionally IP66)
Integrated brake chopper
Integrated EMC mains filter for limit curve A Category C2 or C3
(not for 115V devices)
Operating instructions as pdf file on CD ROM
including NORD CON, PC parameterisation software
Available accessories:Braking resistor, required for energy feedback Section 2.3
Matching RJ12 to SUB-D9 adapter cable to connection to a PC
SK CSX-3H, SimpleBox, 4-digit 7-segment LED display
SK PAR-3H, ParameterBox, plain text LCD display
Expansion module:
internal SK CU4-IOE, internal I/O extension
SK CU4-PBR, internal Profibus module
SK CU4-CAO, internal CANopen module
SK CU4-DEV, internal DeviceNet module
SK CU4-24V-123-B, internal 24V mains unit 1~ 230V
SK CU4-24V-140-B, internal 24V mains unit 1~ 400V
SK CU4-POT, potentiometer adapter: internal potentiometer/switch module
external SK TU4-IOE, external I/O extension
SK TU4-PBR, external Profibus module
SK TU4-CAO, external CANopen module
SK TU4-DEV, external DeviceNet module
SK TU4-24V-123-B, external 24V mains unit 1~ 230V
SK TU4-24V-140-B, external 24V mains unit 1~ 400V
SK TU4-POT-123-B, external 24V and potentiometer/switch module 1~ 230V
SK TU4-POT-140-B, external 24V and potentiometer/switch module 1~ 400V
SK TI4-TU-BUS or NET, connection unit TU4
SK TIE4-WMK-TU, wall-mounting kit TU4
NOTE: Details for the use of the relevant bus systems can be found in the applicable supplementary bus
manual.
> www.nord.com <

NORDAC SK 200E Manual
12 Subject to technical alterations BU 0200 GB
1.4 Safety and installation information
NORDAC SK 200E frequency inverters are devices for use in industrial high voltage systems and are
operated at voltages that could lead to severe injuries or death if they are touched.
•Installation and other work may only be carried out by qualified electricians and with the
device disconnected from mains. The operating instructions must always be available to
these persons and must be strictly observed.
•Local regulations for the installation of electrical equipment and accident prevention
must be complied with.
•The equipment continues to carry hazardous voltages for up to 5 minutes after being
switched off at the mains.
•For single phase operation (115/230V) the mains impedance must be at least 100μH for
each conductor. If this is not the case, a mains choke must be installed.
•For safe isolation from the mains, all poles of the supply cable to the frequency inverter
must be able to be disconnected.
•Even during motor standstill (e.g. caused by an electronic block, blocked drive or output
terminal short circuit), the line connection terminals, motor terminals and braking resistor
terminals may still conduct hazardous voltages. A motor standstill is not identical to
electrical isolation from the mains.
•Warning, with certain settings, the frequency inverter/motor can start up automatically
after the mains are switched on.
•The frequency inverter is only intended for permanent connection and may not be
operated without effective earthing connections which comply with the local regulations
for large leakage currents
(> 3.5mA). VDE 0160 stipulates the installation of a second earthing conductor or an
earthing conductor cross-section of at least 10 mm2.
•Normal FI-circuit breakers are not suitable as the sole protection for three-phase
frequency inverters if the local regulations do not permit a possible DC proportion in the
fault current. According to EN 50178 / VDE 0160, the FI circuit breaker must be an all-
current sensitive FI circuit breaker (type B).
•In normal use, NORDAC SK 200E frequency inverters are maintenance free. The
cooling surfaces must be regularly cleaned with compressed air if the ambient air is
dusty.
CAUTION
The heat sink and all other metal components can heat up to temperatures above 70°C.
When mounting, sufficient distance from neighbouring components must be maintained.
When working on the components, allow sufficient cooling time beforehand
Protection against accidental contact may need to be provided.
ATTENTION
DANGER TO LIFE!
The frequency inverter can carry voltages for up to 5 minutes after being switched off at the
mains. Inverter terminals, motor cables and motor terminals may carry voltage!
Touching open or free terminals, cables and equipment components can lead to severe injury
or death!
Work may only be carried out by qualified specialist electricians and with the electrical supply
to the equipment disconnected!

1 General
BU 0200 GB Subject to technical alterations 13
CAUTION
Children and the general public must be kept away from the equipment!
The equipment may only be used for the purpose intended by the manufacturer.
Unauthorised modifications and the use of spare parts and additional equipment which has
not been purchased from or recommended by the manufacturer of the device may cause fire,
electric shock and injury.
Keep these operating instructions in an accessible location and give them to all operators!
WARNING
This product intended for use in an industrial environment and is subject to sales restrictions
according to IEC 61800-3. In a domestic environment, this product can cause high frequency
interference, in which case the user may be required to take appropriate measures.
An appropriate measure would be the inclusion of a recommended mains filter.

NORDAC SK 200E Manual
14 Subject to technical alterations BU 0200 GB
1.5 Certifications
1.5.1 European EMC Directive
If the NORDAC SK 200E is installed according to the recommendations in
this instruction manual, it meets all EMC Directive, requirements, as per the
EMC product standard for motor-operated systems EN 61800-3. (see also
Section 9.3, Electromagnetic Compatibility [EMC].)
1.5.2 Approval for UL and cUL
UL Approval - File No. E171342
“Suitable For Use On A Circuit Capable Of Delivering Not More Than 100000 rms
Symmetrical Amperes, 120 Volts maximum (SK 2xxE-xxx-112), 240 Volts maximum
(SK 2xxE-xxx-323) or 500 Volts maximum (SK 2xxE-xxx-340) and when protected
by RK5 class or faster fuses as indicated.”
Suitable for use with mains with a maximum short circuit current of 100,000A rms (symmetrical), 120V
maximum (SK 2xxE-xxx112), 240V maximum (SK 2xxE-xxx323), or 500V maximum (SK 2xxE-xxx340), and
with protection with a Class RK5 or faster fuse as described in Section 8.3.5.
“Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms Symmetrical Amperes, 120 Volts
maximum (SK 2xxE-xxx-112), 240 Volts maximum (SK 2xxE-xxx-323) or 500 Volts maximum (SK 2xxE-xxx-340) and
when protected by Circuit Breaker (inverse time trip type) in accordance with UL 489”, current and voltage ratings
according to instruction manual.”
Suitable for use with mains with a maximum short circuit current of 10,000A rms (symmetrical), 120V
maximum (SK 2xxE-xxx112), 240V maximum (SK 2xxE-xxx323), or 500V maximum (SK 2xxE-xxx340) and
with protection via a UL Category DIVQ circuit breaker (thermal and electromagnetic trigger) in accordance
with UL 489. For current and voltage ratings, please refer to Section 8.3.5.
NORDAC SK 200E frequency inverters include protection against motor overload. Further technical details
can be found in Section 8.3.5.
cUL Approval - File No. E171342
“cUL only in combination with SK CIF-340-30 or SK CIF-340-60 for 380-500V models
and SK CIF-323-20 or SK CIF-323-40 for 3 phase 200-240V rated models”. The
recognized transient surge suppression filter board has to be connected between supply
and the input of the drive according to the instruction manual.
Remarks:
•cUL approval for 110-120V models provided without filter board”
cUL compliant, only in combination with SK CIF-340-30 orr SK CIF-340-60 for 380-500V types and
SK CIF-323-20 or SK CIF-323-40 for 200-240V types. The appropriate voltage limitation filter
(SK CIF xxx xx) must be connected between the power input and the frequency inverter (input) according to
the instructions for use.
Remarks:
•cUL conformity applies for 100-120V types without voltage limitation filter

1 General
BU 0200 GB Subject to technical alterations 15
“Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Symmetrical Amperes, 120 Volts
maximum (SK 2xxE-xxx-112), 240 Volts maximum (SK 2xxE-xxx-323) or 500 Volts maximum (SK 2xxE-xxx-340) and
when protected by RK5 class or faster fuses as indicated.”
Suitable for use with mains with a maximum short circuit current of 5,000A rms (symmetrical), 120V
maximum (SK 2xxE-xxx112), 240V maximum (SK 2xxE-xxx323), or 500V maximum (SK 2xxE-xxx340), and
with protection with a Class RK5 or faster fuse as described in Section 8.3.5.
“Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Symmetrical Amperes, 120 Volts
maximum (SK 2xxE-xxx-112), 240 Volts maximum (SK 2xxE-xxx-323) or 500 Volts maximum (SK 2xxE-xxx-340) and
when protected by Circuit Breaker (inverse time trip type) in accordance with UL 489”, current and voltage ratings
according to instruction manual.”
Suitable for use with mains with a maximum short circuit current of 5,000A (symmetrical), 120V maximum
(SK 2xxE-xxx112), 240V maximum (SK 2xxE-xxx323), or 500V maximum (SK 2xxE-xxx340) and with
protection via a UL Category DIVQ circuit breaker (thermal and electromagnetic trigger) in accordance with
UL 489. For current and voltage ratings, please refer to Section 8.3.5.
NORDAC SK 200E frequency inverters include protection against motor overload. Further technical details
can be found in Section 8.3.5.
1.5.3 C-Tick labelling
NORD SK 200E series frequency inverters fulfil all the relevant regulations in
Australia in New Zealand.
1.5.4 RoHS compliance
SK 200E series frequency inverters are designed to be RoHS compliant
according to Directive 2002/95/EU.
N 23134

NORDAC SK 200E Manual
16 Subject to technical alterations BU 0200 GB
1.6 Nomenclature / type codes
Unique type codes have been defined for the individual modules and devices. These provide individual
details of the device type and its electrical data, protection class, fixing version and special versions. A
differentiation is made according to the following groups:
Group Example of type code
Frequency inverter - basic device SK 205E-550-323-A (-C)
Adapter unit - frequency inverter SK TI4-1-205-1 (-C-WMK-1)
Connection unit - Technology Unit SK TI4-TU-BUS (-C-WMK-TU)
Optional modules SK TU4-CAO (-C-M12)
Extension modules SK TIE4-M12-CAO
1.6.1 Type codes / Frequency inverter - basic device
SK 205E-370-323-A (-C)
IP protection class: Standard = IP55, C = “coated“ IP66
Radio interference filter: O = without, A= Class A1, B = Class B1
Mains voltage: x12 = 115V, x23 = 230V, x40 = 400V
Number of mains phases: 1xx = single phase, 3xx = 3-phase
Digits before decimal point for power: 0= 0.xx, 1 = 0x.x0, 2 = 0xx.0
Device nominal power: 250 = 0.25kW, 370 = 0.37kW, ... 751 = 7.5kW
Device series: SK 205E, SK 215E, SK 225E, SK 235E
(...) Options, only implemented if required.
Electrical connections
Internal
(Power/Control)
Integrated
LEDs, potentiometers
and DIP switches
Device type plate

1 General
BU 0200 GB Subject to technical alterations 17
1.6.2 Type codes / Adapter unit - frequency inverter
SK TI4-1-205-1 (-C-WMK-1)
Wall mounting kit: -1 = S I + II, -2 = S III
IP protection class: Standard = IP55, C = “coated“ IP66
Mains connection: 1= 1~ 115/230V*, 3 = 3~ 230/400V*
Suitable device types: 205 =SK 205E, 215 = SK 215E,
225 = SK 225E, 235 = SK 235E
Size: 1= S I, 2 = S II, 3 = S III
Device series: SK TI4 = Adapter unit SK TI4
*) The voltage depends on the frequency inverter used;
please also refer to the technical data.
(...) Options, only implemented if required.
Pin numbering
AS-i cable
Electrical connections
Adapter unit
SK TI4-x-2xx-x-x

NORDAC SK 200E Manual
18 Subject to technical alterations BU 0200 GB
1.6.3 Type codes / Adapter unit - Technology Unit
SK TI4-TU-BUS (-C-WMK-TU)
Wall mounting kit: -1 = S I + II, -2 = S III
IP protection class: Standard = IP55, C = “coated“ IP66
Suitable device types: NET = optional net module (e.g. TU4-24V-… )
BUS = optional bus module (e.g. CANopen: TU4-CAO)
Group: TU =Technology unit
Device series: SK TI4 = Adapter unit SK TI4
(...) Options, only implemented if required.
Adapter unit
SK TI4-TU-xxx (-…)
Optional module
SK TU4-xxx (-…)
Electrical connections
Internal
(Control)

1 General
BU 0200 GB Subject to technical alterations 19
1.6.4 Type codes / Optional modules
For bus module or I/O extension
SK TU4-CAO (-C-M12)
M12 system connector: only TU4, alternative to terminals
IP protection class: Standard = IP55, C = “coated“ IP66
Option type: CAO = CANopen, PBR = Profibus,
DEV = DeviceNet, IOE = I/O extension
Option series: TU4 = external Technology Unit
CU4 = internal Customer Unit
(...) Options, only implemented if required.
For mains unit or potentiometer modules "PotentiometerBox"
SK TU4-24V-123-B (-C)
IP protection class: Standard = IP55, C = “coated“ IP66
Radio interference filter: B= Class B1
Mains connection: 123 = 1~ 230V*, 140 = 1~ 400V*
Option type: 24V = 24V mains unit, POT = potentiometer/switch module
Option series: TU4 = external Technology Unit,
CU4 = internal Customer Unit
*) The voltage depends on the frequency inverter used;
please also refer to the technical data.
(...) Options, only implemented if required.
Optional internal
Customer Unit, SK CU4-…
Optional external
Technology Unit, SK TU4-…

NORDAC SK 200E Manual
20 Subject to technical alterations BU 0200 GB
1.7 Version with protection class IP55 / IP66
NORDAC SK 200E frequency inverters and the additional modules are available in all sizes and in the
protection classes IP55 (standard) or IP66 (optional).
Protection class IP66 must always be stated when ordering!
There are no restrictions or differences to the scope of functions in either protection class. In order to
differentiate the protection classes, modules with protection class IP66 are given an extra “-C” (coated Æ
coated PCBs) in their type designation. e.g. SK 205E-750-340-A-C
IP55 version:
The IP55 version of the SK 200E is the standard version. Both versions (motor-mounted, mounted on the
motor or wall-mounted on a wall bracket) are available. In addition, all adapter units, technology units and
customer units are available for this version.
IP66 version:
In contrast to the IP55 version the IP66 version is a modified option. Both variants (motor-integrated, close
to motor) are also available. The modules available for the IP66 version (adapter units, technology units and
customer units) have the same functionalities as the corresponding modules for the IP55 version.
NOTE
The modules for the IP66 design are identified by an additional "-C" and are modified
according to the following special measures listed below.
Special measures:
Impregnated PCBs, painted housing
Diaphragm valve for pressure compensation on temperature changes.
Low pressure test
ÆA free M12 screw connection is required for low pressure testing. After successful testing, a
diaphragm valve is inserted here. This screw connection is therefore no longer available for
a cable gland.
If the frequency inverter is to be retro-fitted, i.e. the drive unit (inverter mounted on the motor) is not
completely obtained from NORD, the membrane valve is supplied in the bag supplied with the frequency
inverter. The valve must be correctly fitted on site by the plant constructor (Note: the valve must be mounted
as high as possible, in order to avoid contact with standing moisture (e.g.: standing moisture due to
condensation).
NOTE
For all versions, care must be taken that the cable and the cable gland are carefully
matched. This is the only way to ensure permanent compliance with the required protection
class.
Other manuals for SK 200E Series
4
Table of contents
Other Nord Drivesystems DC Drive manuals

Nord Drivesystems
Nord Drivesystems SK 500E Series Reference guide

Nord Drivesystems
Nord Drivesystems NORDAC FLEX SK 210E Series Reference guide

Nord Drivesystems
Nord Drivesystems SK 180E Series User manual

Nord Drivesystems
Nord Drivesystems SK 700E Series Instructions and recipes

Nord Drivesystems
Nord Drivesystems SK 500E User manual

Nord Drivesystems
Nord Drivesystems SK CU4-DEV Instructions and recipes

Nord Drivesystems
Nord Drivesystems SK 180E Series User manual

Nord Drivesystems
Nord Drivesystems NORDAC PRO User manual

Nord Drivesystems
Nord Drivesystems NORDAC LINK SK250E-FDS User manual

Nord Drivesystems
Nord Drivesystems SK 750E-751-323-A User manual