Olimpia electronics SLD-28/SP User manual

Page 1 from 3
Thank you for purchasing this product of Battery charging
Olympia Electronics. A European manufacturer. The battery charging is completely controled. In
this case, is achieved the perfect battery
GENERAL maintenance , as well as the elongation of its
The luminaire consists mainly from two parts, duration. When the battery has completely
the body, where all the electronics are located charged, it charges with a maintenance current.
and the lamp-head where the indication sign
and the high efficiency LEDs are located. Manual Test
The manual test can be conducted only if the
Maintained to non-maintained selection main power supply and the battery is
capability connected. By pressing the test button briefly
Power on the device and press continuously an operation test is initiated. During this test
the TEST button for 10 seconds, until the led period all indication LEDs are OFF.
strip turns off. Release the button and after a
short emergency test, the device operates as Automatic test
non-maintained. If you want to restore the This test includes all the operations that
previous condition (maintained operation), provide the manual test and is conducted
press continuously the TEST button for 10 automatically every 15 days. In order to be
seconds, until the led strip lights. Release the performed, the main power supply and the
button and after a short emergency test, the battery should be connected
device operates as maintained illumination
sign. Automatic Autonomous Test
The Automatic autonomous Test is conducted
Installation and measures the luminaire`s back up
To install the illumination sign follow the operation. This test is conducted automatically
installation instructions on page 2. every six months. In order to be performed, the
main power supply and the battery should be
Battery Cut-off connected (the battery should be charged). If
The luminaire enters in this operation when the the battery is not charged, the test is
mains power supply fails and battery has lost postponed until the battery is completely
its energy. During this operation the luminaire charged. If during the Automatic Autonomous
enters the idle state and battery consumption Test the luminaire’s duration is lower than the
is negligible, in order to be protected from deep named, then the battery must be replaced.
discharge.
SELF TESTING MAINTAINED ILLUMINATION SIGNS WITH WHITE LED’s
SLD-34/SP SLD-44/SP
SLD-28/SP
220-240V AC/50-60Hz
3h
24h
Overcharging and full discharging protection
Charge LED, Lamp LED, Fault LED
IP 30
3.6V/1.5Ah
85lm /85lm 105lm /105lm
9.5 VA9 VA
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838
0 40 C
o
to
up to 95%
Bayblend FR3010, aluminum, plexiglas
280x120x15mm
3 years (1 year for the battery)
790gr. 1110gr. 1580gr.
340x190x15mm 440x240x15mm
289x65x34mm
TECHNICAL CHARACTERISTICS
Operation temperature range
Relative humidity
Construction materials
External panel's dimensions
External unit’s dimensions
Typical weight
Guarantee
Mains voltage
Maximum power consumption
Battery (Ni-MH)
Recharging time
Battery protection
Indications
Minimum emergency duration
Degrees of cover protection
Produced in accordance with
Light source intensity (230V) / (emerg.)
High Quality European based Manufacturers
922044006_09_020

Page 2 from 3
ATTENTION!!
To disconnect the panel’s cables, you have to power off the mains power supply and
disconnect the battery.
Back Up Operation AC Charge
The autonomous duration of battery during On: Good charge current.
emergency mode is at least the one that is Οff: No battery (No charging current or
stated in the list of the first page. During disconnected battery).
emergency mode, a LED strip test is also
performed. Lamp fault
Οn: faulty LED strip.
Resetting Errors Off: Good LED strip.
Push the Test button for 5 seconds, to Fault
extinguish all the indicated LED errors. Οff: Battery OK.
Then the luminaire enters regular operation Blink (With AC Charge LED ON): Autonomy or
mode. low battery problem (the battery must be
replaced).
Indication LED status (with connected mains Blink (With AC Charge LED Off):
power supply). No charging current or disconnected battery.
3
1
4
Installation instructions
Remove the front plastic cover by unscrewing the two
retaining screws.
Pass the mains cables thru the hole of the plastic base.
Connect the live and the neutral wires to the terminal block
as shown in picture.
Mount the device by installing the included mounting
accessories in the holes or use the Α-3018 mounting
springs for suspended seiling mounting.
Install LED strip and batery connectors to the appropriate
PCB connectors.
Refit the front plastic cover by srewing the two
removed screws in step 1, and power on the device.
1
2
3
4
5
6
5
2
L
N
General:
1. Operations for installation, maintainance or testing must be done by authorized personel only.
2. The device must be connected to the mains power supply thru a fuse dependent by the total
amount of the line’s power load.
In case of battery or light source replacement, these must be replaced by parts of the same
type, by the manufacturer or by a competent person.
4
t i
in battery recycling points. Do not incinerate.
3.
. In case of inactive use for a period greater than 2 months, disconnect the battery by pulling
out the battery’s connector.
5. I s not allowed to discard batteries in to common trash bins, they must be discarded
only
922044006_09_020
NOTE!!
After finishing the installation you must power the device
at least for 24 hours for battery charging to perform the
named autonomy.

Page 3 from 3
In recess mounting installation the
required opening is 280 x 50 mm.
The material must withstand the
luminaires weight.
280
50
Placing the mounting springs
Α-3018
1
2
Place one part of the mounting spring
first and then the other one.
Place the edges of the mounting spring
as shown in picture.
1
2
Recess mounting
in suspended ceiling
A-3018
Mounting springs
for recess mounting
A-3018 mounting springs
Ceiling mounting Wall mounting
Mounting methods
When the device is mounted externally it can use the A-1028 mounting box.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
180: 3 hour duration
922044006_09_020
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the mains
power supply or not.
Non-Maintained operation: The luminaire lights its illumination source, only in power supply’s failure.
In case that the led strip must be replaced to ensure lumen output LED module can be
replaced only by a competent personnel.
This manual suits for next models
2
Other Olimpia electronics Lighting Equipment manuals
Popular Lighting Equipment manuals by other brands

Sanmak
Sanmak 8106A operation instruction

Satco
Satco NUCO 62-1580 Installation and safety instructions

Lithonia Lighting
Lithonia Lighting LEM04 instruction manual

Ocean Optics
Ocean Optics LS-450 Series manual

Chauvet Professional
Chauvet Professional COLORado Panel Q40 user manual

Svive
Svive SVIVERL01 manual